venting requirements

A.

Remove the safety barrier and glass front, refer to "safety 
barrier & door removal/installation" section.

B.

Remove the contents from the fi rebox and set aside, you will 
need the exhaust fl ue collar from the top of the log carton.

C.

 

To ease assembly, remove the four hex head screws 
securing the defl ector from inside the top front of the fi rebox, 
refer to Figure 1.

D.

 

Place the gasket (provided) over the 4" (102mm) fl ue collar 
assembly and bend along perforation.

E.

 

From inside the fi rebox, insert the 4" (102mm) fl ue collar through the back 
of the fi rebox. Install the rear exit shield onto the 4" (102mm) fl ue collar, see 
"rear exit shield" section for installation instructions.

F.

 

Secure the fl ue collar assembly, gasket and rear exit shield using the four hex 
head 3/8" thread cutting screws, refer to Figure 2. 

G.

 

Reattach the defl ector using the four screws and 
install the log set, glass door and safety barrier.

H.

 

Install the 7" collar assembly, complete with 
gasket, onto the rear panel around the 4" 
(101.6mm) collar with the screws provided (FIG 
3).

 Fig. 2

DEFLECTOR

É

 Fig. 1

2.10 rear 

exit

• 

Failure to create a seal to the fi rebox with the exhaust collar assembly will cause the appliance to function 
improperly and can cause injury or property damage.

!

WARNING

Do not overtighten. The gasket needs only to be 
snug against the fi rebox.

note:

Fig. 3

INTAKE COLLAR

ASSEMBLY

GASKET 

2.11  rear exit shield (for rear vent only)

A.

  

Remove the safety barrier assembly and door from the appliance, refer to the “safety barrier & door    

 

removal / installation” section of the manual for detailed instructions.

B.

  

Loosen the two screws, that secure the exhaust plate, and slide the shield in place by sliding its slotted  

 

openings behind the screwheads,  

 

tighten the two previously loosened  

 

screws. Refer to the illustration   .

C.

 

Reinstall the door and safety barrier  

 

assembly on the appliance, see to  

 

the “safety barrier & door  

 

 

removal / installation” section.

This shield is used to block the view 
through the venting to the outdoors.

note:

Содержание B30NTR-1

Страница 1: ...touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas suppli...

Страница 2: ...burns A physical barrier is recommended if there are at risk individuals in the house To restrict access to an appliance or stove install an adjustable safety gate to keep toddlers young children and...

Страница 3: ...anemia those under the in uence of alcohol those at high altitudes are more affected by carbon monoxide than others Failure to keep the primary air opening s of the burner s clean may result in sooti...

Страница 4: ...xisting chimney 36 4 4 1 restricting vertical vents 37 5 0 electrical information 38 5 1 battery back up installation 39 5 2 optional wall switch 40 6 0 gas installation 40 7 0 operation electronic 41...

Страница 5: ...rmal and are to be expected Change in ame appearance from HI to LO is more evident in natural gas than in propane This appliance is approved for bathroom bedroom and bed sitting room installations and...

Страница 6: ...with a power cord it must be connected into a properly grounded receptacle The grounding prong must not be removed from the cord plug The following does not apply to inserts as long as the required c...

Страница 7: ...d vacuation Il est n cessaire de bien r installer et resceller l vacuation apr s avoir executer l entretien du syst me de prise d air Optional fan kit AUB Ensemble de ventilateur facultatif AUB Electr...

Страница 8: ...W415 1768 C 03 08 19 EN 8 general information 34 5 8 879mm GAS INLET 14 355mm 6 11 16 170mm 1 13 16 46mm 30 762mm 12 3 4 324mm 4 102mm 178mm 7 24 3 16 614mm 8 5 8 136mm SAFETY BARRIER 1 4 dimensions...

Страница 9: ...venting systems must not be combined Different venting manufacturer components must not be combined These vent kits allow for either horizontal or vertical venting of the appliance The maximum allowab...

Страница 10: ...clearances Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows Keep it pulled tight A 1 31 8mm air gap all around between the inner liner and outer liner is required fo...

Страница 11: ...EN W415 1768 C 03 08 19 11 venting requirements REAR VENT 20 50 8cm Max 24 3 16 61 4cm minimum plus rise See venting section 40 ft 12m Maximum 3 ft 1m minimum 16 40 6cm minimum 24 3 16 61 4cm...

Страница 12: ...upplied with the appliance The insulation sleeve is not required with a stove appliance TOP VENT REAR VENT 2 2 special vent installations 2 2 1 periscope termination 12 30 5cm minimum to grade 30 76 2...

Страница 13: ...porch or deck N 16 40 6cm 16 40 6cm Clearance above the roof O 2 0 6m 2 0 6m Clearance from an adjacent wall including neighbouring buildings P 8 2 4m 8 2 4m Roof must be non combustible without open...

Страница 14: ...Termination Vertical rise is equal to or greater than the horizontal run Vertical rise is less than horizontal run Vertical rise is equal to or greater than the horizontal run Vertical rise is less t...

Страница 15: ...11 FT 3 4m H1 2 5 FT 0 8m H2 2 FT 0 6m HR H1 H2 2 5 FT 0 8m 2 FT 0 6m 4 5 FT 1 4m HO 03 three 90 elbows 90 03 270 90 5 4 FT 1 7m HT HR HO 4 5 FT 1 4m 5 4 FT 1 6m 9 9 FT 3m HT VT 9 9 FT 3m 11 FT 3 4m 2...

Страница 16: ...24 75 FT 7 5m Since both formulas are met this vent configuration is acceptable The shaded area within the lines represents acceptable values for HT and VT 90 V1 H1 H2 90 Example V1 4 FT 1 2m V2 1 5 F...

Страница 17: ...he shaded area within the lines represents acceptable values for HT and HT HT VT For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT VT Formula 2 HT VT...

Страница 18: ...25 5 9 For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT 3 5VT Formula 2 HT VT 24 75 feet 7 5m Example V1 4 FT 1 2m V2 1 5 FT 0 5m VT V1 V2 4FT 1 2m...

Страница 19: ...T VT For vent configurations requiring one or more 90 elbows top exit or one or more 90 elbows rear exit the following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet 12 2m Example V1 5 FT 1 5m...

Страница 20: ...FT 2 5m HT HR HO 8FT 2 4m 8 1FT 2 5m 16 1FT 4 9m HT VT 16 1FT 4 9m 4 5FT 1 4m 20 6FT 6 3m Formula 1 HT 3 5 VT 3 5 VT 3FT 0 9m x 4 5FT 1 4m 13 5 FT 4 1m 16 1FT 4 9m 13 5 FT 4 1m Since this formula is...

Страница 21: ...door and safety barrier H Install the 7 collar assembly complete with gasket onto the rear panel around the 4 101 6mm collar with the screws provided FIG 3 Fig 2 DEFLECTOR Fig 1 2 10 rear exit Failure...

Страница 22: ...J Place the 7 178mm intake collar and gasket onto the top of the appliance and secure with the four screws K Reinstall the outer cover without knock out over the 7 178mm exhaust collar assembly and s...

Страница 23: ...agging or loose insulation or framing and other combustible materials Block opening into the chase to prevent entry of blown in insulation Make sure insulation and other materials are secured When con...

Страница 24: ...ontal runs to combustibles is required Use restop spacer W010 1777 supplied NOTE The minimum clearances from the top of the horizontal vent pipe to combustible materials may be reduced from 3 76mm to...

Страница 25: ...EXIT ENCLOSURE The appliance requires a minimum non combustible enclosure height of 50 1 2 1283mm For temperature requirements the enclosure space around and above the appliance must be left unobstru...

Страница 26: ...the appliance must be left unobstructed For rear vent termination not exceeding 10 254mm of horizontal vent run NON COMBUSTIBLE 0 0MM IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK ANDSTONE 243 16 61...

Страница 27: ...must be left unobstructed MAXIMUM REAR VENT CLEARANCES EXAMPLE 1 COMBUSTIBLE NON COMBUSTIBLE 1 25mm 3 76mm BRICK 0 0MM IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK ANDSTONE 7 178mm 415 8 105 7cm 10...

Страница 28: ...must be left unobstructed MAXIMUM REAR VENT CLEARANCES EXAMPLE 2 241 8 61 3cm MINIMUM PLUSRISE COMBUSTIBLE NON COMBUSTIBLE 1 25mm 3 76mm BRICK 0 0MM IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK AND...

Страница 29: ...e After rough framing place the appliance in its nal position A B For heavier nishing materials such as marble we recommend adding extra support to the frame Ensure there is adequate oor support for t...

Страница 30: ...cannot slip off Do not clamp the exible vent pipe Risk of re explosion or asphyxiation Improper support of the entire venting system may allow vent to sag and separate Use vent run supports and conne...

Страница 31: ...ugh a roof Installation kits for various roof pitches are available from your authorized dealer distributor See the accessories section to order speci c kits required A Determine the air terminal loca...

Страница 32: ...er ex pipe to the required length taking into account the additional length needed for the nished wall surface Apply a heavy bead of the red RTV silicone W573 0002 not supplied to the inner sleeve of...

Страница 33: ...minal connector to the roof support ensuring that the top of the air terminal is 16 40 6cm above the highest point that it penetrates the roof E Remove nails from the shingles above and to the sides o...

Страница 34: ...V Silicone W573 0002 not supplied C Insert the vent pipes through the restop maintaining the required clearance to combustibles Apply a heavy bead of Red RTV Silicone W573 0002 not supplied to both th...

Страница 35: ...minal connector Place the ashing over the air terminal connector and slide it underneath the sides and upper edge of the shingles Ensure that the air terminal connector is properly centered within the...

Страница 36: ...air intake ex liner and the exhaust collar must be connected to the exhaust exible liner Both Simpson Duravent and Selkirk co linear to co axial adaptors have been approved on this appliance Follow v...

Страница 37: ...el approved restrictor kit This kit is not recommended for short vertical vent runs Depending on the model and or year of your appliance mounting holes may not exist A If mounting holes exist remove t...

Страница 38: ...valve or wall switch WARNING This appliance comes equipped with a battery back up If this backup is used install 4 AA batteries not sup plied into the holder and connect to the wire harness Connect t...

Страница 39: ...ontrol module to the black wire of the battery back up Ensure the protective sleeve covers the connections as shown below F Install 4 AA size batteries ensure the positive and negative ends correspond...

Страница 40: ...appliance Connect the gas supply in accordance to local codes In the absence of local codes install to the current CAN CSA B149 1 Installation Code in Canada or to the current National Fuel Gas Code A...

Страница 41: ...ed I Turn on the remote wall switch to the appliance J If the appliance will not operate follow instructions TO TURN OFF GAS and call your service technician or gas supplier A Set thermostat to lowest...

Страница 42: ...inue to burn repeat steps E through I J With pilot lit turn gas knob counter clockwise to the ON position K If equipped with the ame adjustment valve push and turn the knob to high L Turn on all elect...

Страница 43: ...768 C 03 08 19 43 nish framing 301 2 775mm 35 889mm 113 16 46mm 61 2 192mm 141 2 368mm GAS INLET LOCATION ELECTRICAL CONNECTION ENCLOSURE TOP FINISHING MATERIAL 9 0 nish framing 9 1 minimum framing di...

Страница 44: ...e Safety barrier Safety barrier WARNING Glass may be hot Do not touch glass until cooled If equipped with door latches that are part of a safety system they must be properly engaged Do not operate the...

Страница 45: ...oor and screen must be removed B Remove the securing screws from the top of the rebox as shown C Install the front hood ensure it is angled downward when installed D Reinstall the previously removed s...

Страница 46: ...greater projections are desired increase the clearance to the sides bottom and top by 2 50 8mm for every additional 1 25 4mm of projection If using an optional surround the same rule applies starting...

Страница 47: ...52 4mm 8 203 2mm 34 5 8 88cm 2 3 9 1 9 2 50 8mm 2 4 6 8 10 12 MANTEL DEPTH INCHES 4 101 6mm 6 152 4mm 10 254mm 12 30 5cm 8 203 2mm WARNING Risk of re Maintain all speci ed air space clearances to comb...

Страница 48: ...information Refer to the minimum mantel clearances section for detailed mantel clearance information Installing electronics or other materials that may be sensitive to heat on a recessed wall will als...

Страница 49: ...ur pigments burn in during the heat activated curing process A Place the rear log W135 0575 rmly onto the two studs at the rear of the support tray Ensure the log sits at and does not cover the pilot...

Страница 50: ...the right crossover log W135 0579 onto the two remaining pins B A C D E F Reinstall the door and safety screen 10 7 logo placement Remove the backing of the logo supplied and place as illustrated INS...

Страница 51: ...of the pilot assembly has occurred remove the paint from the pilot assembly or replace Fine emery cloth or a synthetic scrub pad such as Scotch Brite can be used to remove the paint from the pilot ho...

Страница 52: ...It s important to periodically perform a visual check of the pilot and burner ames Compare them to the illustration provided If any ames appear abnormal call a service person ADD IMAGE HERE 3 8 1 2 9...

Страница 53: ...ner 5 If your appliance is equipped with a safety barrier cleaning may be necessary due to excessive lint dust from carpeting pets etc simply vacuum using the brush attachment 6 If your appliance is e...

Страница 54: ...ss the blower and clean using a soft brush and vacuum Re assemble the various components in reverse order Inspect the relief system The appliance relieves through the main glass door or through the ap...

Страница 55: ...zor blades steel wool or other metallic objects must not be used on both surfaces of the glass Doing so can remove a thin layer of metal from the razor blades steel wool or other metallic objects that...

Страница 56: ...warranty replacement parts a photocopy of the original invoice will be required to honour the claim When ordering replacement parts always give the following information Model Serial Number of applia...

Страница 57: ...hing trim Right crossover log GL 694 W135 0579 Left crossover log GL 694 Rear log GL 694 W135 0578 W135 0575 2 1 Stocked Stocked Yes Yes Yes Yes Yes W385 2010 Napoleon logo 19 18 14 15 13 W562 0009 Do...

Страница 58: ...e NG Yes 35 W725 0063 886 Pro ame valve P Yes 36 W010 2763 Pilot assembly NG 36 W010 2808 Pilot assembly P W750 0270 Wire assembly Yes W455 0068 Pilot ori ce 35 P Yes W720 0062 Pilot tube w ttings Yes...

Страница 59: ...0025 Valve NG Yes W725 0043 Valve P Yes W357 0001 Push button ignitor Yes W010 0801 Pilot NG Yes W010 0800 Pilot P Yes W680 0004 Thermopile Yes W680 0005 Thermocouple Yes 32 34 W240 0006 Ignitor w wir...

Страница 60: ...ed 1 W565 0154 Safety screen Z30F H30F Yes 45 Z30F Black Zen Decorative Safety Barrie 46 H30F Black Heritage Decorative Safety Barrier 47 W430 0003 Magnet x16 TK30 Yes 48 W715 0981 Top bottom trim x2...

Страница 61: ...DO NOT OVER TORQUE Leak test with a soap and water solution Air shutter improperly adjusted Return air shutter to speci ed opening see venturi adjustments section in the installation manual Carbon is...

Страница 62: ...d Receiver if equipped Reset program hold reset button on receiver and wait for 2 beeps Release after second beep Press small ame button on remote within 20 seconds you will hear an additional beep th...

Страница 63: ...nce will start Starting from off press the on button on the transmitter Approximately 4 seconds on off button is pressed the ignition board will start the spark The rst try for ignition will last appr...

Страница 64: ...AKING PRESSURE READINGS BE SURE TO TURN SCREWS CLOCKWISE FIRMLY TO RESEAL DO NOT OVER TORQUE Leak test with a soap and water solution Air shutter improperly adjusted Return air shutter to speci ed ope...

Страница 65: ...y Loosen and tighten thermocouple Clean thermocouple and valve connection Replace thermocouple Replace valve Faulty valve Replace Pilot burning no gas to main burner gas knob is on HI wall switch ther...

Страница 66: ...t be caused by mechanical systems such as exhaust fans furnaces clothes dryers etc Any damages to the appliance combustion chamber heat exchanger plated trim or other components due to water weather d...

Страница 67: ...EN W415 1768 C 03 08 19 67 notes...

Страница 68: ...TI IN NG G O OV VE ER R 4 40 0 Y YE EA AR RS S A A A O O O O O OF F F F F F H H H H H H H HO O O O O OM M M M ME E E E E C C CO OM M MF F FO OR RT T P PR RO OD DU UC CT TS S 7200 Route Transcanadienne...

Страница 69: ...tallateur quali une agence d entretien ou le fournisseur Cet appareil peut tre install dans une maison pr fabriqu e mobile d j install e demeure si les r glements locaux le permettent Cet appareil doi...

Страница 70: ...aux br lures accidentelles Une barri re de protection est recommand e si des individus risque se trouvent dans la maison A n de restreindre l acc s l appareil installez une barri re de protection ajus...

Страница 71: ...eut entra ner la formation de suies et dommages la propri t Comme dans le cas de tout appareil combustion il est recommand de faire inspecter et entretenir votre appareil r guli rement De m me install...

Страница 72: ...103 4 3 5 installation de la terminaison verticale 104 4 4 terminaison verticale travers une chemin e existante 105 4 4 1 renstreignant des vents verticaux 106 5 0 information lectriques 107 5 1 insta...

Страница 73: ...a tre r duit au taux de 4 pour chaque 1 000ft 305m suppl mentaire Les bruits caus s par l expansion et la contraction lors des cycles de chauffage et de refroidissement sont tout fait normaux et il fa...

Страница 74: ...cas o le souf erie est quip d un cordon d alimentation il doit tre connect une r ceptacle correctement mise la terre La che de mise la terre ne doit pas tre retir du cordon d alimentation Ce qui suit...

Страница 75: ...ons d vacuation Il est n cessaire de bien r installer et resceller l vacuation apr s avoir executer l entretien du syst me de prise d air Optional fan kit AUB Ensemble de ventilateur facultatif AUB El...

Страница 76: ...19 76 FR information g n rales 1 4 dimensions 34 5 8 879mm GAS INLET 14 355mm 6 11 16 170mm 1 13 16 46mm 30 762mm 12 3 4 324mm 4 102mm 178mm 7 24 3 16 614mm 8 5 8 136mm SAFETY BARRIER ENTR E DU GAZ C...

Страница 77: ...e tous les autres syst mes d vents approuv s l exception du raccordement du conduit d vacuation la buse du foyer qui doit tre scell avec le scellant noir haute temp rature Mill Pac Le scellant haute t...

Страница 78: ...ors d utilisation d vacuation exible A n d assurer un fonctionnement s curitaire et ad quat de l appareil vous devez observez les instructions d vacuation la lettre Une terminaison ne doit pas tre ins...

Страница 79: ...5 1768 C 03 08 19 79 exigences d vacuation FR Voir la section vacuation 40pi 12m Maximum 3pi 1m minimum 24 3 16 61 4cm 16 40 6cm minimum 20 50 8cm Max 24 3 16 61 4cm plus la pente vacuation sur l arri...

Страница 80: ...on isolant est illustr dans l illustration ci dessous de l vacuation sur le sessus utiliser seulement lorsqu ils sont fournis avec l appareil Un manchon isolant n est pas requis avec une appareil po l...

Страница 81: ...rs adjacents incluant les maisons voisines P 8 2 4m 8 2 4m Le toit doit tre incombustible et sans ouvertures Q 3 0 9m 3 0 9m Voir le tableau pour les dimensions d un mur plus large R 6 1 8m 6 1 8m Voi...

Страница 82: ...izontale La course verticale est plus petite que la course horizontale La course verticale est plus grande ou gale la course horizontale La course verticale est plus petite que la course horizontale L...

Страница 83: ...30 9 1 17 5 5 3 20 6 1 39 11 9 COURSE VERTICALE REQUISE EN PIEDS M TRES VT LONGUEUR DES COURSES HORIZONTALES PLUS LES D VIATIONS EN PIEDS M TRES HT Lorsque la con guration de l vacuation exige plus d...

Страница 84: ...16 7PI 5 1m 24 75 PI 7 5m Puisque les deux formules sont respect es cette configuration d vacuation est acceptable La section ombrag e l int rieur des lignes repr sente des valeurs acceptables pour HT...

Страница 85: ...TRES HT La section ombrag e l int rieur des lignes repr sente des valeurs acceptables pour HT et VT HT VT Lorsque la configuration de l vacuation exige plus qu un coude de 90 les formules suivantes s...

Страница 86: ...ion de l vacuation exige plus qu un coude de 90 les formules suivantes s appliquent Formule 1 HT 3 5VT Formule 2 HT VT 24 75 pieds 7 5m Exemple V1 4 PI 1 2m V2 1 5 PI 0 5m VT V1 V2 4PI 1 2m 1 5PI 0 5m...

Страница 87: ...s s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 5 PI 1 5m V2 6 PI 1 8m V3 10 PI 3 1m VT V1 V2 V3 5PI 1 5m 6PI 1 8m 10PI 3 1m 21PI 6 4m H1 8 PI 2 4m H2 2 5 PI 0 8m HR H1 H2 8PI...

Страница 88: ...16 1 PI 4 9m HT VT 16 1PI 4 9m 4 5PI 1 4m 20 6 PI 6 3m Formule 1 HT 3VT 3VT 3 PI 0 9m x 4 5 PI 1 4m 13 5 PI 4 1m 16 1PI 4 9m 13 5 PI 4 1m Puisque cette formule n est pas respect e cette configuration...

Страница 89: ...les 4 vis Installez les ensemble de b ches vitre de la porte et la barri re de protection H Installez l assemblage du collet d vacuation avec le joint d tanch it sur le panneau arri re autour du colle...

Страница 90: ...anch it dans le haut de l appareil et xez avec les 4 vis K R installer la couvercle d ext rieur sans knockout sur la collet d vacuation 7 178mm et xez L De l int rieur de la chambre de combustion inst...

Страница 91: ...ceinte de l appareil doit respecter la hauteur minimale requise Mesurez partir de la base de l appareil Si des ensembles de montants en acier avec panneau de ciment sont fournis ou sp ci dans les inst...

Страница 92: ...nt et de 3 76mm au dessus doit tre maintenu sur toutes les courses horizontales Utilisez l espaceur coupe feu W010 1777 fourni NOTE Les d gagements minimaux entre le haut de l vent et les mat riaux co...

Страница 93: ...oir une hauteur minimale de 50 1 2 1283mm A n de respecter les contraintes de temp rature l espace l int rieur de l enceinte autour de l appareil et au dessus doit demeurer sans obstruction NOTE L cra...

Страница 94: ...de l appareil et au dessus doit demeurer sans obstruction Pour la terminaison d vacuation arri re ne d passement pas 10 254mm de sections d vacuation horizontales NON COMBUSTIBLE 0 0MM IF NON COMBUSTI...

Страница 95: ...il et au dessus doit demeurer sans obstruction D GAGEMENTS MAXIMAUX D VACUATION L ARRI RE EXEMPLE 1 COMBUSTIBLE NON COMBUSTIBLE 1 25mm 3 76mm BRICK 0 0MM IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK...

Страница 96: ...il et au dessus doit demeurer sans obstruction D GAGEMENTS MAXIMAUX D VACUATION L ARRI RE EXEMPLE 2 241 8 61 3cm MINIMUM PLUSRISE COMBUSTIBLE NON COMBUSTIBLE 1 25mm 3 76mm BRICK 0 0MM IF NON COMBUSTIB...

Страница 97: ...er votre appareil d terminez les exigences de ventilation avant de d cider de l emplacement nale de l appareil Apr s un encadrement brut placez l appareil dans sa position nale Pour les mat riaux de n...

Страница 98: ...Ne serrez pas la gaine exible Risque d incendie d explosion ou d asphyxie Si l ensemble du syst me de conduit d vent n est pas ad quatement soutenu il risque de chir ou de se s parer Utilisez des sup...

Страница 99: ...coupe feu contre la trou et xez l aide des quatre vis fournies dans le sac de votre manuel B Une fois que le conduit d vent est en place appliquez du scellant Mill Pac rouge W573 0002 non fourni entre...

Страница 100: ...cone rouge W573 0002 non fourni entre le conduit d vacuation et l espaceur coupe feu Calfeutrage Protecteur du conduit d vacuation Protecteur du conduit d vacuation Collet de conduit d vacuation Espac...

Страница 101: ...ext rieur et rendez la tanche en la scellant avec du calfeutrage non fourni D Si plus de sections de gaine doivent tre utilis es pour atteindre l appareil raccordez les ensemble tel qu illustr Le sys...

Страница 102: ...sus le connecteur de terminaison en laissant un minimum de 3 4 19 1mm de connecteur de terminaison visible au dessus du haut du solin Glissez le solin sous les c t s et le bord sup rieur des bardeaux...

Страница 103: ...ni et tout chevauchement de 2 50 8mm entre les composants d vacuation B Appliquez un g n reux joint de scellant haute temp rature Mill Pac W573 0007 non fourni sur le rebord ext rieur du collet int r...

Страница 104: ...sur le dessus et les c t s du connecteur de terminaison Placez le solin par dessus le connecteur de terminaison et glissez le sous les c t s et le bord sup rieur des bardeaux Assurez vous que le conne...

Страница 105: ...doit tre raccord au conduit exible de prise d air et le collet d vacuation de la terminaison au conduit exible d vacuation Les adaptateurs colin aire coaxial Simpson Duravent et Selkirk sont approuv s...

Страница 106: ...Steel approuv Ce kit n est pas recommand pour les longueurs de conduit d vacuation vertical court Selon le mod le et ann e de votre appareil les trous de xation peut ne pas exister A Si les trous de x...

Страница 107: ...N ADAPTATEUR POUR VENT B MISE LA TERRE ALIMENTATION CC ANNEAU DE MISE LA TERRE PANNEAU IPI Cet appareil est quip avec un bo tier de piles Si le bo tier de piles est utilis installez quatre piles AA no...

Страница 108: ...r que le manchon de protection couvre les connexions comme illustr e ci dessous F Installez deux piles D garantir que les extr mit s positive et n gative correspondent ceux identi s sur le sauvegarde...

Страница 109: ...l entr e lectrique voir la section dimensions Lorsque le branchement est termin tous les raccords de gaz doivent se trouver l int rieur de l appareil foyer de gaz seulement Les pressions lev es endomm...

Страница 110: ...ne fonctionne pas suivre les instructions de couper l alimentation de gaz et puis appelez votre technicien de service ou fournisseur de gaz A R gler le thermostat la r glage le plus bas si quip B Tou...

Страница 111: ...oir d ignition Gardez le bouton de contr le du gaz enfonc pendant une minute puis rel chez le Si la veilleuse ne reste pas allum e r p tez les tapes E I J Lorsque la veilleuse est allum e enfoncez et...

Страница 112: ...08 19 112 FR encadrement ni 9 0 encadrement ni 301 2 775mm 35 889mm 113 16 46mm 61 2 192mm 141 2 368mm GAS INLET LOCATION ELECTRICAL CONNECTION ENCLOSURE TOP FINISHING MATERIAL 9 1 dimensions d encad...

Страница 113: ...e la circulation de l air dans les ouvertures d air et les persiennes ni au fonctionnement des persiennes ou des portes ni l acc s pour l entretien Respectez tous les d gagements aux mat riaux combust...

Страница 114: ...doivent tre enl v s B Retirer les vis de xation de la partie sup rieure de l appareil comme illustr C Installez l avant hotte assurer qu elle est inclin e vers le bas lorsqu il est install D Reinstall...

Страница 115: ...mm pour chaque pouce 24 5mm suppl mentaire de projection Si vous utilisez un moulure optionelle les m me r gles s applique commen ant du sommet du moulure Garantir que les d gagements sont maintenus p...

Страница 116: ...re tabeltte assurez vous qu ils soient r sistants la chaleur a n de pr venir la d coloration Le d gagement d une tablette combustible l appareil peut varier selon la profondeur de la tablette Utilisez...

Страница 117: ...e la tablette combustible pour plus d informations des d gagements de la tablette L installation des lectroniques ou d autres mat riaux qui peuvent tre sensibles la chaleur sur un mur en retrait perme...

Страница 118: ...coche du b che gauche A Placez la b che arri re W135 0575 fermement sur les deux goujons l arri re du support Assurez vous que la b che repose plat et ne couvre pas l ouverture du veilleuse Placez les...

Страница 119: ...che crois droite W135 0579 sur les deux tiges restantes B A C D E F Installez la porte et l cran de protection 10 7 mise en place du logo Retirez le papier dorsal du logo et placez le sur comme illus...

Страница 120: ...e tourner fermement les vis vers la droite pour sceller Ne serrez pas trop fort V ri ez pour des fuites en appliquant une solution d eau savonneuse Avant d effectuer le r glage de la veilleuse assurez...

Страница 121: ...es du br leur La amme peut ne pas tre jaune imm diatement allouez de 15 30 minutes pour que la couleur nale de la amme se stabilise LE R GLAGE DU VOLET D AIR DOIT TRE EX CUT PAR UN TECHICIEN OU INSTAL...

Страница 122: ...e br leur 5 Si votre appareil est fourni avec une cran de protection le nettoyage peut tre n cessaire en raison d un exc s de poussi re peluches des tapis animaux etc utilisez un l attachement du bros...

Страница 123: ...n tanche Si la vitre de la porte est ssur remplacer Seulement utiliser le verre fourni par votre d taillant autoris V ri ez si la soupape de gaz de la veilleuse et les boutons Hi Lo bougent librement...

Страница 124: ...ut rayer la surface du verre r duisant ainsi sa puissance Ne pas faire fonctionner l appareil avec la verre bris les fuites de gaz de combustion peut r sulter Contactez votre d taillant local autoris...

Страница 125: ...cement de pi ce sous garantie une photocopie de la facture originale sera requise a n de pouvoir honorer la demande Lorsque vous commandez des pi ces donnez toujours l information suivante Mod le et n...

Страница 126: ...oupape Ces articles peut diff rer de celle illustr L ASSEMBLAGE DE L CRAN DE PROTECTION R f No de pi ce Description En stock R f No de pi ce Description En stock Oui Oui Oui Oui Oui Oui Oui Oui Oui Ou...

Страница 127: ...W010 2763 36 W010 2808 W750 0270 W455 0068 W720 0062 W240 0013 W290 0029 Oui Oui Oui Oui Oui Oui Oui Injecteur de veilleuse 35 P Tube de veilleuse raccord Thermosenseur Joint d tanch it du veilleuse...

Страница 128: ...mocouple Oui Oui Oui Oui Oui Oui Oui Bouton d allumeur Soupape P Soupape NG Veilleuse GN Thermopile Veilleuse P Ensemble de fils Ensemble du veilleuse GN Ensemble du veilleuse P 32 34 W240 0006 W290 0...

Страница 129: ...02 Ces articles peut diff rer de celle illustr L CRAN DE PROTECTION L CRAN DE PROTECTION R f No de pi ce Description En stock R f No de pi ce Description En stock Oui Oui Oui Oui Oui cran de protectio...

Страница 130: ...liquant une solution d eau savonneuse Le volet d air est r gl incorrectement Voir la section r glage du venturi pour le r glage de l ouverture du volet d air dans le manual d installation Du carbone s...

Страница 131: ...mentation de la veilleuse Le module n est pas mis la terre Assurez le bon polarit du thermocouple si fourni V ri ez si les assemblages de le veilleuse et de la soupape sont bien mis la terre R cepteur...

Страница 132: ...le bouton on de la t l commande Environ 4 secondes apr s que le bouton on off ait t enfonc le tableau d allumage commencera produire des tincelles Au premier essai le tableau d allumage formera des ti...

Страница 133: ...DROITE POUR SCELLER NE SERREZ PAS TROP FORT V ri ez pour des fuites en appliquant une solution d eau savonneuse Le volet d air est mal r gl Voir la section r glage du venturi pour le r glage de l ouve...

Страница 134: ...mocouple et la connexion la borne de la soupape Remplacez le thermocouple Remplacez la soupape La soupape est d fecteuse Remplacez la soupape La veilleuse br le pas de gaz au br leur principal le bout...

Страница 135: ...riodes d humidit la condensation des produits chimiques ou produits d entretien nuisibles ne seront pas la responsabilit de Napol on Durant les dix premi res ann es Napol on remplacera ou r parera le...

Страница 136: ...U US S D DE E 4 40 0 A AN NS S D D E EXISTENCE C C C C C CO O O O O ON N N N N N N NS S S S S SA A A A A AC C CR R R R R S S L L LA A C CO ON NC CE EP PT TI IO ON N D DE PR RODUITS DE CONFORT 7200 Rou...

Отзывы: