Caution
Do not remove modules unless power has
been switched off or the area is known to be
nonhazardous.
Caution
Substitution of components may impair
suitability for Class I, Division 2.
Caution
For Division 2 and Zone 2 applications,
install the system in an enclosure rated to at least IP54
as defined by IEC/EN 60079-15.
Caution
For Zone 2 applications, install a protection
device between the Vsup and COM terminals on the
NI 9411. The device must prevent the input Vsup-to-
COM voltage from exceeding 42 V if a transient
overvoltage condition occurs.
Special Conditions for Hazardous Locations Use in
Europe and Internationally
The NI 9411 has been evaluated as Ex nA IIC T4 Gc equipment
under DEMKO Certificate No. 03 ATEX 0324020X and is
IECEx UL 14.0089X certified. Each NI 9411 is marked II 3G
and is suitable for use in Zone 2 hazardous locations, in ambient
temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI 9411
NI 9411 Getting Started Guide
|
© National Instruments
|
5