background image

23

W415-0210 / R / 02.27.08

36

3

/

4

"

37

3

/

4

"

52"

37

3

/

4

38

3

/

4

3”

14

1

/

2

63” (TOP EXIT)

42

1

/

4

” (REAR EXIT)

ENCLOSURE

TOP

FINISHING
MATERIAL

5

1

/

2

GAS
INLET
LOCATION

1

1

/

2

MAXIMUM

14”

MINIMUM

3

1

/

2

MAXIMUM

TOP EXIT INSTALLATION 
SHOWN

For top exit applications: Do not build into this area - it 
must be left clear to provide adequate clearance for the 
vent.  In this 14” wide area centred along the front of 

the fireplace, no combustibles are allowed.

!

WARNING

It is best to frame your fi replace after it is positioned and the 
vent system is installed. Frame to local building codes.

It is not necessary to install a hearth extension with this 
fi replace system. 

When roughing in the fireplace, raise the fireplace to 
accommodate for the thickness of the fi nished fl oor materials, 
i.e. tile, carpeting, hard wood, which if not planned for will 
interfere with the opening of the lower access door and the 
installation of many decorative fl ashing accessories.

Note:

 In order to avoid the possibility of exposed insulation 

or vapour barrier coming in contact with the fi replace body, 
it is recommended that the walls of the fi replace enclosure 
be “fi nished” (ie: drywall/sheetrock), as you would fi nish any 
other outside wall of a home. This will ensure that clearance 
to combustibles is maintained within the cavity.

Combustible materials may be installed fl ush with the front of 
the fi replace but must not cover any of the black face-areas 
of the fi replace. Non-combustible material (brick, stone or 
ceramic tile) may protrude in these areas. 

FIGURE 45

Bend and secure the top stand-off(s) as illustrated:

A

B

C

STAND-OFF ASSEMBLY

MINIMUM FRAMING DIMENSIONS

FIGURE 44 a-d

Combustion protrusions such as mantels and shelves may occur at or after a 
minimum distance of 2" away from the side of the fi replace.  Thereafter, the 
depth of any protrusions must be equal to or less than the distance from the 
side of the fi replace up to a depth of 6", after which no greater clearance than 
6" is required.  This can be considered a side wall with no length boundary.

GD36 FRAMING

37

3

/

4

"

14

1

/

2

"

OUTSIDE

CHASE

14

1

/

2

"

INSIDE

CHASE

37

3

/

4

"

4

"

2

"

SIDE

WALL

2

"

4

"

6

"

PROTRUSION

* HORIZONTAL VENT SECTIONS - A minimum clearance of 1" at the 
bottom and sides and 2" at the top of the vent pipe on all horizontal 
runs to combustibles is required.  Use fi restop spacer W010-1777 
(supplied).
* VERTICAL VENT SECTIONS - A minimum of 1" all around the 
vent pipe on all vertical runs to combustibles is required except 
for clearances in fi replace enclosures.  See "Minimum Enclosure 
Clearances" section.  Use firestop spacer W500-0096 (not 
supplied).

Minimum clearance to combustible construction from 

fi

 replace and vent surfaces:

Combustible Framing:

 

 

0"  to stand-offs

 

1"  to bottom and sides of the vent pipe*

 

2"  to top of the vent pipe*

Combustible Finishing:

 

 

0"  to rear

 

0"  to front face top and sides

 

14 1/4"  recessed depth

 

 Rear 

Exit

 

42 1/4"  to enclosure top from base of the unit

 

72"  to ceiling from base of the unit

 Top 

Exit

 

63"  to enclosure top from base of the unit

 

72"  to ceiling from base of the unit

NorthlineExpress.com

http://www.northlineexpress.com

Toll-Free 1-866-667-8454

Содержание GD36NTR

Страница 1: ...other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighb...

Страница 2: ...ace is out the glass and or screen will remain hot for an extended period of time Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfac...

Страница 3: ...3 W415 0210 R 02 27 08 NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454...

Страница 4: ...le or other combustible material other than wood flooring the fireplace shall be installed on a metal or wood panel extending the full width and depth If the optional fan or blower is installed the ju...

Страница 5: ...r the first 10 hours of operation with a recommended gas fireplace glass cleaner Thereafter clean as required DO NOT CLEAN GLASS WHEN HOT If the glass is not kept clean permanent discolouration and or...

Страница 6: ...RISE ON HORIZONTAL VENTING BGD36 REQUIRED RISE ON HORIZONTAL VENTING REAR VENT RIGID VENTING 1 FT REAR VENT RIGID VENTING 0 FT FLEXIBLE VENTING 1 FT FLEXIBLE VENTING 0 FT TOP VENT RIGID VENTING 0 FT...

Страница 7: ...4a 20 MAXIMUM FIGURE 4b BGD36 ONLY WITH RIGID ONLY 6 RISE MINIMUM FIGURE 2c FIGURE 2d GD36 See chart on Page 6 20 MAXIMUM 241 4 MINIMUM PLUS RISE 24 MAXIMUM 24 MINIMUM 57 MINIMUM PLUS RISE 33 BGD36 F...

Страница 8: ...8 W415 0210 R 02 27 08 FIGURE 5 MINIMUM AIR TERMINAL LOCATION CLEARANCES NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454...

Страница 9: ...to or greater t h a n t h e horizontal run Horizontal run verti cal rise to m a x i m u m of 40 feet Vertical rise is equal to or greater t h a n t h e horizontal run Horizontal run verti cal rise to...

Страница 10: ...than less than equal to or less than HT total of both horizontal vent lengths HR and offsets HO in feet HR combined horizontal vent lengths in feet HO offset factor 03 total degrees of offset 90 in f...

Страница 11: ...1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 360 90 8 1 ft HT HR HO 5 5 8 1 13 6 ft HT VT 13 6 5 5 19 1 ft Formula 1 HT 4 2 VT 4 2 VT 4 2 x 5 5 23 1 ft 13 6 23 1 Formula 2 HT VT 24 75 feet 1...

Страница 12: ...0 03 90 90 90 90 90 8 1 ft HT HR HO 6 5 8 1 14 6 ft HT VT 14 6 15 29 6 ft Formula 1 HT VT 14 6 15 Formula 2 HT VT 40 feet 29 6 40 Since both formulas are met this vent configuration is acceptable FIGU...

Страница 13: ...4 75 Since both formulas are met this vent configuration is acceptable FIGURE 14 For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT 3 5VT Formula 2 HT...

Страница 14: ...this vent configuration is acceptable Simple venting configurations FIGURE 15 For vent configurations requiring more than zero 90 elbow top exit or one 90 elbow rear exit the following formulas apply...

Страница 15: ...t this vent configuration is unacceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas Example 8 V1 1 5 ft V2 5 ft VT V1 V2 1 5 5 6 5 ft H1 1...

Страница 16: ...through the heat shield and out through the retaining ring Secure the assembly to the rear and top of the unit using 4 8 x Hex Head Wildrill screws supplied Do not overtighten The gasket needs only to...

Страница 17: ...may need to be repositioned to ensure a rigid assembly is maintained Figure 25 2 Apply a bead of caulking not supplied to the inside surface of the firestop flange and secure the assembly to the wall...

Страница 18: ...nt any materials such as insulation from filling up the 1 air space around the pipe VERTICAL INSTALLATION FIGURE 29 FIGURE 28 FIRESTOP UNDERSIDE OF JOIST 9 1 2 9 1 2 SHIELD FIGURE 30 VENT PIPE COLLAR...

Страница 19: ...IBLE VENT PIPE SCREWS 10x2 VENT PIPE 2 OVERLAP 7 FLEXIBLE 4 FLEXIBLE VENT PIPE CAULKING ATTENTIO N C HAUD CAUTIO N HOT HIGH TEMPERATURE SEALANT FIGURE 32 1 Stretch the 4 flexible vent pipe to the requ...

Страница 20: ...ing material Figure 36 6 Aligning the seams of the terminal and air terminal connector place the terminal over the air terminal connector making sure the vent pipe goes into the hole in the terminal S...

Страница 21: ...this case the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support 3 Apply high temperature sealant W573 0...

Страница 22: ...tes or the Mobile Home Standard CAN CSA Z240 MH Series in Canada This appliance is only for use with the type s of gas indicated on the rating plate A conversion kit is supplied with the mobile home a...

Страница 23: ...material brick stone or ceramic tile may protrude in these areas FIGURE 45 Bend and secure the top stand off s as illustrated A B C STAND OFF ASSEMBLY MINIMUM FRAMING DIMENSIONS FIGURE 44 a d Combust...

Страница 24: ...ace areas of the fireplace Non combustible material brick stone or ceramic tile may protrude in these areas MINIMUM FRAMING DIMENSIONS FIGURE 46 a d Combustion protrusions such as mantels and shelves...

Страница 25: ...ires a minimum enclosure height of 483 8 Fortemperaturerequirements theenclosurespace around and above the fireplace must be left unobstructed The fireplace requires a minimum enclosure height of 63 F...

Страница 26: ...on of the nailing tab you must first determine the thickness of your finishing material i e drywall This will determine the dimension from the front edge of the corner post to the nailing tab Once the...

Страница 27: ...t LOWER LOUVRES Insert the hinge clips into the slots located at the bottom left and right corners of the unit To remove the louvres pull the back tabs of the clips forward while pushing the louvre as...

Страница 28: ...of the bag should not be used Sprinkle vermiculite around the charcoal embers Note Both charcoal embers and vermiculite are not to be placed on the burner Tear the embers into pieces and place along...

Страница 29: ...touch the fireplace base or the firebox FIGURE 59 FIGURE 60 Attach the connectors from the black and white wires to the thermodisc and secure the thermodisc bracket to the securing stud at the bottom...

Страница 30: ...on box at the bottom left of the unit using the lock washer and wing nut Ensure that the thermodisc touches the firebox wall When installed ensure that any excess wire is contained pre venting it from...

Страница 31: ...knob while lighting the pilot with the push button igniter Keep knob depressed for one minute then release If pilot does not continue to burn repeat steps 3 through 5 7 With pilot lit depress and tur...

Страница 32: ...THERMOCOUPLE THERMOPILE Adjust the pilot screw to provide properly sized flame Turn in a clockwise direction to reduce the gas flow FIGURE 70 VENTURI ORIFICE AIR SHUTTER OPENING FIGURE 72 FIGURE 69 P...

Страница 33: ...PLATE KIT 65 VS47KT VENT SLEEVE 66 W573 0002 HIGH TEMPERATURE SEALANT 67 W573 0007 HIGH TEMPERATURE SEALANT PART NO DESCRIPTION 1 W225 0058 BLACK DOOR FRAME 2 W357 0001 PIEZO IGNITER 3 W680 0004 THERM...

Страница 34: ...0 1774 FIRESTOP SPACER BGD36 ACCESSORIES 76 W175 0159 CONVERSION KIT NG TO LP 77 W175 0164 CONVERSION KIT LP TO NG GD36 COMPONENTS 68 W455 0017 42 NATURAL GAS ORIFICE 68 W455 0003 54 PROPANE GAS ORIFI...

Страница 35: ...ot burner check that the manual valve is turned on check the pilot orifice for blockage replace the valve call the gas distributor Pilot goes out when the gas knob is re leased The gas valve has an in...

Страница 36: ...nt or other obstructions Pilot goes out while standing Main burner is in OFF position Gas piping is undersized turn on all gas appliances and see if pilot flame flutters diminishes or extinguishes esp...

Отзывы: