Table 4.

 STATUS LED Indicators

LED

Color

LED Pattern

Indication

 

 

 

Yellow

Blinks twice and

pauses

The cRIO-9031 is in safe mode. Software is not installed,
which is the factory default state, or software has been
improperly installed on the cRIO-9031.

An error can occur when an attempt to upgrade the software
is interrupted. Reinstall software on the cRIO-9031. Refer
to the 

Measurement & Automation Explorer (MAX) Help

 for

information about installing software on the cRIO-9031.

Blinks three times

and pauses

The cRIO-9031 is in user-directed safe mode, or the
cRIO-9031 is in install mode to indicate that software is
currently being installed.

This pattern may also indicate that the user has forced the
cRIO-9031 to boot into safe mode by pressing the reset
button for longer than five seconds or by enabling safe
mode in MAX. Refer to the 

Measurement & Automation

Explorer (MAX) Help

 for information about safe mode.

Blinks four times

and pauses

The cRIO-9031 is in safe mode. The software has crashed
twice without rebooting or cycling power between crashes.

Continuously

blinks

The cRIO-9031 has not booted into NI Linux Real-Time.
The cRIO-9031 either booted into an unsupported operating
system, was interrupted during the boot process, or detected
an unrecoverable software error.

On momentarily

The cRIO-9031 is booting. No action required.

Red

Continuously

blinks

This indicates a hardware error. An internal power supply
has failed. Check front-panel I/O and C Series module
connections for shorts. Remove any shorts and cycle power
the cRIO-9031. If the problem persists, contact NI.

Off

The cRIO-9031 is in run mode. Software is installed and the
operating system is running.

NI cRIO-9031 Getting Started Guide

  | 

© National Instruments

  | 

15

Содержание cRIO-9031

Страница 1: ...omise the safety protection built into the product if the product is damaged in any way If the product is damaged return it to NI for repair Safety Guidelines for Hazardous Locations The cRIO 9031 is...

Страница 2: ...s must be used in a conduit or cable gland to wire to a nonhazardous location Do not disconnect a cable unless the cRIO 9031 is powered off or the area is known to be nonhazardous Table 1 Hazardous Lo...

Страница 3: ...ermore any changes or modifications to the product not expressly approved by National Instruments could void your authority to operate it under your local regulatory rules Caution To ensure the specif...

Страница 4: ...ifications Operating temperature IEC 60068 2 1 IEC 60068 2 2 40 C to 70 C Operating humidity IEC 60068 2 56 10 RH to 90 RH noncondensing Pollution degree 2 Maximum altitude 5 000 m Indoor use only Not...

Страница 5: ...are and device drivers on the host computer in this order 1 LabVIEW 2014 or later 2 LabVIEW Real Time Module 2014 or later 3 LabVIEW FPGA Module 2014 or later1 4 NI RIO Device Drivers August 2014 or l...

Страница 6: ...module with a slot and seat it in the slot until the latches lock in place Removing C Series Modules Verify that power is not connected to the I O connector s on the C Series module before you remove...

Страница 7: ...rminal to the grounding electrode system of the facility What to Use Ring lug Wire 1 3 mm2 16 AWG or larger Screwdriver Phillips 2 What to Do Complete the following steps to ground the cRIO 9031 1 Att...

Страница 8: ...031 has a primary power input V1 and a secondary power input V2 The POWER LED on the cRIO 9031 indicates which power input is in use as shown in the following table Table 2 POWER LED Indicators LED Co...

Страница 9: ...tive leads of the power supply as shown in the following figure Figure 3 Installing a Ferrite on the Power Leads 2 1 1 Pass the leads through the ferrite twice leaving 50 mm to 75 mm 2 in to 3 in betw...

Страница 10: ...cRIO 9031 When you power on the cRIO 9031 for the first time the device boots into safe mode The POWER LED illuminates the STATUS LED illuminates briefly and then the STATUS LED blinks twice every few...

Страница 11: ...system password Note The default username for the cRIO 9031 is admin There is no default password for the cRIO 9031 so you must leave the password field blank when logging in until you set a system pa...

Страница 12: ...odule Tip You can use this wizard at anytime to install additional software 7 Click Next 8 Verify that the summary of software to install is correct 9 Click Next to start the installation 10 Click Fin...

Страница 13: ...System IP Configuration 1 Put the cRIO 9031 in safe mode and enable the RS 232 serial port by holding the RESET button down for 5 seconds The STATUS LED starts blinking three times every few seconds...

Страница 14: ...d RESET button for 5 s Press and hold RESET button for 5 s Run Mode Safe Mode Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold...

Страница 15: ...r longer than five seconds or by enabling safe mode in MAX Refer to the Measurement Automation Explorer MAX Help for information about safe mode Blinks four times and pauses The cRIO 9031 is in safe m...

Страница 16: ...eshooting and application development self help resources to email and phone assistance from NI Application Engineers Visit ni com services for NI Factory Installation Services repairs extended warran...

Страница 17: ...the United States create your service request at ni com support or dial 1 866 ASK MYNI 275 6964 For telephone support outside the United States visit the Worldwide Offices section of ni com niglobal...

Страница 18: ...d third party legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni com legal export compliance for the National Instruments global trade compliance pol...

Отзывы: