F3 FASEALERT-3  MANUAL

Description

Features

Operation

The F3 series is a family of 3-phase voltage monitors. It 
continuously  measures  the  voltage  of  each  of  the 
three  phases  with  microcontroller  accuracy  and 
compares  the  value  with  preset  trip  points.  It  
separately senses  phase  reversal  and  loss,  as  well  as 
under and unbalanced voltages. 
Protection is assured during periods of large voltage 

uctuations  or  when  regenerated  voltages  are 

present. 
Trip  and  restart  delays  are  included  to  prevent 
nuisance  tripping  and  short  cycling  of  sensitive 
equipment.  The  isolated  10A  SPDT  output  relay 
contact trips when a phase voltage exceeds the trip 
limit after the time established by the trip delay.  
The under  voltage limit  is adjustable.
Both  delta  and  wye  systems  can  be  monitored;  no 
connection to neutral is needed.

The FASEALERT-3 protects motors against: 
Under  voltage,  phase  loss,  voltage  unbalance  and 
reverse  phase sequence. To adjust the Under Voltage 
limit set the knob at the desired level.

Note: 

If the “Reverse Phase” LED turns ON when you 

are  connecting  the  F3  for  the  rst  time,  swap  the 
cables connected to the L1 and L2 terminals and the 
fault LED should turn OFF.

UPON APPLICATION OF LINE VOLTAGES 

Ÿ

The  output relay is de-energized

Ÿ

The failure red LED is OFF

Ÿ

The  “RUN”  green  LED  ashes  during  the  restart 
delay (Depending on the model), and when it ends 
the  green  LED  stays  ON  and  the  output  relay  is 
energized.

IN NORMAL VOLTAGES

Ÿ

The output relay is energized. 

Ÿ

The “RUN” green LED is ON.

Ÿ

The red  failure LED  is OFF.

UPON A VOLTAGE FAILURE

Ÿ

The  red  LED  indicates  the  corresponding  failure  
and the “RUN” green LED goes OFF. 

Ÿ

Once  the  adjusted  period  in  the  trip  delay  has 
passed,  the    output  relay  is  de-energized  to 
disconnect the motor.

Ÿ

Protects against phase reversal, phase 
loss, under and unbalanced voltages.

Ÿ

Surface mounting  or 35mm DIN rail. 

Ÿ

Isolated, 10A, relay contacts.

Ÿ

LEDs indicate each fault, status, and 
time delays.

Ÿ

3-wire connection for delta or wye 
systems. 

WHEN VOLTAGES GO BACK TO NORMAL

Ÿ

The red  failure LED  is OFF.

Ÿ

The  output relay stays  de-energized. 

Ÿ

The  “RUN”  green  LED  ashes  during  the  restart 
delay (optional), and once it’s  nished, the green 
LED stays   ON, then the output relay is energized 
to reconnnect the motors.