![background image](http://html1.mh-extra.com/html/national-instruments/fieldpoint-fp-ctr-502/fieldpoint-fp-ctr-502_operating-instructions-manual_3386126020.webp)
©
National Instruments Corp.
19
FP-CTR-502 and cFP-CTR-502
Maximum output current
Per channel ................................. 1 A
Across all channels..................... 4 A
Output impedance............................. 0.12
Ω
Output bandwidth ............................. 16 kHz for a current flow
≥
3.2 mA
Maximum off-state
leakage current.................................. 50
µ
A
Physical Characteristics
Indicators .......................................... Green
POWER
and
READY
indicators, 16 green
input/output state indicators
Weight
FP-CTR-502 ............................... 143 g (5.0 oz)
cFP-CTR-502 ............................. 113 g (4.0 oz)
Power Requirements
Power from network module ............ 800 mW
Isolation Voltage
Channel-to-channel isolation ............ No isolation between
channels
Transient overvoltage........................ 2,300 V
rms
Environmental
FieldPoint modules are intended for indoor use only. For outdoor
use, they must be mounted inside a sealed enclosure.
Operating temperature
cFP-CTR-502 ............................. –40 to 60 °C
FP-CTR-502 ............................... –40 to 70 °C
Storage temperature .......................... –55 to 85 °C
Humidity ........................................... 10 to 90% RH,
noncondensing
Maximum altitude............................. 2,000 m; at higher altitudes
the isolation voltage ratings
must be lowered
Pollution Degree ............................... 2