Caution

 The system shall be mounted in an ATEX/IECEx-certified

enclosure with a minimum ingress protection rating of at least IP54 as

defined in IEC/EN 60079-15.

Caution

 The enclosure must have a door or cover accessible only by the

use of a tool.

Wiring the NI 9866

The NI-9866 has one 9-pin male D-Sub connector that provides connections to a LIN

bus.
The port has two common pins (COM) that are internally connected to the module’s

isolated reference and serve as the reference ground for LIN signal. You can connect

the LIN bus reference ground to one or both COM pins. The port also has an optional

shield pin, SHLD, that you can connect to a shielded LIN cable. Connecting SHLD

may improve signal integrity and EMC performance in a noisy environment.

Caution

 You must use a UL listed ITE power supply marked LPS with the

NI-9866.

The NI-9866 requires an external power supply of +8 to +18 V to operate. Supply

power to the NI-9866 V

SUP

 pin from the LIN bus.

Note

 Power on V

SUP

 is required for LIN operation.

The NI-9866 pinout is listed in Table 1.

Connector

Pin

Signal Name

1

No Connection (NC)

2

NC

3

COM

4

NC

5

SHLD

6

COM

© National Instruments

5

NI-9866 Getting Started

Содержание NI 9866

Страница 1: ...NI 9866 Getting Started 2022 07 06...

Страница 2: ...esistors 6 NI 9866 Hardware Overview 6 NI 9866 Specifications 7 LIN Characteristics 7 Power Requirements 7 Physical Characteristics 7 Safety Voltages 8 Safety Compliance and Hazardous Locations Standa...

Страница 3: ...n Using the product in a manner not specified can damage the product and compromise the built in safety protection Attention Suivez toutes les instructions et respectez toutes les mises en garde de la...

Страница 4: ...e and Internationally The NI 9866 has been evaluated as Ex nA IIC T4 Gc equipment under DEMKO 07ATEX 0626664X and is IECEx UL 14 0089X certified Each NI 9866 is marked II 3G and is suitable for use in...

Страница 5: ...und for LIN signal You can connect the LIN bus reference ground to one or both COM pins The port also has an optional shield pin SHLD that you can connect to a shielded LIN cable Connecting SHLD may i...

Страница 6: ...nts and should be suitable for most applications Cable Lengths The maximum allowable cable length is 40 m per the LIN specification Number of LIN Devices The maximum number of devices on a LIN bus is...

Страница 7: ...xt Pwr Supply Required Rx Tx LIN Controller LIN LIN Transceiver Rx Tx COM Vsup _ NI 9866 Specifications The following specifications are typical for the range 40 C to 70 C unless otherwise noted LIN C...

Страница 8: ...to earth ground Withstand 1 000 V RMS verified by a 5 s dielectric withstand test Continuous 60 V DC Measurement Category I Safety Compliance and Hazardous Locations Standards This product is designe...

Страница 9: ...information about meeting these specifications Operating temperature IEC 60068 2 1 IEC 60068 2 2 40 C to 70 C Storage temperature IEC 60068 2 1 IEC 60068 2 2 40 C to 85 C Ingress protection IP40 Opera...

Страница 10: ...ct Certification section Note For EMC compliance operate this product according to the documentation CE Compliance 2014 34 EU Potentially Explosive Atmospheres ATEX Product Certifications and Declarat...

Страница 11: ...e RoHS NI RoHS NI RoHS ni com environment rohs_china For information about China RoHS compliance go to ni com environment rohs_china NI Services Visit ni com support to find support resources includin...

Отзывы: