venting requirements

2.3  minimum air terminal location clearances

Covered balcony applications 

††*

Q

MIN

R

MAX

MAX

R

= 3 feet

(0.9m)

= 2 x 

≤ 15 feet

(4.6m)

Q

ACTUAL

R

Q

S

G

P

INSTALLATIONS

CANADA

U.S.A.

A

12” (30.5cm)

12” (30.5cm)

Clearance above grade, veranda porch, deck or balcony.

B

12” (30.5cm)

Δ

9” (229mm) 

Δ

Clearance to windows or doors that open.

C

12” (30.5cm)*

12” (30.5cm)*

Clearance to permanently closed windows.

D

18”

(45.7cm)**

18” 

(45.7cm)**

Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ (0.6m) 

from the center line of the terminal.

E

12” (30.5cm)**

12” (30.5cm)**

Clearance to unventilated soffi t.

F

0” (0mm)

0” (0mm)

Clearance to an outside corner wall.

G

0” (0mm)***

0” (0mm)***

Clearance to an inside 

non

-combustible corner wall or protruding 

non

-combustible obstructions (chimney, etc.).

2” (51mm)***

2” (51mm)***

Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).

H

3’(0.9m)

3’(0.9m)****

Clearance to each side of the center line extended above the meter / regulator assembly to a maximum 

vertical distance of 15’ (4.6m).

I

3’ (0.9m)

3’ (0.9m)****

Clearance to a service regulator vent outlet.

J

12” (30.5cm)

9” (229mm)

Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.

K

6’ (1.8m)

3’ (0.9m) †

Clearance to a mechanical air supply inlet.

L

7’ (2.1m) ‡

7’ (2.1m) ****

Clearance above a paved sidewalk or paved driveway located on public property.

M

12” (30.5cm)†† 12” (30.5cm)**** Clearance under a veranda, porch, deck or overhang.

N

16” (40.6cm)

16” (40.6cm)

Clearance above the roof.

O

2’ (0.6m)†*

2’ (0.6m) †*

Clearance from an adjacent wall including neighbouring buildings.

P

8’ (2.4m)

8’ (2.4m)

Roof must be 

non

-combustible without openings.

Q

3’ (0.9m)

3’ (0.9m)

See chart for wider wall dimensions.

R

6’ (1.8m)

6’ (1.8m)

See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening 

between the terminal and the open side of the structure.

S

12” (30.5cm)

12” (30.5cm)

Clearance under a covered balcony

Δ

The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.

*

Recommended to prevent condensation on windows and thermal breakage

**

It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.

***

The periscope requires a minimum 18 inches clearance from an inside corner.

****

This is a recommended distance. For additional requirements, check local codes.

3 feet above if within 10 feet horizontally.

A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.

††

Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.

†*

Recommended to prevent recirculation of exhaust products. For additional requirements, check local codes.

††*

Permitted only if the balcony is fully open on a minimum of one side.

Clearances are to be in accordance with local 

installation codes and the requirements of the gas 

supplier. In their absence, clearances are to be as 

listed above and are based on national codes.

note:

9.1B

note:

Wall terminals are for illustration purposes only. Size and 

shapes may vary.

Содержание Vittoria GD19P-2

Страница 1: ...electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call t...

Страница 2: ...touching hot surfaces Even after the appliance is off it will remain hot for an extended period of time Check with your local hearth specialty dealer for safety screens and hearth guards to protect c...

Страница 3: ...r s barrier for this appliance Installation and repair should be done by a qualified service person It is imperative that control compartments burners and circulating air passageways of the appliance...

Страница 4: ...rmination installation using rigid venting 31 5 0 electrical information 32 5 1 hard wiring connection 32 5 2 receptable wiring diagram 32 5 3 battery installation replacement 33 5 4 wiring diagram 34...

Страница 5: ...re recycl es et accept es dans votre centre de recyclage local Rensei gnez vous aupr s de votre municipalit au sujet des directives de recyclage Las bater as deben desecharse de acuerdo con las leyes...

Страница 6: ...de ANSI Z223 1 NFPA 54 in the United States Suitable for mobile home installation if installed in accordance with the current standard CAN CSA Z240MH Series for gas equipped mobile homes in Canada or...

Страница 7: ...ajoutez pas cet appareil aucun mat riau devant entretien contact avec les flammes autre que celui qui est fourni avec cet appareil par le fabricant Maximum horizontal extension X See installation manu...

Страница 8: ...VIEW 21 1 2 546mm 1 3 4 45mm 2 1 2 64mm 5 127mm 9 1 2 241mm 9 229mm 7 178mm 4 102mm 26 3 8 670mm 13 330mm 19 3 4 502mm 33 1 8 841mm SAFETY BARRIER 20 1 2 521mm 33 13 16 859mm Finishing flange depth t...

Страница 9: ...ld climates For optimum flame appearance and appliance performance keep the vent length and number of elbows to a minimum The air terminal must remain unobstructed at all times Examine the air termina...

Страница 10: ...horizontal runs have a minimum 1 4 rise per foot or 21mm rise per meter using flexible venting For safe and proper operation of the appliance follow the venting instructions exactly A terminal shall...

Страница 11: ...EN W415 2355 A 12 09 20 11 venting requirements 16 406MM MINIMUM 35FT 11M MAXIMUM 3FT 1M MINIMUM 26 3 8 67cm 26 3 8 67cm MINIMUM PLUS RISE 20 50 8cm MAXIMUM See venting section 2 1 2 rear vent...

Страница 12: ...with a stove appliance 8 1 TOP VENT REAR VENT 2 2 special vent installations 2 2 1 periscope termination 30 MINIMUM 12 MINIMUM TOP EXIT INSTALLATION REAR EXIT INSTAL 30 MINIMUM MAXIMUM 10FT VENT LENGT...

Страница 13: ...deck or overhang N 16 40 6cm 16 40 6cm Clearance above the roof O 2 0 6m 2 0 6m Clearance from an adjacent wall including neighbouring buildings P 8 2 4m 8 2 4m Roof must be non combustible without o...

Страница 14: ...30 5 5 H V V H 35 ft For longer vent runs a power vent is required V H are measured from the centre of vent elbows Elbows are considered as 90 Two 45 elbows One 90 elbow Base of air collar 10 min 10...

Страница 15: ...5 21 3 25 30 5 5 H V V H 35 ft For longer vent runs a power vent is required V H are measured from the centre of vent elbows Elbows are considered as 90 Two 45 elbows One 90 elbow Base of air collar 3...

Страница 16: ...bow zone 2 3 elbow zone 2 4 elbow zone 2 5 elbow zone 2 6 elbow zone H V V H 35 ft For longer vent runs a power vent is required H 19 25 ft V H are measured from the centre of vent elbows Elbows are c...

Страница 17: ...5 1 elbow zone 1 2 elbow zone 1 3 elbow zone 1 4 elbow zone 1 5 elbow zone H V V H 35 ft For longer vent runs a power vent is required V H are measured from the centre of vent elbows Elbows are consid...

Страница 18: ...remove components as illustrated below When reinstalling in the alternate position check gaskets for tears and replace if necessary to ensure a proper seal 4 102mm Collar 4 102mm Gasket 7 178mm Colla...

Страница 19: ...he air intake flex liner and the exhaust collar must be connected to the exhaust flexible liner Both Simpson Duravent and Selkirk co linear to co axial adaptors have been approved on this appliance Fo...

Страница 20: ...UL763 shall be considered non combustible materials Minimum clearance to combusibles must be maintained or a serious fire hazard could result The appliance requires a minimum enclosure height Measure...

Страница 21: ...inimum framing dimensions 2 51mm 4 102mm 6 152mm 2 51mm 4 102mm 23 58 4cm MINIMUM 331 2 85 1cm OUTSIDE CHASE INSIDE CHASE 221 4 56 5cm PROTRUSION SIDE WALL 131 4 33 7cm Do not put objects in front of...

Страница 22: ...ight of 39 1 8 99 4cm and a minimum ceiling height of 45 1 8 114 6cm for rear vent For temperature requirements the enclosure space around and above the appliance must be left unobstructed 3 2 1 rear...

Страница 23: ...ides and 2 51mm at the top of the vent pipe in all horizontal runs to combustibles is required except for clearances in appliance enclosure which must be a minimum of 6 152mm Vertical Vent Sections A...

Страница 24: ...cm Before framing your appliance determine vent requirements before deciding the final location of the appliance After rough framing place the appliance in its final position For heavier finishing mat...

Страница 25: ...st also be used to ensure the connection cannot slip off Do not clamp the flexible vent pipe Risk of fire explosion or asphyxiation Improper support of the entire venting system may allow vent to sag...

Страница 26: ...between the pipe and the firestop Bend the tabs for reduced side clearances or move the shield for reduced top clearances dependent on specific appliance clearances Do not fill the air space between t...

Страница 27: ...iling that the venting system passes through Apply a bead of caulking all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the fire...

Страница 28: ...l length needed for the finished wall surface Apply a heavy bead of the red RTV silicone W573 0002 not supplied to the inner sleeve of the air terminal Slip the vent pipe a minimum of 2 50 8mm over th...

Страница 29: ...ing Where possible cover the sides and top edges of the flashing with roofing material F Aligning the seams of the terminal and air terminal connector place the terminal over the air terminal connecto...

Страница 30: ...ing no greater than the depth of the return flange 18 4 SCREWS 10x2 OUTER RIGID PIPE CAULKING INNER RIGID PIPE SCREWS SELF DRILLING 8x1 2 MINIMUM 1 1 4 31mm OVERLAP SEALANT HI TEMP SEALANT HI TEMP OUT...

Страница 31: ...the flashing over the air terminal connector and slide it underneath the sides and upper edge of the shingles Ensure that the air terminal connector is properly centered within the flashing giving a...

Страница 32: ...hard wiring connection WARNING Do not use this appliance if any part has been under water Call a qualified service technician immediately to have the appliance inspected for damage to the electrical...

Страница 33: ...ompartment D Install 2 D alkaline batteries not supplied into the battery housing Ensure the positive and negative ends correspond with those identified on the holder E Turn the gas and electrical pow...

Страница 34: ...l for Optional Wall Switch GD 660 Wiring Brown SWI Black Red Green x2 Main Black Ground Black Yellow Blue Orange x2 Pilot MODULE PLUG RELAY PLUG To Optional Receiver Main Burner Switch IGNITION WIRE O...

Страница 35: ...essures above 1 2 PSIG Valve settings have been factory set do not change Installation and servicing to be done by a qualified installer Move the appliance into position and secure If equipped with a...

Страница 36: ...cal power to the appliance and re install the batteries into the transmitter Set thermostat to desired setting if equipped I Turn on the remote wall switch to the appliance J If the appliance will not...

Страница 37: ...nter clockwise to adjust the main burner flame height NIGHT LIGHTTM SWITCH This switch turns the Night LightTM on and off FAN CONTROL OPTION If installed this switch will turn the power to the blower...

Страница 38: ...the variable speed switch F Insert the blower assembly into the left side under the firebox slide into the clip and place onto the same stud used for the thermal switch assembly Secure with the lock...

Страница 39: ...MATERIAL NON COMBUSTIBLE BOARDREQUIRED 201 2 54 6cm 3 76mm MINIMUM 3 76mm MINIMUM 3313 16 85 9cm FINISHING MATERIAL OPENING HEIGHT MUSTBE Finishing material MUST NEVER be installed behind the finishi...

Страница 40: ...ebox Fig 5 F Place the front facing onto the appliance by hooking the its brackets over the screws and spacers Fig 6 G Install the rest of the top trim and control panel Fig 7 Fig 1 BARRIER SAFETY Fig...

Страница 41: ...EN W415 2355 A 12 09 20 41 finishing BARRIER SAFETY Fig 6 SAFETY BARRIER Fig 7 X4 Fig 5 SAFETY SCREEN L CRAN DE PROTECTION SAFETY SCREEN L CRAN DE PROTECTION...

Страница 42: ...any damages during bracket installation Fig 1 C Install the lower side bracket on the front Fig 2 D Install the safety barrier spline up Fig 3 E Install the 4 screws with spacers into the sides of the...

Страница 43: ...the door to release B Slide the door forward off its support C Reverse steps to reinstall the glass door Slide the front with safety barrier onto the hooks over the top of the spacers and then let it...

Страница 44: ...ERIAL FINISH MATERIAL FINISH MATERIAL 3 4 19mm WARNING Non combustible facing material may protrude past the face of the opening relative to its depth If it does it is considered a non combustible pro...

Страница 45: ...f equipped PLACE REMOTE RECEIVER ON TOP OF THIS LABEL APPLIANCE BASE JUNCTION BOX REMOTE RECEIVER PLACEMENT Positionnez le t l commande aux compartiment du soupape pr s du bo te de d rivation lectriqu...

Страница 46: ...G This installation should be done by a qualified installer and shall be in compliance with local codes In the absence of local codes use the current CAN1 B149 Installation Code in Canada or the curre...

Страница 47: ...ot screw to provide properly sized flame Turn in a clockwise direction to reduce the gas flow Check Pressure Readings Inlet pressure can be checked by turning screw A counter clockwise 2 or 3 turns an...

Страница 48: ...service person ADD IMAGE HERE 36 1 B19N PS 2 Rock Burner B19N PL 2 Log Burner 12 7mm 9 5mm of Flame sensor DEXEN EI ODS MILLIVOLT 3 8 1 2 9 5mm 12 7mm Flame must envelop upper 3 8 to 1 2 12 7mm 9 5mm...

Страница 49: ...ner 5 If your appliance is equipped with a safety barrier cleaning may be necessary due to excessive lint dust from carpeting pets etc simply vacuum using the brush attachment 6 If your appliance is e...

Страница 50: ...as control valve pilot and Hi Lo knobs move freely if equipped Replace if any stiffness in movement is experienced Check for gas leaks on all gas connections up and downstream from the gas valve inclu...

Страница 51: ...onstrated an ability to provide a clean streak free glass surface note Do not clean glass when hot Do not use abrasive cleaners to clean glass 5 1 3 This appliance is factory equipped with 5mm ceramic...

Страница 52: ...ement A Remove the safety barrier front door and top shield from the firebox B Compress the retainer fins in with a screw driver while pressing firmly on the top of the light assembly C Once all the r...

Страница 53: ...r warranty replacement parts a photocopy of the original invoice will be required to honour the claim When ordering replacement parts always give the following information Model Serial Number of appli...

Страница 54: ...9 2 Overview Yes Yes 21 22 23 24 W010 3687 W500 0149 W290 0054 W290 0056 W500 0171 Door latch 7 vent cover 7 flange gasket 4 flange gasket 4 vent cover B19N PL 2 B19N PS 2 W705 0206 SER W750 0185 Logs...

Страница 55: ...bly W432 0078 SER 10 st st manifold service kit W105 0001 7 8 bushing W456 0062 Burner orifice 62 P W456 0052 Burner orifice 52 NG 10 9 8 11 12 12 Stocked Stocked W445 0024 W707 0020 3 8 black nipple...

Страница 56: ...cription 1 2 3 4 5 6 7 8 W010 1653 Pan burner assembly W135 0322 Rear log GL 622 W135 0323 Left log GL 622 W135 0324 Right log GL 622 W135 0325 Centre log GL 622 GL 622 Log set W550 0001 Charcoal embe...

Страница 57: ...AND BURNER ASSEMBLY Ref No Part Number Description 1 2 3 4 5 W010 2493 Pan burner assembly W010 2498 Front rock trim assembly X2 W655 0912 Rock burner support MRKXXS Mineral Rock Kit W010 2499 Rock b...

Страница 58: ...tocked 8 6 S a fe ty B a rr ie r S a fe ty B a rr ie r FK19SB FK19PWSB CFK19SB CFS19SB 6 7 CFS19SB FK19SB FK19PWSB 7 Contemporary brushed stainless steel surround Traditional metallic black surround T...

Страница 59: ...r missing and the seal is tight Ensure vent liners are free of holes and well sealed at all joints Check that minimum rise per foot meters has been adhered to for any horizontal venting White grey fil...

Страница 60: ...ocess several times or purge the pilot supply line Incorrect wiring grounding Ensure correct polarity of wiring of thermocouple if equipped Verify pilot assembly valve are properly grounded Receiver i...

Страница 61: ...g posi tion Verify that the switch is in the on position Transmitter isn t operational if required Check battery power and battery orientation Light won t function if applicable Light bulb burnt out C...

Страница 62: ...be caused by mechanical systems such as exhaust fans furnaces clothes dryers etc Any damages to the appliance combustion chamber heat exchanger plated trim or other components due to water weather dam...

Страница 63: ...EN W415 2355 A 12 09 20 63 notes 29 1...

Страница 64: ...oute Transcanadienne Montr al Qu bec H4T 1A3 24 Napoleon Road Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Crittenden Kentucky USA 41030 Phone 1 866 8...

Отзывы: