Table 1. 

Signal Descriptions

Signal

Description

TC

Thermocouple connection

TC+

Positive thermocouple connection

TC-

Negative thermocouple connection

NI 9212 Connection Guidelines

Make sure that devices you connect to the NI 9212 are compatible with the

module specifications.

The shield grounding methodology can vary depending on the application.

Refer to your thermocouple documentation or the thermocouple wire spool

to determine which wire is the positive lead and which wire is the negative

lead.

Minimizing Thermal Gradients

Changes in the ambient air temperature near the front connector or a thermocouple

wire conducting heat directly to terminal junctions can cause thermal gradients.

Observe the following guidelines to minimize thermal gradients and improve the

system accuracy.

Use small-gauge thermocouple wire. Smaller wire transfers less heat to or

from the terminal junction.

Run thermocouple wiring together near the TB-9212 to keep the wires at the

same temperature.

Avoid running thermocouple wires near hot or cold objects.

Minimize adjacent heat sources and air flow across the terminals.

Keep the ambient temperature as stable as possible.

Make sure the NI 9212 terminals are facing forward or upward.

Keep the NI 9212 in a stable and consistent orientation.

Allow the thermal gradients to settle after a change in system power or in

ambient temperature. A change in system power can happen when the

ni.com

10

NI-9212

Содержание NI 9212

Страница 1: ...NI 9212 2023 06 07...

Страница 2: ...arine Applications 8 Preparing the Environment 9 TB 9212 Pinout 9 NI 9212 Connection Guidelines 10 Minimizing Thermal Gradients 10 NI 9212 and TB 9212 with Screw Terminal Thermocouple Connection 11 NI...

Страница 3: ...nt in the system to determine the safety and EMC ratings for the entire system 2015 2016 National Instruments Corporation All rights reserved Refer to the National Instruments _Legal Information direc...

Страница 4: ...ts on the same module Caution Ensure that devices and circuits connected to the module are properly insulated from human contact Caution When module terminals are hazardous voltage LIVE 42 4 Vpk 60 VD...

Страница 5: ...ion system referred to as MAINS voltage MAINS is a hazardous live electrical supply system that powers equipment This category is for measurements of voltages from specially protected secondary circui...

Страница 6: ...tinuous 60 VDC Measurement Category I Withstand 1 000 Vrms Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as...

Страница 7: ...azardous Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous Caution Substitution of components may impair suitability for Class I Division 2 Cauti...

Страница 8: ...ith the regulatory requirements and limits for electromagnetic compatibility EMC stated in the product specifications These requirements and limits provide reasonable protection against harmful interf...

Страница 9: ...r filtered power and input output ports In addition take precautions when designing selecting and installing measurement probes and cables to ensure that the desired EMC performance is attained Prepar...

Страница 10: ...conducting heat directly to terminal junctions can cause thermal gradients Observe the following guidelines to minimize thermal gradients and improve the system accuracy Use small gauge thermocouple...

Страница 11: ...ermocouple Connection Thermocouple TC TC Shield TB 9212 NI 9212 Ground Lug NI 9212 and TB 9212 with Mini TC Thermocouple Connection Caution Electrostatic Discharge ESD can damage the TB 9212 with mini...

Страница 12: ...ximum torque of 0 4 N m 3 6 lb in Do not overtighten the jackscrews Wiring the TB 9212 with screw terminal What to Use TB 9212 with screw terminal 0 05 mm to 0 5 mm 30 AWG to 20 AWG wire with 5 1 mm 0...

Страница 13: ...no exposed wire extends past the screw terminal 3 Route the wire through the TB 9212 with screw terminal opening remove slack from the wiring and secure the wires using a zip tie 4 Replace the foam pa...

Страница 14: ...orque of 0 4 N m 3 6 lb in Do not overtighten the jackscrews Connecting the TB 9212 with mini TC What to Use TB 9212 with mini TC Shielded thermocouple Clamp on ferrite bead part number 781233 01 What...

Страница 15: ...t self help resources to email and phone assistance from NI Application Engineers Visit ni com services for NI Factory Installation Services repairs extended warranty and other services Visit ni com r...

Страница 16: ...es create your service request at ni com support or dial 1 866 ASK MYNI 275 6964 For telephone support outside the United States visit the Worldwide Offices section of ni com niglobal to access the br...

Отзывы: