5-24
|
ni.com
Chapter 5
Counters
Single Pulse Generation
The counter can output a single pulse. The pulse appears on the Counter
n
Internal Output signal
of the counter.
You can specify a delay from when the counter is armed to the beginning of the pulse. The delay
is measured in terms of a number of active edges of the Source input.
You can specify a pulse width. The pulse width is also measured in terms of a number of active
edges of the Source input. You also can specify the active edge of the Source input (rising or
falling).
Figure 5-26 shows a generation of a pulse with a pulse delay of four and a pulse width of three
(using the rising edge of Source).
Figure 5-26.
Single Pulse Generation
Single Pulse Generation with Start Trigger
The counter can output a single pulse in response to one pulse on a hardware Start Trigger signal.
The pulse appears on the Counter
n
Internal Output signal of the counter.
You can specify a delay from the Start Trigger to the beginning of the pulse. You also can specify
the pulse width. The delay is measured in terms of a number of active edges of the Source input.
You can specify a pulse width. The pulse width is also measured in terms of a number of active
edges of the Source input. You can also specify the active edge of the Source input (rising and
falling).
Figure 5-27 shows a generation of a pulse with a pulse delay of four and a pulse width of three
(using the rising edge of Source).
Figure 5-27.
Single Pulse Generation with Start Trigger
S
OURCE
OUT
Co
u
nter Armed
S
OURCE
GATE
(
S
t
a
rt Trigger)
OUT