ADJUSTMENTS

VENTURI ADJUSTMENT

To access the air shutter, remove the control panel.  

Remove the two screws that secure the cover to the 

air housing and loosen the set screw to adjust the air 

shutter position.

Air shutter have been factory set open according to the 

chart below:

These settings are for (maximum) horizontal termination.

NG

0”

P

1/4”

Adjustments may be required depending on fuel type, 

vent configuration and altitudes.

Closing the air shutter will cause a more yellow flame, 

but can lead to carboning.  Opening the air shutter will 

cause a more blue flame, but can cause flame lifting 

from the burner ports.  The flame may not appear yellow 

immediately; allow 15 to 30 minutes for the final flame 

colour to the established.

Air shutter adjustment must be done by a qualified 

installer!

FLAME CHARACTERISTICS

GENERAL INFORMATION

Maximum Input Ratings:
 Natural Gas 

Propane

 17,000 BTU/hr  17,000 BTU/hr

Shown in 

“OFF” 

position.

Manual 

Shut-off Valve

A

B

It is important to periodically perform a visual check of the 

pilot and burner flames. Compare them to the illustrations 

provided. The distribution of the glass embers over the 

burner tube will influence the flame appearance.

Inlet pressure can be checked by turning screw (A) 

counter-clockwise until loosened and then placing 

pressure gauge tubing over the test point. Gauge should 

read 7” (minimum 4.5”) water column for natural gas or 

13” (11” minimum) water column for propane. Check that 

main burner is operating on “HI”.

Outlet pressure can be checked the same as above using 

screw (B). Gauge should read 3.5” water column for 

natural gas or 10” water column for propane. Check that 

main burner is operating on “HI”.

AFTER TAKING PRESSURE READINGS, TIGHTEN 

SCREWS FIRMLY TO SEAL. DO NOT OVERTORQUE.

LEAK TEST BY BRUSHING ON A SOAP AND WATER 

SOLUTION 

Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 0G8 Canada        •  1(866)820-8686         

 • www.napoleonfireplaces.com

W415-0970 / A / 05.12.17

VENTURI

AIR SHUTTER 

OPENING

ORIFICE

Содержание BGD36CFG

Страница 1: ...g key position for proper alignment FIGURE 4 FUEL CONVERSION FOR MODELS BGD36CFG BCDV36CFG This kit is for use at altitudes of 0 to 4 500 feet W175 0279 Propane to Natural Gas Kit Includes REGULATOR ASSEMBLY 1 48 BURNER ORIFICE 1 NATURAL GAS PILOT INJECTOR 1 CONVERSION DATA LABEL 1 INSTALLER THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOME OWNER CHECK THE BOXES TO INDICATE THAT THE CORRESPONDING STE...

Страница 2: ...pane 17 000 BTU hr 17 000 BTU hr Shown in OFF position Manual Shut off Valve A B It is important to periodically perform a visual check of the pilot and burner flames Compare them to the illustrations provided The distribution of the glass embers over the burner tube will influence the flame appearance Inlet pressure can be checked by turning screw A counter clockwise until loosened and then placi...

Страница 3: ...eux vis situées derrière le brûleur tubulaire FIGURE 2 4 Retirez l injecteur du brûleur principal en utilisant une clé à douille longue Utilisez une clé en même temps sur le collecteur situé sous le boîtier pour vous assurer que le tube d aluminium ne se torde ou ne se plie pas Remplacez l injecteur de brûleur existant par celui fourni en utilisant un composé à joint 5 Retirez la hotte de dérivati...

Страница 4: ...TU h 17 000 BTU h Illustrée à OFF Soupape d arrêt manuelle A B Il est important d effectuer périodiquement une inspection visuelle de la flamme de la veilleuse et du brûleur Comparez les à cette illustration La disposition des braises vitrifiées par dessus le brûleur tubulaire influencera l apparence de la flamme Pour vérifier la pression d arrivée tournez la vis A vers la gauche jusqu à ce qu ell...

Отзывы: