WIRING THE TAMPER SWITCHES
(REQUIRED FOR UL COMMERCIAL BURGLARY)
Before installation and wiring, the tamper switches (part
GEM-
Tamperkit
) are normally open devices; when placed into
the circuit and into operation, they are normally closed devic-
es.
Tamper switches protect against the opening of the radio cabi-
net door or the removal of the radio enclosure from the wall or
other mounting surface.
There are two places in the cabinet to mount tamper switches:
(1) To prevent cabinet removal from the wall, located on the
left side of the cabinet there is one knockout for the switch
plunger and three mounting holes (in the enclosure sheet met-
al). (2) To protect the cabinet door, mount a tamper switch in
the three mounting holes (in the enclosure sheet metal).
When mounted, the switch button contacts the inside surface
of the door.
Note:
Be sure to alert the user that opening the
enclosure door will cause a tamper alarm.
Wiring a normally closed sensor loop for tamper supervision,
wire to a zone on the control panel.
GEM-Tamperkit
consists of
Description
QTY
SC206LF
Slotted Pan Head 6-32 x 3/4
Machine Screw
6
SW105
Tamper Switch
2
Tamper Switch Mounting Instructions
Back T
a
m
p
er
D
o
or
Tam
p
er
VIEW OF TAMPER SWITCHES:
(1) = ENCLOSURE BASE;
(2-BACK) = TAMPER SWITCH TO PREVENT REMOVAL FROM WALL;
(3-DOOR) = TAMPER SWITCH TO PROTECT THE ENCLOSURE
DOOR
1
3
2
NYCFD Conditions of Acceptability
1. Only radios Listed for UL 864 Commercial Fire are NYCFD approved.
2. All installations must be dual path (DACT and Radio) and DACT shall be primary.
3. Each path must be supervised not exceeding 24 hours.
4. Failure of either path shall be annunciated at the protected premises.
5. Failure of either path shall cause a trouble to be sent to the central station within 5 minutes on the other
communications path.
6. When a remote antenna is used, the antenna transmission line shall be installed in rigid metal, intermediate metal,
or electrical metallic tubing in accordance with NFPA70, NEC.
7. Interconnections between elements of transmitting equipment, including any antennas, shall be supervised either to
cause an indication of failure at the protected premises or to transmit a trouble signal to the supervising station.
8. All UL requirements must be complied with.