![National Instruments cDAQ-9138 Скачать руководство пользователя страница 31](http://html2.mh-extra.com/html/national-instruments/cdaq-9138/cdaq-9138_user-manual_3389078031.webp)
© National Instruments
|
1-21
Removing Modules from the cDAQ Controller
Complete the following steps to remove a C Series module from the cDAQ controller.
1.
Make sure that no I/O-side power is connected to the module. If the controller is in a
nonhazardous location, the controller power can be on when you remove modules.
2.
Squeeze the latches on both sides of the module and pull the module out of the controller.
cDAQ Controller Features
The cDAQ controller features many ports, DIP switches, LEDs, a RESET button, and a power
button. Refer to Figure 1-1 for the locations of these features on the cDAQ controller.
Video (VGA) Port
The cDAQ controller video (VGA) port, shown in Figure 1-1, outputs graphics using VESA
standard VGA analog signaling. Use this port to connect a monitor to program the
NI cDAQ-9138/9139 for Windows. Table 1-3 lists the video port pin locations and VGA
signals.
Table 1-3.
Video Port Pin Locations
Pinout
Pin
Signal Name
Signal Description
1
RED
Red analog video signal
2
GREEN
Green analog video signal
3
BLUE
Blue analog video signal
4
No Connect
—
5
GND
Ground reference
6
RED RETURN
Ground reference
7
GREEN RETURN
Ground reference
8
BLUE RETURN
Ground reference
9
PWR
5 V power for DDC
10
GND
Ground return for power
11
No Connect
—
12
DDC_D
Data signal of serial communication
13
HSYNC
Horizontal synchronization signal
14
VSYNC
Vertical synchronization signal
15
DDC_C
Clock signal of serial communication