FOR YOUR SATISFACTION, THIS FIREPLACE HAS 
BEEN TEST-FIRED TO ASSURE ITS OPERATION AND 
QUALITY!

 

Minimum inlet gas supply pressure is 4.5 inches water column 
for natural gas and 11 inches water column for propane. 
Maximum inlet gas pressure is 7 inches water column for 
natural gas and 13 inches water column for propane. When 
the valve is set to "HI", the manifold pressure under 

fl

 ow 

conditions is 3.5 inches water column for natural gas and 
10 inches water column for propane. When the 

fi

 replace is 

installed at elevations above 4,500ft, and in the absence of 
speci

fi

 c recommendations from the local authority having 

jurisdiction, the certi

fi

 ed high altitude input rating shall be 

reduced at the rate of 4% for each additional 1,000ft. 
Expansion / contraction noises during heating up and cooling 
down cycles are normal and to be expected.
This appliance is only for use with the type of gas indicated 
on the rating plate

.

 This appliance is not convertible for use 

with other gases, unless a certi

fi

 ed kit is used.

Maximum input is 11,500 BTU/hr for natural gas. Maximum 
output for natural gas is 8,600 BTU/hr at an ef

fi

 ciency of 75%. 

Maximum input is 11,000 BTU/hr for propane. Maximum output 
for propane gas is

 

8,250 BTU/hr at an ef

fi

 ciency of 75%.

Provide adequate accessibility clearance for servicing and 

operating the 

fi

 replace. 

Never obstruct the front opening of the 

fi

 replace.

Provided that the clearance to combustibles are achieved, 
the most desirable and bene

fi

 cial location for a Napoleon® 

fi

 replace is in the centre of a building, thereby allowing 

the most ef

fi

 cient use of the heat created. The location of 

windows, doors and the traf

fi

 c 

fl

 ow in the room where the 

fi

 replace is to be located should be considered. If possible, 

you should choose a location where the vent will pass 
through the house without cutting a 

fl

 oor or roof joist.

RATING LABEL LOCATION:  

The rating label is located 

under the control panel and is chained to the 

fi

 replace. 

DO NOT REMOVE.

THIS GAS FIREPLACE SHOULD BE INSTALLED AND 
SERVICED BY A QUALIFIED INSTALLER

  to conform with 

local codes. Installation practices vary from region to region 
and  it is important to know the speci

fi

 cs that apply to your 

area, 
for example: in Massachusetts State:

•   The 

fi

 replace damper must be removed or welded in the open  

  position prior to installation of a 

fi

 replace insert or gas log.

•  

A carbon monoxide detector is required in all rooms containing  

 gas 

fi

 red appliances. 

•   The appliance off valve must be a “T” handle gas cock.
•   The 

fl

 exible connector must not be longer than 36 inches.

•   The appliance is not approved for installation in a bedroom or  
  bathroom unless the unit is a direct vent sealed combustion  
 product.
•   WARNING: This product must be installed by a licensed 
    plumber or gas 

fi

 tter when installed within the commonwealth of 

 Massachusetts.

In absence of local codes, install to the current CAN1-B149 
Installation Code in Canada or to the National Fuel Gas 
Code, ANSI Z223.1, and NFPA 54 in the United States. 
Mobile home installation must conform with local codes. In 
the absence of local codes, install to the current standard for 
gas equipped mobile housing CAN/CSA Z240 MH Series in 
Canada or the manufactured home construction and safety 
standard, Title 24 CFR, part 3280, or the Fire Safety Criteria 
for manufactured home installations, Sites and Community 
Standard ANSI/NFPA 501A in the United States.

Objects placed in front of the 

fi

 replace must be kept a 

minimum of 48" away from the front face of the unit.

The fireplace and its individual shutoff valve must be 
disconnected from the gas supply piping system during any 
pressure testing of that system at test pressures in excess 
of ½ psig (3.5 kPa). The 

fi

 replace must be isolated from the 

gas supply piping system by closing its individual manual 
shutoff valve during any pressure testing of the gas supply 
piping  system at test pressures equal to or less than ½ psig 
(3.5 kPa).

When the 

fi

 replace is installed directly on carpeting, vinyl tile 

or other combustible material other than wood 

fl

 ooring, the 

fi

 replace shall be installed on a metal or wood panel extending 

the full width and depth.

The fireplace, when installed with a blower, must be 
electrically connected and grounded in accordance with 
local codes. In the absence of local codes, use the current 
CSA C22.1 CANADIAN ELECTRICAL CODE in Canada or 
the ANSI/NFPA 70 NATIONAL ELECTRICAL CODE in the 
United States. 

GENERAL INSTRUCTIONS

GENERAL INFORMATION

CARE OF GLASS AND PLATED PARTS

Do not use abrasive cleaners to clean these parts. Buff lightly 
with a clean dry cloth. 
The glass is 

3

/

16

" ceramic glass available from your Napoleon® 

/ Wolf Steel Ltd. dealer. 

DO NOT SUBSTITUTE MATERIALS.

 

Clean the glass after the 

fi

 rst 10 hours of operation with a 

recommended gas 

fi

 replace glass cleaner. Thereafter clean 

as required. 

DO NOT CLEAN GLASS WHEN HOT!

 If the 

glass is not kept clean permanent discolouration and / or 
blemishes may result.

Содержание Vittoria GD19N

Страница 1: ...s supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified inst...

Страница 2: ...nder water Do not operate the fireplace with the glass door removed cracked or broken Replacement of the glass should be done by a licensed or qualified service person Do not strike or slam shut the f...

Страница 3: ...ents used in the installation of the fireplace NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life subject to the following condi tions During the first...

Страница 4: ...log A carbon monoxide detector is required in all rooms containing gas fired appliances The appliance off valve must be a T handle gas cock The flexible connector must not be longer than 36 inches Th...

Страница 5: ...RTV this same sleant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the fireplace flue colla...

Страница 6: ...ns use either the 5 foot Vent Kit GD220 or the 10 foot Vent Kit GD330 The maximum allowable vertical vent length is 35 feet the minimum is 3 feet For optimum flame appearance and fireplace performance...

Страница 7: ...of horizontal run in addition to the 45 offset In this case zero rise is acceptable when using rigid See FIGURE 5a Flexible venting must maintain a 6 rise See FIGURE 5b TYPICAL VENT INSTALLATIONS PER...

Страница 8: ...8 W415 0612 C 01 25 08 FIGURE 6 MINIMUM AIR TERMINAL LOCATION CLEARANCES...

Страница 9: ...u m of 35 feet Vertical rise is equal to or greater t h a n t h e horizontal run Horizontal run verti cal rise to m a x i m u m of 35 feet Vertical rise is equal to or greater t h a n t h e horizontal...

Страница 10: ...n is acceptable FIGURE 8 The shaded area within the lines represents acceptable values for HT and VT For the following symbols used in the venting calculations and examples are greater than equal to o...

Страница 11: ...ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 360 90 8 1 ft HT HR HO 5 5 8 1 13 6 ft HT VT 13 6 5 5 19 1 ft Formula 1 HT 4 2 VT 4 2 VT 4 2 x 5 5 23 1...

Страница 12: ...RIZONTAL TERMINATION Simple venting configuration only two 90 elbows FIGURE 13 H3 90 90 90 V2 H1 V1 H2 V1 9 ft V2 6 ft VT V1 V2 9 6 15 ft H1 3 ft H2 2 ft H3 1 5 ft HR H1 H2 H3 3 2 1 5 6 5 ft HO 03 fou...

Страница 13: ...mula 2 HT VT 24 75 feet 20 45 24 75 Since both formulas are met this vent configuration is acceptable FIGURE 15 For vent configurations requiring more than two 90 elbows the following formulas apply F...

Страница 14: ...Since both formulas are met this vent configuration is acceptable FIGURE 16 For vent configurations requiring more than zero 90 elbow top exit or one 90 elbow rear exit the following formulas apply F...

Страница 15: ...ormula 2 HT VT 35 feet 20 6 35 Since only formula 2 is met this vent configuration is unacceptable and a new fireplace location or vent configuration will need to be established to satisfy both formul...

Страница 16: ...exit remove the components as illustrated When reinstalling in the alternate position Check gaskets for tears replace if necessary to ensure a proper seal TOP EXIT CONVERSION FIGURE 18 4 Collar 4 Gask...

