Narada 6V Series Скачать руководство пользователя страница 8

6V&12V Serials

13

14

Table 3-5 discharge end voltage at different current

I<0.2C

0.2C≤I

<0.5C

0.5C≤I

<1.0C

I≥1.0C

1.80

1.80

1.70

1.60

Discharge Current(A)

Discharge End Voltage(V/Cell)

Fig.3-1: Ambient Temperature VS Available Capacity

The capacity will decrease if the temperature is too low. The reason is that the negative plates is 
passivated at lower temperature, then it causes the battery to be failed to recharge and the negative 
active material sulfation.
The  capacity  will  increase  as  the  temperature  increases.  However,  the  higher  temperature  will 
accelerate the corrosion of the grid and cause water loss inside the battery, thus shorten the life of 
the battery.

Conductance, Resistance vs. Capacity 

There  is  a  certain  corresponding  relationship  between  conductance  &  resistance  and  battery 

capacity. We suggest to test battery conductance and resistance data at difficult stage with same 

type instruments from same factory. Conductance and resistance data is only a reference to judge 
whether battery is good. These data cannot replace loading test to judge whether battery is good. 
We recommend to test these data on the surface or side of battery post. 

Ambient Temperature

VRLA batteries can be used in very low or high temperature. Yet all standard data (such as capacity, 

life,  floating  voltage)  are  measured  under  standard  temperature  of  20°C-25°C.  The  capacity  will 

decrease under lower temperature as Fig. 3-1:

Battery life is the battery operation life, it is influenced by many factors. The factors are charge mode, 

discharge mode, ambient Temperature and so on.

Lifetime and influence factors

Floating voltage

Equalization voltage

≤ 0.25C

10

 A

The Equalization 

charge time is 24h

1.80V/cell per block at 

10h rate.

15~25°C

(1) The charge voltage is too high, it will 

accelerate corruption of the grid and shorten 

life of the battery.

(2) The charge voltage is too low, the battery 

will be insufficient.

If the current is too high, the battery 

temperature will be higher, then it will cause 

water loss, thermal runaway.

The charge time is only aimed at the 

equalization charge procedure, it can ensure 

the battery can be fully charged.

If the end voltage is too low, it will be difficult to 

recharge the battery and decrease the charge 

efficiency, thus reduce the life of battery.

When temperature exceeds 25°C, the battery 

life will decrease half per 10°C temperature 

raise.

t25~35=t

T

×2

 (T-25)/10

Notes: T the actual ambient temperature;

T

T

 is designed life at T ambient temperature

T

25

 is designed life at 25°C ambient 

temperature

Charge mode

Discharge 

mode

Ambient 

temperature

End voltage

/

Voltage

Current

Time

Normal Value

Note

Main factors

Main failure

/

/

(1) Different brands of battery cannot be 

installed in one bank;

(2) Different group no. of battery cannot be 

installed in one bank or in the same parallels.

If the capacity is failed, the failed battery 

should be replaced timely.

Mixed 

operation

Replace the 

failure battery

/

/

Содержание 6V Series

Страница 1: ...VALVE REGULATED SEALED LEAD ACID BATTERY NARADA POWER SOURCE CO LTD Email intl narada biz Website en naradapower com OPERATION MANUAL Version V1 0 6V 12V Series ...

Страница 2: ...0 Product Features Main application Working principle Discharge performance Charge performance General Inspection Corrective actions Annex1 Annex2 Parameter settings Operation condition Capacity and influence factors Lifetime and influence factors Storage 4 4 5 6 6 16 16 17 18 19 10 11 12 14 15 01 02 notes two one Four three ...

Страница 3: ...uthorized by the manufacturer To replace the battery or maintenance equipment please call the after sales service hotline for information of the nearest service center Please check the local regulations on the correct way of battery disposal or send the battery to the authorized service center for replacement Battery replacement should be operated or supervised by engineers who are experienced and...

Страница 4: ...aled structure Figure 2 2 is the battery charging characteristics curve of 6V 12V series battery with constant voltage and limited current 0 1C10 A current voltage limit 2 35V cell fully discharged battery charges for 24 hours and the charge power up to 105 The dotted line is the 50 charge curve Pb PbO2 2H2SO4 2PbSO4 2H2O Discharge Charge 2Pb O2 2PbO PbO H2SO4 PbSO4 H2O Discharge performance techn...

Страница 5: ...ch series of batteries is shown in Table 2 2 Similarly the average charging voltage needs to be adjusted with the ambient temperature and the temperature compensation coefficient of the battery charging voltage is 5 mV C cell Table 2 1 Floating Voltage of Each Series 25 C Table 2 2 Equalization charging Voltage of Each Series 25 C Table 2 3 Temperature and voltage setting MP MPG Acme AcmeG GP GPG ...

Страница 6: ...e batteries will be rejected if the situation is serious Battery recharge method Step 1 Connect the batteries in series and ensure that the bolts and screws are fastened Step 2 Connect the positive and negative poles of the battery to the positive and negative poles of the charging device Step 3 Turn on the charging power supply set the charging current limit value and charging voltage value accor...

Страница 7: ... 25 C 15 C 25 C 15 C 35 C 15 C 35 C 15 C 35 C Operation status Operation status Optimum temperature Optimum temperature Temperature range Temperature range Capacity and influence factors The capacity can be expressed in Rated Capacity or Actual Capacity The Actual Capacity is the product of discharge current A and discharge time h The usual unit of capacity is ampere hour shortened as Ah The Influ...

Страница 8: ...The capacity will decrease under lower temperature as Fig 3 1 Battery life is the battery operation life it is influenced by many factors The factors are charge mode discharge mode ambient Temperature and so on Lifetime and influence factors Floating voltage Equalization voltage 0 25C10 A The Equalization charge time is 24h 1 80V cell per block at 10h rate 15 25 C 1 The charge voltage is too high ...

Страница 9: ...or battery replacement The users must consider their particular application and reliability needs if maintenance procedures other than those recommended in this document are used Battery maintenance should be performed by personnel knowledgeable of batteries and the safety precautions involved General Inspection Maintenance Chapter Four 04 Monthly Maintenance Keep the battery room clean Measure an...

Страница 10: ...igated Routine The following items indicate conditions that if allowed to persist for extended periods can reduce battery life They do not necessarily indicate a loss of capacity Therefore the corrective action may be accomplished before the next quarterly inspection provided that the battery condition is monitored at regular intervals a If any cell unit voltage is below its respective critical mi...

Страница 11: ...ing VRLA batteries Digital multimeter Wrenches insulated Adjustable wrench insulated Torque wrench Rubber gloves Full set of masks Plastic apron Portable eyedrops Fire extinguishers C grade The following equipment is optional according to the type of maintenance Resistance tester Charger and discharger special for storage battery portable ...

Страница 12: ...6V 12V Serials ...

Страница 13: ...1 56975955 Website en naradapower com E mail intl narada biz Block 9 Khaki Bukit Road 1 02 10 Eunos Technolink Singapore 415938 Tel 65 6848 1191 Fax 65 6749 3498 Website www narada ap com Email sales narada ap com Spectrum House Dunstable Road Redbourn St Albans Herts Al3 7PR Tel 44 0 845 612 2031 Fax 44 0 845 612 2031 E mail sales naradaeurope com After sale Services ...

Отзывы: