FP-AI-112 and cFP-AI-112
12
ni.com
Physical Characteristics
Indicators .......................................... Green
POWER
and
READY
indicators
Weight
FP-AI-112................................... 142 g (5.0 oz)
cFP-AI-112................................. 113 g (4.0 oz)
Power Requirements
Power from network module ............ 350 mW
Isolation Voltage
Channel-to-ground isolation
Continuous ................................. 250 V
rms
,
Installation Category II
Dielectric withstand.................... 2,300 V
rms
, 1 minute
Channel-to-channel isolation ............ None
Environmental
FieldPoint modules are intended for indoor use only. For outdoor
use, they must be mounted inside a sealed enclosure.
Operating temperature ...................... –40 to 70 °C
Storage temperature .......................... –50 to 85 °C
Humidity ........................................... 10 to 90% RH,
noncondensing
Maximum altitude............................. 2,000 m; at higher altitudes
the isolation voltage ratings
must be lowered.
Pollution Degree ............................... 2