SINCE 1973
PUMP MONITORMODEL PM-23
www.nassarelectronics.com
The best solutions for
automation and protection
User Manual
Страница 1: ...SINCE 1973 PUMP MONITOR MODEL PM 23 www nassarelectronics com The best solutions for automation and protection User Manual...
Страница 2: ...ephasepumps with a current consumption in the range of 16 to 60 Amps Connect the 220 V voltage supply to terminals TC and T1 Then connect the current transformer by plugging the black wire into termin...
Страница 3: ...i e the system is pumping water and the motor current is normal Try to achieve the maximum water flow rate Calibrationonafullyrecoveredwellisrecommended The calibration may be repeated to assure that...
Страница 4: ...UP button and the under voltage setup will be displayed if the voltage is under this value the pumpwillshutdown SET UNDER VOLTAGE 200 V SET OVER VOLTAGE 245 V Usethearrowbuttonstoadjustthedesiredvolta...
Страница 5: ...iggeringoftheunderloadprotection In this case underload should be adjusted manually to alowervalueinthesetupmenu The overload trip point is set to 125 of the power consumption during automatic calibra...
Страница 6: ...lizetheLEDindicators italsomakessetupadjustmentseasier Ifthisunit ispanelmounted thepanelneedstobeinstalledindoors Din rail mounting Mounting hole Mounting hole Mounting options Dimensions This unit c...
Страница 7: ...IN CONTRACT INFRINGEMENT NEGLIGENCE STRICT LIABILITY OTHER TORT OR OTHERWISE SHALL NASSAR ELECTRONIC S LIABILITY TO THE BUYER AND OR ITS CUSTOMERS EXCEED THE PRICE TO THE BUYER OF THE SPECIFIC GOODS...