National Instruments FieldPoint FP-1001 Скачать руководство пользователя страница 2

2

The FP-1001 has a simple rail clip for mounting reliably onto a 
standard 35 mm DIN rail. To install the FP-1001 to the DIN rail, 
follow these steps:

1. With a flat bladed screwdriver, open the DIN rail clip to the 

unlocked position as shown in Figure 1.

Figure 1.  

DIN Rail Clip

2. Hook the lip on the rear of the FP-1001 onto the top of a 35 mm 

DIN rail and press the FP-1001 down onto the DIN rail as 
shown in Figure 2.

Figure 2.  

Installing the Network Module onto a DIN Rail

3. Slide the FP-1001 to the desired position along the DIN rail. 

After the FP-1001 is in position, lock it to the DIN rail by 
pushing the rail clip in.

4. Add terminal bases to the DIN rail with their local bus 

connectors firmly mated to the FP-1001 local bus connector. 
The FP-1001 is shipped with a protective cover over the local 
bus connector. Remove this protective cover, and place it over 
the local bus connector of the last terminal base in the stack as 
shown in Figure 3.

Rail Clip Locked

Rail Clip Unlocked

Press

DIN Rail

Cover

Local Bus

Connector

FP1001.fm  Page 2  Thursday, July 31, 1997  8:51 AM

Содержание FieldPoint FP-1001

Страница 1: ...to 70 C operation Overview The FP 1001 is a network module for the FieldPoint system It provides connection to an RS 485 network using a simple ASCII protocol This document provides a quick guide to installing and configuring the FP 1001 network module For more detailed information on using the network module refer to the FP 1000 1001 user manual For information on the ASCII protocol used by the n...

Страница 2: ...ng the Network Module onto a DIN Rail 3 Slide the FP 1001 to the desired position along the DIN rail After the FP 1001 is in position lock it to the DIN rail by pushing the rail clip in 4 Add terminal bases to the DIN rail with their local bus connectors firmly mated to the FP 1001 local bus connector The FP 1001 is shipped with a protective cover over the local bus connector Remove this protectiv...

Страница 3: ...port of an FP 1000 The pinout of the RS 485 connector is shown in Figure 4 Figure 4 RS 485 Connector Pinout The TX of the host port or FP 1000 RS 485 repeater port must be connected to the RX of all of the FP 1001 modules and the TX of the host port or FP 1000 RS 485 repeater port must be connected to the RX of all of the FP 1001 modules This pair of connections provides communication from the hos...

Страница 4: ...t the resistor leads with the RS 485 signal wires and insert them into the RS 485 port terminals An RS 485 network also needs biasing resistors to protect the devices on the network against noise during intervals when no RS 485 drivers are transmitting on the network The host computer s RS 485 interface normally has provisions for such biasing resistors You should use this biasing feature for bett...

Страница 5: ...connected the network module is at address 21 the next I O module is at address 22 and so on A terminal base is assigned a network address whether an I O module is inserted into it or not Table 1 shows the possible switch positions and the corresponding address of the FP 1001 Table 1 Network Address Switch Settings Switch Positions 1 5 Network Module Address Decimal Switch Positions 1 5 Network Mo...

Страница 6: ...Network Address Switch Settings Continued Switch Positions 1 5 Network Module Address Decimal Switch Positions 1 5 Network Module Address Decimal 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 ...

Страница 7: ...l connector whose pinout is shown in Figure 7 Figure 7 FP 1000 and FP 1001 Power Connector Pinout The two terminals labeled V are internally connected on the network module as are the two terminals labeled C Power must be applied to one V and C pair for operation of the FieldPoint system If you want to power your field I O devices from the same power supply the second V and C pair provides a conve...

Страница 8: ...ark Compliance This product meets applicable EU directive s as follows Safety isolation EN 61010 double insulation for 250 Vrms working isolation installation category II EMC Directive Immunity EN 50082 1 1994 Emissions EN 55011 1991 Group I Class A at 10 meters Mechanical Dimensions Figure 8 shows the mechanical dimensions of the FP 1001 Figure 8 Mechanical Dimensions 4 31 109 5 3 58 90 9 4 19 10...

Отзывы: