25
W415-0583 / D / 07.24.07
FIGURE 60
Adjust the pilot screw to provide properly sized fl ame. Turn
in a clockwise direction to reduce the gas fl ow.
FIGURE 61
ADJUSTMENTS
PILOT BURNER ADJUSTMENT
TURN OFF THE GAS AND ELECTRICAL POWER
BEFORE SERVICING THE FIREPLACE.
CAUTION: Label all wires prior to disconnection when servic-
ing controls. Wiring errors can cause improper and danger-
ous operation. Verify proper operation after servicing. This
fi replace and its venting system should be inspected before
use and at least annually by a qualifi ed service person. The
fi replace area must be kept clear and free of combustible
materials, gasoline or other fl ammable vapours and liquids.
The fl ow of combustion and ventilation air must not be ob-
structed.
1.
In order to properly clean the burner and pilot as-
sembly, remove the bowl and rockset to expose both
assemblies.
2.
Keep the control compartment, bowl and rockset,
burner, air shutter opening and the area surrounding
the logs clean by vacuuming or brushing,
at least
once a year
.
3.
Check to see that all burner ports are burning. Clean
out any of the ports which may not be burning or are
not burning properly.
4.
Check to see that the pilot fl ame is large enough to
engulf the thermocouple and thermopile and reaches
toward the burner with the third jet.
5.
Replace the cleaned bowl and rockset.
6.
Check to see that the main burner ignites completely
on all openings when the gas knob for the burner
is turned on. A 5 to 10 second total light-up period
is satisfactory. If ignition takes longer, consult your
Napoleon® dealer / distributor.
7.
Check that the gasketing on the sides, top and bot-
tom of the door is not broken or missing. Replace if
necessary.
MAINTENANCE
3/8” - 1/2”
It is important to periodically perform a visual check of the pilot
and burner fl ames. Compare them to the illustration below.
FLAME CHARACTERISTICS
Check Pressure Readings:
(Fig. 60)
Inlet pressure can be checked by turning screw (A) coun-
ter-clockwise 2 or 3 turns and then placing pressure gauge
tubing over the test point. Gauge should read 7” (minimum
4.5”) water column for natural gas or 13” (11” minimum) water
column for propane. Check that main burner is operating
on “HI”.
Outlet pressure can be checked the same as above using
screw (B). Gauge should read 3.5” water column for natural
gas or 10” water column for propane. Check that main burner
is operating on “HI”.
AFTER TAKING PRESSURE READINGS, BE SURE TO
TURN SCREWS CLOCKWISE FIRMLY TO RESEAL. DO
NOT OVERTORQUE.
Leak test with a soap and water solution.
PILOT
SCREW
A
B
Содержание Tureen GD82NT-T
Страница 9: ...9 W415 0583 D 07 24 07 FIGURE 12 ...
Страница 23: ...23 W415 0583 D 07 24 07 DIP SWITCH NUMBER 0 ON 1 OFF FIGURE 57 ...
Страница 32: ...32 W415 0583 D 07 24 07 NOTES ...