Isolation and Safety Guidelines

Caution

Read the following information before 

attempting to connect the cFP-DI-304 to any circuits 
that may contain 

hazardous voltages

.

1

This section describes the isolation of the cFP-DI-304 and 
its compliance with international safety standards. The field 
wiring connections are isolated from the backplane and the 
inter-module communication bus. The isolation barriers in the 
module provide 250 V

rms

 Measurement Category II continuous 

channel-to-backplane and channel-to-ground isolation, verified 
by a 2,300 V

rms

, 5 s dielectric withstand test.

2

 The cFP-DI-304 

provides 

double insulation

 compliant with IEC 61010-1 for 

working voltages of 250 V

rms

.

3

 Safety standards (such as those 

published by UL and IEC) require the use of double insulation 
between hazardous voltages and any human-accessible parts or 
circuits.

Never

 try to use any isolation product between human-accessible 

parts (such as DIN rails or monitoring stations) and circuits that 
can be at hazardous potentials under normal conditions, unless the 
product is specifically designed for such an application, as is the 
cFP-DI-304.

Even though the cFP-DI-304 is designed to handle applications 
with hazardous potentials, follow these guidelines to ensure a safe 
total system:

There is no isolation between channels on the cFP-DI-304. If a 
hazardous voltage is present on any channel, all channels are 
considered hazardous. Make sure that all other devices and 
circuits connected to the module are properly insulated from 
human contact.

Do 

not

 share the external supply voltages (the V and 

C terminals) with other devices, including other FieldPoint 
devices, unless those devices are isolated from human contact.

1  

A hazardous voltage is a voltage greater than 42.4 V

peak

 or 60 VDC. When a 

hazardous voltage is present on any channel, all of the channels must be considered 
to be carrying hazardous voltages. Ensure that all circuits connected to the module 
are inaccessible to human touch.

2  

Refer to the 

Safety Isolation Voltage

 section for more information about isolation on 

the cFP-DI-304.

3  

Working voltage

 is defined as the signal voltage plus the common-mode voltage. 

Common-mode voltage

 is the voltage of the module with respect to ground.

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Содержание FieldPoint cFP-DI-304

Страница 1: ...l service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR MORE INFORMATION Visit us on the web at www artisantg com for more information on ...

Страница 2: ...eight channels 250 Vrms CAT II continuous channel to ground isolation verified by 2 300 Vrms 5 s dielectric withstand test On off LED indicators Hot swappable Installing the cFP DI 304 The cFP DI 304 mounts on a Compact FieldPoint backplane cFP BP x which provides operating power to the module Installing the cFP DI 304 onto a powered backplane does not disrupt the operation of the FieldPoint bank ...

Страница 3: ...screws to 1 1 N m 10 lb in of torque The nylon coating on the screws prevents them from loosening Figure 1 Installing the cFP DI 304 1 cFP DI 304 2 Captive Screws 3 cFP Controller Module 4 Screw Holes 5 cFP BP x Backplane 2 2 1 3 5 4 4 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Страница 4: ... Upright Wiring the cFP DI 304 The cFP CB 1 has connections for each of the 32 input channels You can use the cFP CB 3 but it has connections for only 16 channels Each channel has one input terminal VIN Table 1 lists the VIN terminal assignment for each channel Table 1 Terminal Assignments Channel VIN Terminal 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 Up Artisan Technology Group Quality Instrumenta...

Страница 5: ...ides a path to a voltage source 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 Table 1 Terminal Assignments Continued Channel VIN Terminal Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Страница 6: ...is ON When you apply a voltage below 5 V to a VIN terminal the channel is OFF When you apply a voltage between 5 and 10 V the channel may be ON or OFF The cFP DI 304 has sinking inputs which means that current flows through the VIN terminal to the input circuitry The inputs are compatible with sourcing output devices capable of sourcing or driving current from a positive supply voltage to common A...

Страница 7: ...nd READY lights each channel has a numbered green status indicator that lights when the channel is in the ON state Upgrading the FieldPoint Software In order to use the cFP DI 304 you must have FieldPoint software version 5 0 or later installed on the host computer Go to ni com support select Drivers and Updates Current Versions Distributed I O FieldPoint and select the latest version under Driver...

Страница 8: ...ss the product is specifically designed for such an application as is the cFP DI 304 Even though the cFP DI 304 is designed to handle applications with hazardous potentials follow these guidelines to ensure a safe total system There is no isolation between channels on the cFP DI 304 If a hazardous voltage is present on any channel all channels are considered hazardous Make sure that all other devi...

Страница 9: ...eans that only nonconductive pollution occurs in most cases Occasionally however temporary conductivity caused by condensation must be expected Operate the cFP DI 304 at or below Measurement Category II Measurement Category II is for measurements performed on circuits directly connected to the low voltage installation This category refers to local level distribution such as that provided by a stan...

Страница 10: ...s marked II 3G and is suitable for use in Zone 2 hazardous locations Safety Guidelines for Hazardous Voltages If hazardous voltages are connected to the module take the following precautions Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local electrical standards Caution Do not mix hazardous voltage circuits and human accessible circuits on the s...

Страница 11: ...e 10 V Input current 330 µA Hysteresis Input voltage 2 V min Input current 60 µA min Input impedance 30 kΩ 6 I O protection Input voltage Eight channels 60 VDC channel max 32 channels 30 VDC channel max Reverse biased voltage Eight channels 60 VDC channel max 32 channels 30 VDC channel max Physical Characteristics Indicators Green POWER and READY indicators 32 green input state indicators Weight 1...

Страница 12: ...ted upright1 40 to 70 C With system in other orientations 40 to 65 C Storage temperature 55 to 85 C Humidity 10 to 90 RH noncondensing Maximum altitude 2 000 m at higher altitudes the isolation voltage ratings must be lowered Pollution Degree 2 Shock and Vibration Operating vibration random IEC 60068 2 64 10 500 Hz 5 grms Operating vibration sinusoidal IEC 60068 2 6 10 500 Hz 5 g Operating shock I...

Страница 13: ...ity EN 61326 1997 A2 2001 Table 1 CE C Tick and FCC Part 15 Class A Compliant Note For EMC compliance you must operate this device with shielded cabling CE Compliance This product meets the essential requirements of applicable European Directives as amended for CE marking as follows Low Voltage Directive safety 73 23 EEC Electromagnetic Compatibility Directive EMC 89 336 EEC Note Refer to the Decl...

Страница 14: ...ne support outside the United States contact your local branch office Australia 1800 300 800 Austria 43 0 662 45 79 90 0 Belgium 32 0 2 757 00 20 Brazil 55 11 3262 3599 Canada 800 433 3488 China 86 21 6555 7838 Czech Republic 420 224 235 774 Denmark 45 45 76 26 00 Finland 385 0 9 725 725 11 France 33 0 1 48 14 24 24 Germany 49 0 89 741 31 30 India 91 80 51190000 Israel 972 0 3 6393737 Italy 39 02 ...

Страница 15: ...ore information about National Instruments trademarks Other product and company names mentioned herein are trademarks or trade names of their respective companies For patents covering National Instruments products refer to the appropriate location Help Patents in your software the patents txt file on your CD or ni com patents Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURC...

Страница 16: ...l service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR MORE INFORMATION Visit us on the web at www artisantg com for more information on ...

Отзывы: