Safety Guidelines for Hazardous Locations
The NI 9210 is suitable for use in Class I, Division 2, Groups A,
B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC T4
Gc and Ex nA IIC T4 Gc hazardous locations; and nonhazardous
locations only. Follow these guidelines if you are installing the
NI 9210 in a potentially explosive environment. Not following
these guidelines may result in serious injury or death.
Caution
Do not disconnect I/O-side wires or
connectors unless power has been switched off or the
area is known to be nonhazardous.
Caution
Do not remove modules unless power has
been switched off or the area is known to be
nonhazardous.
Caution
Substitution of components may impair
suitability for Class I, Division 2, or Zone 2.
Caution
The system must be installed in an enclosure
certified for the intended hazardous (classified)
location, having a tool secured cover/door, where a
minimum protection of at least IP54 is provided.
6
|
ni.com
|