Страница 17: ...Dura Vent Selkirk Direct Temp American Metal Amerivent or Wolf Steel rigid or flexible vent components For safe and proper operation of the fireplace follow the venting instructions exactly CAULKING V...

Страница 18: ...f the high temperature sealant W573 0007 not supplied NOTE If using pipe clamps to connect vent components 3 screws must also be used to ensure the connection cannot slip off 2 Using the 7 flexible ve...

Страница 19: ...t that it penetrates the roof Figure 27 DO NOT CLAMP THE FLEXIBLE VENT PIPE 5 Remove nails from the shingles above and to the sides of the chimney Place the flashing over the air terminal connector le...

Страница 20: ...slide down to the caulking Tighten to ensure that a weather tight seal between the air terminal and the collar is achieved 9 Continue adding rigid vent pipe sections sealing and securing as above Att...

Страница 21: ...he mobile home appliance This appliance is certified to be installed in an aftermarket permanently located manufactured mobile home where not prohibited by local codes This fireplace is only for use w...

Страница 22: ...Combustible Finishing 0 to rear 0 to front face top and sides 13 recessed depth Rear Vent 39 1 8 to enclosure top from base of the unit 45 1 8 to ceiling from base of the unit Top Vent 53 1 8 to encl...

Страница 23: ...CK COMBUSTIBLE NON COMBUSTIBLE 26 3 8 MINIMUM PLUS RISE 0 IF NON COMBUSTIBLE FINISHING IS USED SUCH AS BRICK AND STONE The fireplace requires a minimum enclosure height of 53 1 8 for a top vent and 39...

Страница 24: ...heavy use care when lifting and ensure they are firmly secured once installed This front facing does not replace the main glass door Do not operate without the main glass door installed The front fac...

Страница 25: ...LIFIED INSTALLER and must be connected and grounded in accordance with local codes In the absence of local codes use the current CSA C22 1 CANADIAN ELECTRICAL CODE in Canada or the current ANSI NFPA 7...

Страница 26: ...htly and lift out of bottom retainer FIGURE 58 90 2 Place the left log as shown ensuring the hole on the underside is placed onto the burner pin This will rest on the left side of the rear log 1 Place...

Страница 27: ...able from your Napoleon dealer CHARCOAL EMBERS LOGO PLACEMENT GLOWING EMBERS VERMICULITE Remove the backing of the logo supplied and place on the glass viewing door as indicated FIGURE 61 CONTROL FUNC...

Страница 28: ...o the two corresponding spade connectors on the back of the on off switch for the burner located behind the lower access panel Repeat connecting the wires to the Night LightTM on off switch for remote...

Страница 29: ...ETY READ BEFORE OPERATING OPERATION MAINTENANCE MAINTENANCE TURN OFF THE GAS AND UNPLUG ELECTRICAL POWER BEFORE SERVICING THE STOVE Caution Label all wires prior to disconnection when servicing contro...

Страница 30: ...TMENTS PILOT INJECTOR AND ORIFICE REPLACEMENT VENTURI ADJUSTMENT Remove the 2 screws securing the burner Natural gas models have air shutters set to 0 031 open 1 32 Propane models have air shutters se...

Страница 31: ...R SLEEVE 22 W010 0567 ROOF SUPPORT 23 W170 0063 STORM COLLAR 24 W263 0055 ROOF FLASHING GD112 FLAT ROOF 20 W670 0006 AIR TERMINAL 21 W490 0073 4 7 INNER OUTER SLEEVE 22 W010 0567 ROOF SUPPORT 23 W170...

Страница 32: ...32 W415 0612 C 01 25 08 25 29 6 7 27 5 12 1 2 3 21 8 18 24 21 20 23 22 17 31 4 32...

Страница 33: ...ire about 3 16 away from the I terminal on the module If no spark the I terminal module must be replaced If there is a spark the I terminal is fine Inspect pilot assembly for a shorted wire or cracked...

Страница 34: ...cted in the right order Module or Valve Conduct the following test to verify if the problem is the module or valve To measure voltages turn multimeter to DC place the red lead from multimeter on the s...

Страница 35: ...35 W415 0612 C 01 25 08 Fireplace Service History This fireplace must be serviced annually depending on usage DATE DEALER NAME SERVICE TECHNICIAN NAME SERVICE PERFORMANCE SPECIAL CONCERNS...