background image

Caution

 Substitution of components may impair suitability for Class I,

Division 2, or Zone 2.

Caution

 The system must be installed in an enclosure certified for the

intended hazardous (classified) location, having a tool secured cover/door,

where a minimum protection of at least IP54 is provided.

Special Conditions for Hazardous Locations Use in Europe and

Internationally

The NI-9209 has been evaluated as equipment under DEMKO ATEX and is IECEx

certified. Each NI-9209 is marked and is suitable for use in Zone 2 hazardous

locations, in ambient temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI-9209

in Gas Group IIC hazardous locations, you must use the device in an NI chassis that

has been evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.

Caution

 Transient protection shall be provided that is set at a level not

exceeding 140% of the peak rated voltage value of 85 V at the supply

terminals to the equipment.

Caution

 The system shall only be used in an area of not more than

Pollution Degree 2, as defined in IEC/EN 60664-1.

Caution

 The system shall be mounted in an ATEX/IECEx-certified

enclosure with a minimum ingress protection rating of at least IP54 as

defined in IEC/EN 60079-15.

Caution

 The enclosure must have a door or cover accessible only by the

use of a tool.

© National Instruments

5

NI-9209 Getting Started

Содержание NI 9209

Страница 1: ...NI 9209 Getting Started 2022 07 06...

Страница 2: ...atibility Guidelines 5 Special Conditions for Marine Applications 6 Preparing the Environment 6 NI 9209 Pinout 7 Signals 7 Grounded Differential Connections 8 Floating Differential Connections 8 Singl...

Страница 3: ...o the documentation for each component in the system to determine the safety and EMC ratings for the entire system Safety Guidelines Caution Observe all instructions and cautions in the user documenta...

Страница 4: ...ic withstand test 860 V RMS up to 5 000 m Safety Guidelines for Hazardous Locations The NI 9209 is suitable for use in hazardous locations and hazardous locations and nonhazardous locations only Follo...

Страница 5: ...you are using the NI 9209 in Gas Group IIC hazardous locations you must use the device in an NI chassis that has been evaluated as Ex nC IIC T4 Ex IIC T4 Ex nA IIC T4 or Ex nL IIC T4 equipment Cautio...

Страница 6: ...in the product documentation Furthermore any changes or modifications to the product not expressly approved by National Instruments could void your authority to operate it under your local regulatory...

Страница 7: ...COM Common reference connection to isolated ground NC No connection Table 1 Signal Descriptions Signals You can connect single ended or differential signals to the NI 9209 Use a differential measureme...

Страница 8: ...AI25 18 AI18 AI26 19 AI19 AI27 20 AI20 AI28 21 AI21 AI29 22 AI22 AI30 23 AI23 AI31 Table 2 Differential Pairs Grounded Differential Connections Voltage Source AI AI COM NI 9209 Floating Differential C...

Страница 9: ...ire or a stranded wire with a ferrule Open the terminal by pressing the push button when using stranded wire without a ferrule High Vibration Application Connections If your application is subject to...

Страница 10: ...umentation downloads and troubleshooting and application development self help such as tutorials and examples Visit ni com services to learn about NI service offerings such as calibration options repa...

Отзывы: