National Instruments FIELDPOINT FP-DO-403 Скачать руководство пользователя страница 7

© 

National Instruments Corp.

7

[c]FP-DO-403

mount the flyback diode within 18 in. of the load. Figure 5 shows 
a flyback diode connected to an inductive load.

Figure 5.  

Connection to Inductive Load with Flyback Diode

Although the [c]FP-DO-403 contains flyback diodes to prevent 
excessively high voltage from damaging the module, National 
Instruments recommends the use of an external protection circuit 
across any inductive load.

Status Indicators

The [c]FP-DO-403 has two green status LEDs, 

POWER

 and 

READY

. After you insert the FP-DO-403 into a terminal base 

or the cFP-DO-403 into a backplane and apply power to the 
connected network module, the green 

POWER

 indicator lights 

and the [c]FP-DO-403 informs the network module of its presence. 
When the network module recognizes the [c]FP-DO-403, it sends 
initial configuration information to the [c]FP-DO-403. After the 
module receives this initial information, the green 

READY

 

indicator lights and the [c]FP-DO-403 is in normal operating 
mode.

In addition to the green 

POWER

 and 

READY

 indicators, each 

channel has a numbered, green output state indicator, which lights 
when the channel is in the ON state.

Isolation and Safety Guidelines

Caution

Read the following information before 

attempting to connect the [c]FP-DO-403 to any circuits 
that may contain hazardous voltages.

This section describes the isolation of the [c]FP-DO-403 and its 
compliance with international safety standards. The field wiring 
connections are isolated from the backplane and the inter-module 
communication bus. The isolation barriers in the module provide 

Flyb

a

ck Diode 

V

OUT

Lo

a

V or V

S

UP

Содержание FIELDPOINT FP-DO-403

Страница 1: ...e following features 16 sinking digital output channels Outputs that sink 2 A per channel 16 A2 per module Compatible with voltages from 5 to 30 VDC 250 Vrms CAT II continuous channel to ground isolation verified by 2 300 Vrms 5 s dielectric withstand test 40 to 70 C operation ON OFF LED indicators Hot swappable Installing the FP DO 403 The FP DO 403 mounts on a FieldPoint terminal base FP TB x wh...

Страница 2: ...onto a powered backplane does not disrupt the operation of the bank To install the cFP DO 403 refer to Figure 2 and complete the following steps 1 Align the captive screws on the cFP DO 403 with the screw holes on the backplane The alignment keys on the cFP DO 403 prevent backward insertion 2 Press firmly to seat the cFP DO 403 on the backplane 3 Using a number 2 Phillips screwdriver with a shank ...

Страница 3: ... cFP DO 403 Each channel has one output terminal VOUT The output channels share eight VSUP terminals and eight COM terminals All of the channels are referenced to the COM terminals The V and VSUP terminals are all internally connected as are the C and COM terminals Use a 5 30 VDC external power supply for the output channels The power supply must provide enough current to power all of the 1 cFP I ...

Страница 4: ...card on the front of the FP DO 403 module National Instruments recommends that you wire the external power supply to multiple VSUP and COM terminals Figure 3 shows how to connect two output channels to loads Wiring for Low Current Applications If your application requires 2 A or less combined current through all channels of the c FP DO 403 you can wire your application as shown in Figure 3 Install...

Страница 5: ...e your application as shown in Figure 4 Install a 2 A maximum fast acting fuse F2A 250V in series with each load as shown Figure 4 Wiring for High Current Applications COM VOUT V C c FP DO 403 Load 5 30 VDC External Power Supply VSUP VOUT 2 A Max User Supplied Fuse Load COM VOUT V C c FP DO 403 Load 5 30 VDC External Power Supply VSUP VOUT 2 A Max User Supplied Fuse Load 2 A Max User Supplied Fuse...

Страница 6: ... four channels sink 1 A each 2 A 2 2 A 2 2 A 2 1 A 2 1 A 2 1 A 2 1 A 2 16 A2 Caution The outputs must not be short circuited to the potential of the V or VSUP terminals the positive voltage of the external supply Short circuits damage the c FP DO 403 output channels Check all wiring carefully before applying power In the ON state there is an effective resistance of 0 12 Ω between the output VOUT a...

Страница 7: ...he network module of its presence When the network module recognizes the c FP DO 403 it sends initial configuration information to the c FP DO 403 After the module receives this initial information the green READY indicator lights and the c FP DO 403 is in normal operating mode In addition to the green POWER and READY indicators each channel has a numbered green output state indicator which lights...

Страница 8: ...e sure that all other devices and circuits connected to the module are properly insulated from human contact Do not share the external supply voltages the V and C terminals with other devices including other FieldPoint devices unless those devices are isolated from human contact For Compact FieldPoint you must connect the protective earth PE ground terminal on the cFP BP x backplane to the system ...

Страница 9: ...us locations Class I Zone 2 AEx nA IIC T4 and Ex nA IIC T4 hazardous locations and nonhazardous locations only Follow these guidelines if you are installing the c FP DO 403 in a potentially explosive environment Failing to follow these guidelines may result in serious injury or death Caution Make sure that all products you use in hazardous locations are certified for such use Refer to the product ...

Страница 10: ...G and is suitable for use in Zone 2 hazardous locations Specifications These specifications are typical for 40 to 70 C unless otherwise noted Specifications are subject to change without notice Output Characteristics Number of channels 16 Output type Sinking Voltage range 5 to 30 VDC Output impedance 0 12 Ω 0 12 V drop at 1 A Maximum current Per channel 2 A All channels FP DO 403 16 A2 cFP DO 403 ...

Страница 11: ...erature Input voltage 25 V 40 to 70 C Input voltage 30 V 40 to 50 C Storage temperature 45 to 85 C Humidity 10 to 90 RH noncondensing Maximum altitude 2 000 m at higher altitudes the isolation voltage ratings must be lowered Pollution Degree 2 Shock and Vibration These specifications apply only to the cFP DO 403 NI recommends Compact FieldPoint if your application is subject to shock and vibration...

Страница 12: ...Emissions Class A CE Compliance This product meets the essential requirements of applicable European Directives as amended for CE marking as follows 2006 95 EC Low Voltage Directive safety 2004 108 EC Electromagnetic Compatibility Directive EMC Note Refer to the Declaration of Conformity DoC for this product for any additional regulatory compliance information To obtain the DoC for this product vi...

Страница 13: ...ironment weee htm Mechanical Dimensions Figure 6 shows the mechanical dimensions of the FP DO 403 installed on a terminal base Dimensions are given in millimeters inches If you are using the cFP DO 403 refer to the Compact FieldPoint controller user manual for the dimensions and cabling clearance requirements of the Compact FieldPoint system Figure 6 FP DO 403 Mechanical Dimensions ᄤֵᙃѻક ᶧ ࠊㅵ ࡲ Ё ...

Страница 14: ...s or dial 512 795 8248 For telephone support outside the United States contact your local branch office Australia 1800 300 800 Austria 43 662 457990 0 Belgium 32 0 2 757 0020 Brazil 55 11 3262 3599 Canada 800 433 3488 China 86 21 5050 9800 Czech Republic 420 224 235 774 Denmark 45 45 76 26 00 Finland 358 0 9 725 72511 France 01 57 66 24 24 Germany 49 89 7413130 India 91 80 41190000 Israel 972 3 63...

Страница 15: ...to the Terms of Use section on ni com legal for more information about National Instruments trademarks Other product and company names mentioned herein are trademarks or trade names of their respective companies For patents covering National Instruments products refer to the appropriate location Help Patents in your software the patents txt file on your CD or ni com patents ...

Отзывы: