background image

13

WS-415-55 / 11.10.97

TROUBLE SHOOTING GUIDE

White / grey film forms.

Sulphur from fuel is being
deposited on glass, logs or
combustion chamber sur-
faces.

-  clean the glass with a recommended gas glass cleaner or a
non-abrasive ammonia or vinegar based glass cleaner. DO NOT
CLEAN GLASS WHEN HOT.  If deposits are not cleaned off regu-
larly, the glass may become permanently marked.

SYMPTOM

SYMPTOM

SYMPTOM

SYMPTOM

SYMPTOM

PROBLEM

PROBLEM

PROBLEM

PROBLEM

PROBLEM

TEST SOLUTION

TEST SOLUTION

TEST SOLUTION

TEST SOLUTION

TEST SOLUTION

B

EFORE

 

ATTEMPTING

 

TO

 

TROUBLESHOOT

PURGE

 

YOUR

 

UNIT

 

AND

 

INITIALLY

 

LIGHT

 

THE

 

PILOT

 

AND

 

THE

 

MAIN

 

BURNER

 

WITH

 

THE

 

GLASS

 

DOOR

 

REMOVED

.

Exhaust fumes smelled
in room, headaches.

Fireplace is spilling.

-  check all seals. Check venting action. Consult with a qualified

inspector.

Pilot will not light.

Out of propane gas

-  fill the tank.

-   check if pilot can be lit by a match
-  check that the wire is connected to the push button ignitor.
-  check if the push button ignitor needs tightening.
-  replace the wire if the wire insulation is broken or frayed.
-  replace the electrode if the ceramic insulator is cracked or bro-
ken.
-  replace the push button ignitor.

No spark at pilot burner

Spark gap is incorrect

-  spark gap should be 0.150" to 0.175" (5/32" to 11/64" approx.)
from the electrode tip and the pilot burner. To ensure proper elec-
trode location, tighten securing nut (finger tight plus 1/4 turn).

-  check that the manual valve is turned on.
-  check the pilot orifice for blockage.
-  replace the valve.
-  call the gas distributor.

No gas at the pilot burner

PILOT

THERMOPILE

BURNER

ELECTRODE

THERMO-
COUPLE

Pilot goes out when the
gas knob is released.

System is not correctly
purged.

Out of propane gas.

Pilot flame is not large
enough

The gas valve has an
interlock device which
will not allow the pilot
burner to be lit until the
thermocouple has
cooled. Allow approxi-
mately 60 seconds for
the thermocouple to
cool.

-  turn up the pilot flame.

Pilot flame is not engulfing the
thermocouple.

-  loosen and tighten thermocouple.
-  clean thermocouple and valve connection.
-  replace thermocouple.
-  replace valve.

Thermocouple shorting.

Faultly thermocouple.

 Faulty valve.

-  replace.

-  fill the tank.

-  purge the gas line.

-  turn up the pilot flame.

-  replace.

Carbon is being depos-
ited on glass, logs or
combustion chamber
surfaces.

Flame is impinging on the
logs or combustion cham-
ber.

-  check that the logs are correctly positioned.
-  open air shutter to increase the primary air.
-  check the input rate: check the manifold pressure and orifice
size as specified by the rating plate values.
- check that the door gasketing is not broken or missing and that
the seal is tight.
- check that both 4" and 7" vent liners are free of holes and well
sealed at all joints.
- check that minimum rise per foor has been adhered to for any
horizontal venting.

Air shutter has become
blocked

-  ensure air shutter opening is free of lint or other obstructions.

Содержание GS3500 - N

Страница 1: ...96 RESPECTIVELY FOR GAS FIRED VENTED ROOM HEATER AND VENTED DECORATIVE GAS APPLIANCE W W W W WARNING ARNING ARNING ARNING ARNING Improper installation adjustment alteration service or maintenance can...

Страница 2: ...to operating the stove It is imperative that the control compartments burners and circulating blower and its passageway in the stove and venting system are kept clean The stove and its venting system...

Страница 3: ...es the prior approval of an authorized company official Labour costs to work however requires the prior approval of an authorized company official Labour costs to the account of the account of the acc...

Страница 4: ...of specific recommendations from the local authority having jurisdiction the certified high altitude input rating shall be reduced at the rate of 4 for each additional 1 000ft Maximum output for natur...

Страница 5: ...approximately 2 from the crimped end of the 6 diameter chimney section to be inserted into the 6 1 4 canopy opening minimum 18 from stove top to ceiling NO ADDITIONAL FLOOR PROTECTION IS REQUIRED NO...

Страница 6: ...at least 2 feet higher than any wall roof or building within 10 feet FIGURE 4 This is a guide line only local venting codes should be followed which may differ in height and clearance requirements IN...

Страница 7: ...m left of the stove back panel Attach the terminal of the ground wire green to the threaded weld stud and secure with a nut 6 Connect one bare lead of wire B to the white wire of the speed switch usin...

Страница 8: ...o the log support brackets located on the rear wall of the combustion chamber The notch situated at the lower left of the back log should be centered evenly above the pilot assembly FIGURE 13 3 While...

Страница 9: ...of the dilution hood visible through the rear wall opening and extend it 1 into the dilution hood 4 Venting action is satisfactory if smoke is drawn into the draft dilution hood and the flame rises v...

Страница 10: ...and turn gas knob counter clockwise to on 8 If equipped with remote on off switch ther mostat main burner may not come on when you turn valve to on Remote switch must be in the on position to ignite...

Страница 11: ...E GLASS FRAME POLISHED BRASS FACIA BLACK TRIVET CHARCOAL EMBERS ASH FENDER TRIM C W CORNER BRACKET ADJUSTMENTS PILOT BURNER ADJUSTMENT PILOT BURNER ADJUSTMENT PILOT BURNER ADJUSTMENT PILOT BURNER ADJU...

Страница 12: ...TION DESCRIPTION DESCRIPTION DESCRIPTION GOLD PLATED TRIVET STOVE PIPE ADAPTER BRASS DECORATIVE BRASS BAND REMOTE WALL SWITCH c w 20FT WIRE DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION...

Страница 13: ...ion tighten securing nut finger tight plus 1 4 turn check that the manual valve is turned on check the pilot orifice for blockage replace the valve call the gas distributor No gas at the pilot burner...

Страница 14: ...ain burner goes out pilot goes out REFER TO MAIN BURNER GOES OUT PILOT STAYS ON Thermopile shorting Remote wall switch wire is too long too much resistance in the system Faulty thermostat or switch sh...

Отзывы: