This conversion kit shall be installed by a qualifi ed service agency in accordance with the 
manufacturer’s instructions and all applicable codes and requirements of the authority having 
jurisdiction.  If the information in these instructions is not followed exactly, a fi re, explosion or 
production of carbon monoxide may result causing property damage, personal injury or loss 
of life.  The qualifi ed service agency is responsible for the proper installation of this kit.  The 
installation is not proper and complete until the operation of the converted appliance is checked 
as specifi ed in the owner instructions supplied with the kit.

FUEL CONVERSION KIT FOR MODEL

C/GDI3 / C/GDI3E / C/GDIX3

These kits are for use at altitudes of 0 to 4500 feet.

INSTALLER: THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOME OWNER.

CHECK THE BOXES TO INDICATE THAT THE CORRESPONDING STEPS HAVE BEEN COMPLETED.

  Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 0G8 Canada   •     1(866)820-8686    •    www.napoleon.com

C/GDI3 / E

     Kit W175-0687 / W175-0724  NG to P Includes:
1x       REGULATOR
1x       #53 BURNER ORIFICE
1x       CONVERSION DATA LABEL
1x       PROPANE PILOT INJECTOR

C/GDI3 / E

     Kit W175-0692 / W175-0725 P to NG Includes:
1x       REGULATOR
1x       #43 BURNER ORIFICE
1x       CONVERSION DATA LABEL
1x       NATURAL GAS PILOT INJECTOR

C/GDIX3

     Kit W175-0689 NG to P Includes:
1x       REGULATOR
1x       #52 BURNER ORIFICE
1x       CONVERSION DATA LABEL
1x       PROPANE PILOT INJECTOR

C/GDIX3

     Kit W175-0694 P to NG Includes:
1x       REGULATOR
1x       #37 BURNER ORIFICE
1x       CONVERSION DATA LABEL
1x       NATURAL GAS PILOT INJECTOR

WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts specifi cally ap-
proved with this appliance may result in property damage or personal injury.
CAUTION: Before proceeding with the conversion, shut off the gas supply fi rst and then disconnect the electrical 
power.

1.  Remove the door, logs, and panels from the ap-

pliance (see the “fi nishing” section of your installa-
tion manual).

2.  Remove the 7 screws that secure the log cover in 

place. Lift the cover out 

(Fig. 1)

.

3.  Remove the 2 screws holding the burner tube, 

then slide it to the left, up, and out 

(Fig. 2)

.

4.  Remove the orifi ce and replace it with the orifi ce 

supplied (use pipe thread compound).

5.  Adjust the air shutter according to the table lo-

cated on the back of this page.

6.  To convert the main valve to the desired fuel, fol-

low the instructions that are supplied with the SIT regulator assembly.

7.  Remove the pilot hood from the pilot assembly by pulling vertically. Use an Allen key to unscrew the 

injector 

(Fig. 3)

. Replace the pilot injector with the one supplied. Re-assembly the pilot hood onto 

the assembly ensuring key position for proper alignment.

8.  The conversion data label must be fi lled out and attached adjacent to the valve.
9.  Turn on the gas supply and check for gas leaks by brushing on a soap and water solution.

Do not 

use open fl ame.

10.  Re-install the burner and log cover, then light the pilot and main burner to ensure that the gas lines 

have been purged.

 Purge all gas lines with the glass door off.

 Refer to the lighting instructions in 

your appliance installation manual. Once all systems have been checked, replace the logs.

11.  Ensure there is a continuous fl ow at the burner before replacing the door.

 Turn on all electrical 

supply to the appliance.

W415-1918 / B / 01.09.20

Fig. 1

Fig. 2

PILOT

HOOD

PILOT

INJECTOR

SPRING 

CLIP

Fig. 3

(C/GDIX3 Illustrated)

(C/GDIX3 Illustrated)

Содержание W175-0689

Страница 1: ...use only parts specifically ap proved with this appliance may result in property damage or personal injury CAUTION Before proceeding with the conversion shut off the gas supply first and then disconnect the electrical power 1 Remove the door logs and panels from the ap pliance see the finishing section of your installa tion manual 2 Remove the 7 screws that secure the log cover in place Lift the cov...

Страница 2: ...hutters have been factory set open according to the chart below Closing the air shutter will cause a more yellow flame but can lead to carboning Opening the air shutter will cause a more blue flame but can cause flame lifting from the burner ports The flame may not appear yellow immediately allow 15 to 30 minutes for the final flame colour to be established Adjustment may be required depending on ...

Страница 3: ...ant d effecteur la conversion vous devez couper l alimentation en gaz avant de couper l alimentation électrique 1 Retirez la porte les bûches et les panneaux de l appareil voir la section finitions dans votre manuel d installations 2 Retirez les 7 vis servant à fixer la couverture de bûche en place Soulevez la couverture puis la retirez Fig 1 3 Retirez les 2 vis servant à fixer le brûleur tubulair...

Страница 4: ...flamme est jaune et aura tendance à causer des dépôts de carbone Plus le volet est ouvert plus la flamme est bleue et plus elle a tendance à se détacher des orifices du brûleur La flamme peut ne pas être jaune immédiatement allouez de 15 à 30 minutes pour que la couleur finale de la flamme se stabilise D autres réglages peuvent être nécessaires selon le type de gaz utilisé la configuration d évacu...

Отзывы: