Installation Guide for Comfort Pack (CPG) Units

Limit Control

If it is determined that a limit control needs replacing, use only 

the factory-authorized replacement part that is designed for 

the size of heater. The limit control is accessible in the control 

compartment. For approximate limit control location (see 

Figure 1).

Gas Valve

The gas valve requires no field maintenance except careful 

removal of external dirt accumulation and checking of wiring 

connections. Instructions for testing pressure settings are in 

paragraph entitled “Gas Piping and Pressures.

THE OPERATING VALVE IS THE PRIMARY 

SAFETY SHUTOFF. ALL GAS SUPPLY 

LINES MUST bE FREE OF DIRT OR SCALE 

bEFORE CONNECTING TO THE UNIT TO 

ENSURE POSITIVE CLOSURES. SEE HAzARD 

INTENSITY LEVELS, PAGE 3.  

!

CAUTIoN

Pressure Switch

If it is determined that the pressure switch needs replacing, use 

only the factory-authorized replacement part that is designed for 

this heater. For approximate location (see Figure 5)

NOTE: A unit operating above 6000 ft elevation 

requires a high altitude pressure switch,  P/N 

14208325 (see page 17).

Flame Rollout Switch

For approximate location (see Figure 6A). The cause of a flame 

rollout switch activating must be determined. Activation of the 

manually reset flame rollout switch could be caused by one or 

more of the following: • Restricted or plugged heat exchanger. • 

Pressurization of the heat exchanger. • Restricted combustion air 

inlet or exhaust outlet in combination with a defective pressure 

switch. • Electrical power interruption during operation. If a flame 

rollout switch trips, inspect the burner/control compartment for 

signs of excessive heat and burned wiring. 

If the compartment appears normal, reset by depressing the red 

button on the switch. 15 to 20 minutes are required for the switch 

to cool sufficiently for resetting. A distinct click will be felt when 

the switch resets. Operate the furnace. If the flame rollout switch 

trips again, determine and correct the cause before resetting the 

switch. 

If there is damage to the burner/control compartment, repairs 

must be made before resetting the switch.

If it is determined that the flame rollout switch needs replacing, 

use only the factory-authorized replacement part that is designed 

for that size of heater.

Vent System

Check at least once a year. Inspect all joints and seams. Replace 
any defective parts.

Troubleshooting

Check the DSI Integrated Control Module (Circuit Board) - The 

Integrated Circuit Board monitors the operation of the heater 

and includes an LED signal that indicates normal operation 

and various abnormal conditions. If the heater fails to operate 

properly, check this signal to determine the cause and/or to 

eliminate certain causes. 

Do not attempt to repair the DSI integrated control 

module; the only field replaceable component is the 

fuse.

CoNTRoL 

STATUS

GREEN LED

STEADY ON 

FAST FLASH 

1 FLASH 
2 FLASH 
3 FLASH 
4 FLASH 

STEADY OFF

Normal operation, no call for heat 

Normal operation, call for heat 

In lockout from failed ignition or flame loss 

Pressure switch does not close for 30 seconds 

Limit switch or rollout switch open 

Limit switch is closed before venter is energized 

Internal control fault or no power

FLAME 

STATUS

YELLoW LED

STEADY ON 

SLOW FLASH 

FAST FLASH

Flame sensed 

Weak flame (current below 1.0 microamps = +/-50%) 

Undesired flame (valve open and no call for heat)

Содержание CPG41228-U

Страница 1: ...nance To ensure long life and satisfactory performance a heater that is operated under normal conditions should be inspected and cleaned at the start of each heating season If the heater is operating...

Страница 2: ...h end Loosen burner assembly by removing only the two screws indicated Burner Assembly Secondary Air Shield End Cap Remove secondary air shield end cap by removing four screws indicated Remove screw o...

Страница 3: ...he fuse Do not attempt to disassemble the control module However each heating season check the lead wires for insulation deterioration and good connections Proper operation of the direct spark ignitio...

Страница 4: ...pect the burner control compartment for signs of excessive heat and burned wiring If the compartment appears normal reset by depressing the red button on the switch 15 to 20 minutes are required for t...

Страница 5: ...tions to Slide Out the Furnace After removing front panels 1 Remove the 4 screws indicated at the right Gas Line Power Cord 2 Remove the patch plate Gas Line Power Cord Front Furnace Baffle 3 Remove 2...

Страница 6: ...insulation when pulling the heat exchanger furnace assembly forward 4 Unplug 2 molex plugs before sliding out the heat exchanger furnace assembly Lift Pull Forward Power Cord 6 With your right hand re...

Страница 7: ...U 2 5 27 000 9 2 64 000 51 200 360 Electrical Data Models Voltage Compressor Outdoor Fan Motor Indoor Blower Motor Total Amps Minimum Circuit Amps Maximum Overcurrent Protector RLA LRA HP FLA LRA HP...

Страница 8: ...F Nominal 45 F to 60 F 38MBTU 52 5 F Nominal 45 F to 60 F 51MBTU 55 F Nominal 45 F to 65 F 64MBTU 67 F Nominal 60 F to 80 F In order to calculate CFM use the formula CFM BTU Output 1 08 x Temp Rise S...

Страница 9: ...0 59 3 328 63 2 Comfort Pack Gas CFM and Temperature Rise 38 000 BTU Input UNIT SIZE COLOR SPEED 1 w c TD 2 w c TD 3 w c TD 4 w c TD 5 w c TD CPG41238 Red 1 780 36 1 770 36 6 760 37 0 725 38 8 680 41...

Страница 10: ...nge 5 410 92 1 320 118 1 225 167 9 Comfort Pack Gas CFM and Temperature Rise 64 000 BTU Input UNIT SIZE COLOR SPEED 1 w c TD 2 w c TD 3 w c TD 4 w c TD 5 w c TD CPG41864 Red 1 780 60 8 770 61 6 760 62...

Страница 11: ...range 5 415 325 225 X X CPG418 Red 1 780 770 760 725 680 Yellow 2 715 690 660 620 560 Blue 3 620 580 520 450 380 Black 4 550 500 430 340 240 Orange 5 415 325 225 X X CPG424 Red 1 850 833 815 803 790 Y...

Страница 12: ...36 Installation Guide for Comfort Pack CPG Units...

Страница 13: ...37 Installation Guide for Comfort Pack CPG Units REVISION 3...

Страница 14: ...38 Installation Guide for Comfort Pack CPG Units...

Страница 15: ...Set thermostat at lowest setting 2 Turn on manual gas valve 3 Turn on power to unit 4 Set thermostat at desired setting 5 Thermostat calls for heat energizing the venter motor 6 Venter pressure switc...

Страница 16: ...ain power Replace combustion air proving switch 6 7 a If 24 volt is measured at the valve connections and valve remains closes replace valve b Check and tighten all wiring connections 8 a Check and ti...

Страница 17: ...678 All All All All All All All All All All All All All All All All All All All All All All All All All All All All All All All All All 28 Mbh 38 Mbh 51 Mbh 64 Mbh All All All All 38 Mbh 38 Mbh 51 Mbh...

Страница 18: ...or Coil Outdoor Coil Compressor Low Pressure Switch High Pressure Switch Dual Run Capacitor 40 5 TXV 14256641 14208304 14208383 14210248 14265026 14265029 14225372 14275103 30 30 30 30 30 30 30 30 CHA...

Страница 19: ...ding between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Winding OHM...

Страница 20: ...the goods and are in lieu of and exclude all other warranties express or implied arising by operation of law or otherwise including without limitation merchantability and fitness for a particular purp...

Страница 21: ...shall render the warranty void B Compressors In addition to the above referenced requirements Customer is also required to purchase a replacement compressor and return the original compressor to Nati...

Отзывы: