Caution
Do not remove modules unless power has
been switched off or the area is known to be
nonhazardous.
Caution
Substitution of components may impair
suitability for Class I, Division 2.
Caution
For Division 2 and Zone 2 applications,
install the system in an enclosure rated to at least IP54
as defined by IEC/EN 60079-15.
Caution
For Division 2 and Zone 2 applications,
connected signals must be within the following limits.
...........................................................
Capacitance
0.2 µF max
Special Conditions for Hazardous Locations Use in
Europe and Internationally
The NI 9421 has been evaluated as Ex nA IIC T4 Gc equipment
under DEMKO Certificate No. 03 ATEX 0324020X and is
IECEx 14.0089X certified. Each NI 9421 is marked II 3G and
is suitable for use in Zone 2 hazardous locations, in ambient
temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI 9421
in Gas Group IIC hazardous locations, you must use the device in