Control board 

 

Analog inputs (10 or 15 Vdc): 
1.

 

AN1: 4-20 mA 

2.

 

AN2: 4-20 mA 

3.

 

AN3: 4-20 mA / 0 - 10 Vdc (settable 
by jumper C.C.) 

4.

 

AN4: 4-20 mA / 0 - 10 Vdc (settable 
by C.C.)

 

Digital outputs: 

Power source signal relay: 
NO1, COM1: closed contact with AC power supply 
NC1, COM1: closed contact with DC power supply 
Alarm Relay: 
NO2, COM2: contact closed without alarm. 
NC2, COM2: contact closed with alarm or without 
power supply. 
Generator start / stop relay: 
NO3, COM3: contact closed for generator start. 
NC3, COM3: contact open for generator start. 
 

The digital output relays are non-voltage contacts. 
The maximum voltage applicable to the contacts is 
250 V AC, max 5 A. 

RS485 for COMBO with 
device to be controlled: 

 

S1+ 

 

S1- 

 

It is recommended to 
respect  the polarity 
linking devices. 

Digital inputs: 

 

IN1 : float or pressure switch for 
pump start and stop

 

 

IN2: AC / DC switch

 

 

IN3: genset alarm

 

 

IN4 : genset lack of fuel

 

 

0V 

 

 
We recommend using only no voltage 
contacts. 

5V power supply (max 1 A): 
• 0V 
• + 5V 

RS485 for MODBUS: 

 

S2+ 

 

S2- 

 

It is recommended to 
respect the polarity. 

 

 

Содержание HMA Series

Страница 1: ...Operating manual HMA manHMA_eng_00...

Страница 2: ...Electric wiring 6 4 1 Protections 8 4 2 Electromagnetic compliance 8 5 HMA installation 9 6 HMA Use and Programming 10 6 1 HMA display 10 6 2 Initial configuration 10 6 3 Initial view 11 6 4 Menu vie...

Страница 3: ...automatically based on the programmed logic Mechanical disconnection of the two power supplies Two interlocked contactors guarantee the uniqueness of the power supply and ensure separation in order t...

Страница 4: ...before operation Install safety devices on both DC and AC side Avoid any shock or significant impact during transport Check the product immediately upon delivery and check for damage and or missing p...

Страница 5: ...VS 409 430 MP HMA 485 190 850 3x190 520 85 A VS 438 485 MP Ambient temperature at rated current da 10 a 50 C Max altitude at rated current 1000 m Grade of protection IP54 NEMA 12 Connettivity MODBUS R...

Страница 6: ...polarity HMA 430 AC input P E T1 T2 T3 DC input P E It is necessary to respect the polarity AC DC output F1 F2 F3 P E It is necessary to respect the polarity HMA 485 AC input P E T1 T2 T3 DC input P E...

Страница 7: ...or start stop relay NO3 COM3 contact closed for generator start NC3 COM3 contact open for generator start The digital output relays are non voltage contacts The maximum voltage applicable to the conta...

Страница 8: ...ommend to use 1000 VDC circuit breaker and if possible 1000 VDC surge protection For AC side we recommend to use overload protection with the characteristic curve of type C and type B circuit breaker...

Страница 9: ...alled on the wall following the holes shown in the drawing The IP54 protection degree NEMA 12 allows installation even in humid and dusty environments However it is recommended to avoid direct exposur...

Страница 10: ...ey can be only displayed 6 1 HMA display It is a backlit display with 2 rows of 16 characters An acoustic signal accompanies the user in use and provides a quick indication in case of an alarm 6 2 Ini...

Страница 11: ...supply INV SUPPLY AC AC power supply DC Wait waiting for the DC supply to stabilize for 5 minutes before attempting to switch to DC AC Wait waiting for the AC supply to stabilize before attempting to...

Страница 12: ...y the panels is not sufficient to operate the pump the HMA starts the generator if present and exchanges with AC power When the irradiation returns above the minimum threshold the generator is switche...

Страница 13: ...C to AC XX Set time for the passage from AC to DC By pressing the ENT key it is possible to change the installer level password level 1 default 001 6 6 IN OUT parameters Parameter Default Description...

Страница 14: ...tivity parameters Parameters Default Description XXXXX End user communication language 1 MODBUS address from 1 to 247 9600 MODBUS baudrate from 1200 bps to 57600 bps RTU N81 MODBUS data format RTU N81...

Страница 15: ...E Overvoltage in DC power supply Check the causes of overvoltage AC CLOSING FAULT Failure to detect closure of the AC contactor Check the wiring of contactor Check the function of the contactor DC CLO...

Страница 16: ...generator INV SUPPLY OFF Deactivation of both AC and DC contactors following the simultaneous pressing of both the AC and DC buttons Select a power source using the corresponding button INV SUPPLY DC...

Страница 17: ...17 NOTE...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...reserves the right to modify without previous notice any technical information contained in this document Nastec srl Via della Tecnica 8 36024 Mossano Vicenza Italy Tel 39 0444 886289 Fax 39 0444 7760...

Отзывы: