WS-415-112 / 06.18.99

INSTALLATION

USING RIGID VENT COMPONENTS

FOR SAFE AND PROPER OPERATION OF THE FIREPLACE, FOLLOW THE VENTING

INSTRUCTIONS EXACTLY.

FOR OPTIMUM PERFORMANCE, IT IS RECOMMENDED THAT ALL HORIZONTAL RUNS

HAVE A MINIMUM ¼ INCH RISE PER FOOT.

The vent system must be supported approximately every 3 feet for both vertical and horizontal runs.  Use Napoleon vent
spacers 

WS-615-33

 or equivalent every 3 feet and either side of each elbow to maintain the minimum 1¼" clearance

between the outer and inner vent pipes. Use Napoleon support ring assembly 

GA-GD-010.370

 or equivalent noncom-

bustible strapping to maintain the minimum 1" clearance to combustibles for both vertical and horizontal runs.

HORIZONT

HORIZONT

HORIZONT

HORIZONT

HORIZONTAL AIR TERMINAL INST

AL AIR TERMINAL INST

AL AIR TERMINAL INST

AL AIR TERMINAL INST

AL AIR TERMINAL INSTALLA

ALLA

ALLA

ALLA

ALLATION

TION

TION

TION

TION

1. 

Move the fireplace into position. Measure the vent

length required between terminal and fireplace taking
into account the additional length needed for the fin-
ished wall surface and any 1¼" overlaps between vent-
ing components.

2. 

Apply high temperature sealant to the outer edge

of the 4" inner collar of the fireplace.  Attach the first vent
component and secure using 3 self tapping screws. Re-
peat using 7" piping.

3. 

Holding the air terminal (lettering in an upright, readable po-

sition), insert into both vent pipes with a twisting motion to ensure
that both the terminal sleeves engage into the vent pipes and the sealant. Secure the terminal to the exterior wall and
make weather tight by sealing with caulking (not supplied). 

 

The air terminal mounting plate may be recessed to a

maximum of 

3

/

4

" into the exterior wall or siding.

EXTENDED HORIZONT

EXTENDED HORIZONT

EXTENDED HORIZONT

EXTENDED HORIZONT

EXTENDED HORIZONTAL AND CORNER AIR TERMINAL INST

AL AND CORNER AIR TERMINAL INST

AL AND CORNER AIR TERMINAL INST

AL AND CORNER AIR TERMINAL INST

AL AND CORNER AIR TERMINAL INSTALLA

ALLA

ALLA

ALLA

ALLATION

TION

TION

TION

TION

A 45° corner installation can have 0 inch rise between the fireplace combustion air
collar and the air terminal. 

 

In this case, vent lengths must be kept to a maximum of

36". For longer vent lengths, a minimum vertical rise of 24" is required. 

FIGURE 2c.

1. 

Follow the instructions for "Horizontal Air Terminal Installations", items 1 to 2.

2. 

Continue adding components alternating inner and outer venting. Ensure that

all 4" venting and elbows have sufficient vent spacers attached and each compo-
nent is securely fastened to the one prior. Attach the 4" telescopic sleeve to the vent
run. Repeat using a 7" telescopic sleeve. Secure and seal as before. To facilitate
completion, attach 4" and 7" couplers to the air terminal.

3.

Install the air terminal. 

See item 3 above.

 Extend the 4" telescopic sleeve;

connect to the air terminal assembly. Fasten with self tapping screws and seal.
Repeat using the 7" telescopic sleeve.

FIGURE 15

TELESCOPIC SLEEVE

VENTING

20" 
COUPLER

AIR TERMINAL

FIGURE 16

Содержание GD16 - N

Страница 1: ...ESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS CSA 2 22 AND ANSI Z21 50 RESPECTIVELY FOR VENTED GAS FIREPLACES Fax 705 722 6031 Email ask napoleon on ca Web www napoleon on ca Wolf Steel Ltd RR 1 9 Napoleon Rd Barrie ON Canada L4M 4Y8 705 721 1212 R 2000 W W W W WARNING ARNING ARNING ARNING ARNING If the information in th...

Страница 2: ...im Removal Installation Log Placement PG PG PG PG PG 17 17 17 17 17 OPTIONAL BLOWER INST OPTIONAL BLOWER INST OPTIONAL BLOWER INST OPTIONAL BLOWER INST OPTIONAL BLOWER INSTALLA ALLA ALLA ALLA ALLATION TION TION TION TION 18 18 18 18 18 OPTIONAL F OPTIONAL F OPTIONAL F OPTIONAL F OPTIONAL FAN INST AN INST AN INST AN INST AN INSTALLA ALLA ALLA ALLA ALLATION TION TION TION TION THERMOST THERMOST THER...

Страница 3: ...es the prior approval of an authorized company official Labour costs to work however requires the prior approval of an authorized company official Labour costs to the account of the account of the account of the account of the account of NAPOLEON NAPOLEON NAPOLEON NAPOLEON NAPOLEON are based on a predetermined rate schedule and any repair work are based on a predetermined rate schedule and any rep...

Страница 4: ...nse of specific recommendations from the local authority having jurisdiction the certified high altitude input rating shall be reduced at the rate of 4 for each additional 1 000ft Maximum output for natural gas is 12 500 BTU hr at an efficiency of 73 5 with the fan on and 12 750 BTU hr for propane at an efficiency of 75 with the fan on Minimum inlet gas supply pressure is 4 5 inches water column f...

Страница 5: ... Do not operate the fireplace with the glass door removed cracked or broken Replacement of the glass should be done by a licensed or qualified service person Use only with a glass door certified with the fireplace Do not strike or slam shut the fireplace glass door FIGURE 1 For safe and proper operation of the fireplace follow the venting instruction exactly Deviation from the minimum vertical ven...

Страница 6: ...R TERMINAL LOCA VENTING LENGTHS AND AIR TERMINAL LOCATIONS TIONS TIONS TIONS TIONS Use only Napoleon or Simpson Dura Vent Model DV GS venting components Minimum and maximum vent lengths for both horizontal and vertical installations and air terminal locations for these installations are set out in this manual and must be adhered to For Simpson Dura Vent follow the installation procedure provided w...

Страница 7: ...EET Clearance above grade veranda porch deck or balcony Clearance to windows or doors that open Clearance to permanently closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to unventilated soffit Clearance to an outside corner wall Clearance to an inside non combustible corner wall or...

Страница 8: ...on dealer See Accessories to order the specific kit required 1 Determine the air terminal location cut and frame 9 inch openings in the ceiling and the roof to provide the minimum 1 inch clearance between the fireplace pipe liner and any combustible material Try to center the exhaust pipe location midway between two joist to prevent having to cut them Use a plumb bob to line up the center of the o...

Страница 9: ...rior wall or siding 4 From outside apply a bead of the high temperature sealant to the inside of both liners approximately 1 from the end of each liner 5 Holding the air terminal lettering in an upright readable position insert into both liners with a twisting motion to ensure that both the terminal sleeves engage into the liners sealant Secure the terminal to the exterior wall and make weather ti...

Страница 10: ... the air terminal and slide it underneath the sides and upper edge of the shingles Ensure that the air terminal is properly centered within the flashing giving a 3 4 margin all around Fasten to the roof Do not nail through the lower portion of the flashing Make weather tight by sealing with caulking Where possible cover the sides and top edges of the flashing with roofing mate rial 6 Apply a heavy...

Страница 11: ...nto both vent pipes with a twisting motion to ensure that both the terminal sleeves engage into the vent pipes and the sealant Secure the terminal to the exterior wall and make weather tight by sealing with caulking not supplied The air terminal mounting plate may be recessed to a maximum of 3 4 into the exterior wall or siding EXTENDED HORIZONT EXTENDED HORIZONT EXTENDED HORIZONT EXTENDED HORIZON...

Страница 12: ...rminal assembly as it is passed through the attic FIGURE 19 The air terminal must be located vertically and plumb 6 Remove nails from the shingles above and to the sides of the chimney Place the flashing over the air terminal and slide it underneath the sides and upper edge of the shingles Ensure that the air terminal is properly centered within the flashing giving a 3 4 margin all around Fasten t...

Страница 13: ...in a convenient location Route 2 strand solid core millivolt wire through the electrical hole located at the bottom left side of the unit The recommended maximum lead length depends on wire size WIRE SIZE MAX LENGTH 14gauge 100 feet 16gauge 60 feet 18gauge 40 feet Attach the two leads to terminals 1 and 3 located on the gas valve FIGURE 20 3 Install rigid black pipe 1 2 type L copper tubing or if ...

Страница 14: ...ed on either side of the fireplace and secure to the 2x4 framing to facilitate drywall installation and or secure the fireplace to the floor using 10 screws not supplied using the two diameter holes in the front left and right corners of the base Combustible materials must be installed flush with the front of the fireplace but must not cover any of the black face area of the fireplace Non combusti...

Страница 15: ...nal plated door trim door side trim and arched door facias are available at your local Napoleon Wolf Steel dealer LOG PLACEMENT LOG PLACEMENT LOG PLACEMENT LOG PLACEMENT LOG PLACEMENT PHAZERTM logs exclusive to Napo leon Fireplaces provide a unique and realistic glowing effect that is different in every installation POSITIONING THE LOGS IMPROP ERLY WILL CAUSE FLAME IMPINGE MENTANDCARBONING Positio...

Страница 16: ...ecure to the threaded stud using the lock washer and wing nut provided Ensure that the blower does not touch the fireplace base or the firebox Attach the connectors from the black and white wires to the thermodisc and secure the thermodisc bracket to the securing stud at the bottom left of the unit using a lock washer and wing nut Ensure that the thermodisc touches the firebox wall Attach the conn...

Страница 17: ...e the thermodisc bracket to the securing stud at the bottom left of the unit using a lock washer and wing nut Ensure that the thermodisc touches the firebox wall GD36THERMOSTATICSENSORCONTROL This optional kit is meant to be used only in conjunction with the GD65 Fan Kit shown above which may be ordered from your Wolf Steel Napoleon dealer With the thermostatic sensor option the fan when turned on...

Страница 18: ...do not try to repair it Call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this fireplace if any part has been under water Immediately call a qualified service technician to inspect the fireplace and replace any part of the control system and any gas control which has been under water P I N O L O T F F O GAS KNOB LIGHTINGINSTRUCTIONS WARNIN...

Страница 19: ...ace and its venting system should be inspected before use and at least annually by a qualified service person The fireplace area must be kept clear and free of combustible materials gasoline or other flammable vapours and liquids The flow of combustion and ventilation air must not be obstructed 1 In order to properly clean the burner and pilot assembly remove the logs to expose both assemblies 2 K...

Страница 20: ...CE WS 455 24 30 PROPANE GAS PILOT ORIFICE WS 725 25 NATURAL GAS VALVE WS 725 26 PROPANE GAS VALVE WS 750 09 IGNITER WIRE WS385 33 NAPOLEON LOGO WS 430 001 CERAMIC MAGNET GD660 STANDARD WALL SWITCH 20FT OF WIRE FLEXIBLE VENT KITS FLEXIBLE VENT KITS FLEXIBLE VENT KITS FLEXIBLE VENT KITS FLEXIBLE VENT KITS PART NO PART NO PART NO PART NO PART NO DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION DESCRIP...

Страница 21: ... 072 VENT PIPE SHIELD WS175 1 4 COUPLER WS175 13 7 COUPLER BM6087 7 TO 8 INCREASER GD 500 96 FIRE STOP FLEXIBLE VENTING GD 500 136 FIRESTOP RIGID VENTING GD 101 WINDSHIELD KIT GD 301 HEAT GUARD GD 303 VINYL SIDING SHIELD GD10 370 WALL SUPPORT ASSEMBLY GD 225 K DOOR FACIA BLACK GD 225 PB DOOR FACIA POLISHED BRASS GD6PB 6 TRIM KIT POLISHED BRASS GD 225 AB DOOR FACIA ANTIQUE BRASS GD 225C DOOR FACIA ...

Страница 22: ...l switch wire is too long too much resis tance in the system shorten wire to correct length or wire gauge Faulty thermostat or switch replace Pilot goes out when the gas knob is re leased The gas valve has an interlock device which will not allow the pilot burner to be lit until the ther mocouple has cooled Allow ap proximately 60 seconds for the thermocouple to cool System is not correctly purged...

Страница 23: ...nected from fireplace re attach to fireplace Remote wall switch is in OFF position main burner comes on when gas knob is turned to ON po sition Wall switch is mounted up side down reverse Faulty valve replace replace Remote wall switch is grounding check for ground short repair ground or replace wire Remote wall switch wire is grounding Main burner flame is a blue lazy transparent flame Blockage i...

Страница 24: ...24 WS 415 112 06 18 99 NOTES ...

Отзывы: