Narada REXC Series Скачать руководство пользователя страница 18

Narada Power Source Co., Ltd.                                                                                      REXC operation manual V1.2         

18 

6.4 Operation and Maintenance Precautions 
Insufficient Charge 

If the floating voltage is not set correctly (too low or not compensate according to 
temperature),  the  battery  system  will  in  an  insufficient  charge  state  for  a  long 
period  of  time.  When  the  electricity  is  out,  the  battery  may  not  be  able  to  work 
because the acid is satirized and the capacity is decreased. 

 

Over Charge 

If we neglect the performance of rectifier to transfer floating charge to equalization 
charge.  If  the  rectifier  cannot  transfer  charge  modes  because  of  its  wrong 
performance  or  no  adjustment,  the  battery  system  is  always  in  an  equalization 
charge state. Thus may cause serious problems for battery, such as water loss, life 
decrease, thermal runaway, deformation, etc. 

Too low or too high temperature 

We  have  mentioned  that  too  low  temperature  will  affect  the  capacity  of  battery. 
While  too  high  temperature  will  also  cause  problems,  such  as  water  loss,  life 
decrease, thermal runaway, deformation, etc. 

Too low end voltage 

The end voltage is also an important parameter for battery. The battery shall stop 
discharge when reach a certain voltage (The normal end voltage is 1.8Vpc for 10 
hours rated). If the end voltage is too low, it will be difficult to recharge the battery 
and decrease the charge efficiency, thus reduce the life of battery.   

Long time storage after discharge   

If  the  battery  is  put  aside  without  charge  for  a  long  time  after  discharge,  it  will 
affect the capacity and life of the battery, because some large size PbSO

4

 will be 

created  in  the  negative,  which  are  difficult  to  transfer  to  active  Pb.  Thus  it  will 
affect battery life and capacity 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Содержание REXC Series

Страница 1: ...LEAD CARBON BATTERY OPERATION MANUAL Version V1 2 NARADA POWER SOURCE CO LTD REXC Series Series...

Страница 2: ...arbon Working Principle 7 Chapter Two Technical characteristic 8 1 Discharge Curve and Discharge Data 8 2 Charge Curve 8 3 Internal Resistance and Short Circuit Current 9 Chapter Three Operation and M...

Страница 3: ...eat harms to environment and heath Please check local laws and regulations to get the validity handle ways or send the equipment to authorized service center The replacement of battery can only be don...

Страница 4: ...mance Reduce sulfation of the negative plate longer cycle life 1 1 Design floating life is above 20 years Grid alloy with special patented formula Special patented negative paste formula 4BS paste tec...

Страница 5: ...Shockproof blocking assembling Satisfy customer s individual requirements and provide up to 8 class shockproof Streamline and dime light battery outside looking design 2 Main applications Home energy...

Страница 6: ...End voltage 1 80V End voltage 1 85V REXC 200 2 200 240 227 96 291 303 17 REXC 300 2 300 360 227 133 291 303 24 REXC 400 2 400 480 227 170 291 303 31 REXC 500 2 500 600 231 155 396 408 39 REXC 600 2 6...

Страница 7: ...he chemical reaction taking place in lead carbon battery is as follows positive electrode negative electrode Because of the reaction is based on double layer capacitance which caused from carbon elect...

Страница 8: ...O So it is possible to build REXC battery in sealed structure Chapter Two Technical characteristic 1 Discharge Curve and Discharge Data Fig 2 1 REXC Battery Discharge Performance Curves at Different D...

Страница 9: ...e internal resistance is the lowest when battery is fully charged The table 2 3 shows the internal resistance and short circuit current of REXC battery in fully charged state according to the IEC60896...

Страница 10: ...e protection V Please refer to table 3 2 Temperature Compensate Ratio With Floating Voltage mV cell 3 3 Temperature Compensate Ratio With Equalization Voltage mV cell 5 5 High Temperature Warning 35 3...

Страница 11: ...the capacity at 3 hours rate The capacity can be expressed in Rated Capacity or Actual Capacity For Rated Capacity of REXC please see Table 1 1 The Actual Capacity is the actual output capacity in ce...

Страница 12: ...mperature and Floating Voltage Equalization Voltage The purpose to select certain floating voltage is make the battery operate in best conditions If the floating voltage is higher the floating current...

Страница 13: ...rature and voltage Ambient Temperature Equalization Voltage V cell Float Voltage V cell 15 2 350 2 275 20 2 325 2 260 25 2 300 2 245 30 2 275 2 230 35 2 250 2 215 40 2 225 2 200 3 2 Ambient temperatur...

Страница 14: ...nce vs Capacity There is a certain corresponding relationship between conductance resistance and battery capacity We suggest to test battery conductance and resistance data at different stage with sam...

Страница 15: ...ge according to initial current When the current is larger than 0 05C10A reference current to change to equalization charge equalization voltage is recommended The charge time is 24 hours We can also...

Страница 16: ...e charger to recharging batteries 4 Stop charging when reaching the cut off condition At the last one hour before finishing test the battery voltage one by one the battery which voltage is below 2 16V...

Страница 17: ...ld be fully charged before storage It s suggested to record storage time in periodic maintenance record and record the time when another necessary supplementary charge should be made The quality certi...

Страница 18: ...water loss life decrease thermal runaway deformation etc Too low or too high temperature We have mentioned that too low temperature will affect the capacity of battery While too high temperature will...

Страница 19: ...g A No 50 Zijinghua Road Hangzhou China Tel 86 571 28827013 Fax 86 571 28828290 E mail intl narada biz Website www naradabattery com NARADAASIA PACIFIC PTE LTD 65 Ubi Crescent 07 05 Hola centre Singap...

Страница 20: ...2 20 Annex 1 VRLA Battery Regular Maintenance Record Type Place Status Number of battery Total Voltage V Current A Temperature No Voltage V No Voltage V 1 13 2 14 3 15 4 16 5 17 6 18 7 19 8 20 9 21 1...

Отзывы: