VRLA Installation, Operation & Maintenance Manual

 

4    Subject to revision without prior notice. E.&.O.E V2.3 

 

Two other factors are relevant when discussing battery 
discharges. First, batteries must not be left in a 
discharged state, and must be charged immediately after 
a discharge. Second,   

MPINarada battery discharge rates are given for a 
reference temperature of 77°F (25°C). At temperatures 
above the reference the capacity increases at the 
expense of life, while at temperatures below the reference 
capacity diminishes and extends battery life. Please refer 
to industry standard IEEE 1188 for more information on 
the effect of temperature on battery capacity.     

7.

 

Maintenance and record keeping 

MPINarada VRLA batteries do not require periodic 
watering. However, for optimum life and performance they 
must be kept clean; cleaning should be done with only a 
damp cloth, avoiding the use of any organic solvents. 
Below are the recommended maintenance procedures. 

 

Monthly maintenance (Recommended)

 

 

Keep battery room /site clean. 

 

Check each battery for cleanliness and look 

for signs of damage due to overheating, 
particularly at and around the terminals and 
on the cables. 

 

Record battery room /cabinet ambient 

temperature. 

 

Measure and record the total string float 

voltage and float charge current at the 
closest point to the battery or battery string 
termination. The string voltage should read 
(

N × Recommended float voltage

), where 

N

 

is the number of cells in the series string. 

 

Quarterly maintenance (Recommended)

 

 

Perform monthly maintenance procedures 

 

Measure and record voltage of each 

individual on-line battery/cell of the string. If 
more than two cells or batteries vary by 
more than 0.10 VPC (13V and 6.5V for a 12V 
and 6V battery, respectively) equalize the 
string as noted in the Section 4 on 
equalizing charge. If the problem exists the 
batteries may be given the yearly 
maintenance noted below. 

 

Annual maintenance (Required)

 

 

Perform quarterly maintenance procedures 

 

Check all connections for looseness and 

retorque them as necessary. 

 

Conduct a load test to 30-40% depth of 

discharge (DOD), or perform an 
impedance /conductance /resistance test 
to verify battery change from Baseline or 
Reference.  

 

3-year maintenance (Recommended)

 

 

Perform quarterly maintenance procedures 

 

Check all connections for looseness and 

retorque them as necessary. 

 

Conduct a load test to 80% DOD or perform 

an impedance/conductance /resistance 
test to verify battery system capacity. 

 

 

All of the records should be carefully kept in a logbook as 
MPINarada will require all maintenance records in the event of 
a warranty claim. The logbook should also record any unusual 
activity such as power outages, rectifier/UPS alarms, etc. 

 

After sales service

 

North America: 
MPINarada 
44 Oak Street, Newton, MA 02464 
Tel: 800-982-4339 
www.mpinarada.com 
[email protected]  
 
China:   
NARADA POWER SOURCE CO.,LTD. 
No.459 Wensan Road, Hangzhou, Zhejiang, P.R.China 
Tel:+86-571-28827013 Fax:+86-571-85126942 
www.en.naradapower.com 
[email protected] 
 
 

 

Отзывы: