 SLE Commercial LTEVI & LTEAI Series Dual-Path Alarm Communicators -- Installation Instructions 

Wiring Diagram for Generic FACPs 

with TELCO RJ Sockets 

 

F A C P     P C   B O A R D  

(CONTROL PANEL HOUSING) 

Refer to section "

SUPPLYING POWER

". 

TELCO RJ SOCKET (SECONDARY) 

(STARLINK RADIO HOUSING) 

StarLink Radio Terminals

 

PC Board:  All connections are power limited except AC Mains and battery terminals.   

LOCAL 

DOWNLOAD  

TELCO  

SECONDARY 

TELCO  

PRIMARY 

ETHERNET 

(+) 

(

POWER  PGM3 

IN1 

IN2 

IN3 

(

(+) 

(+) 

(

(

(+) 

(+) 

10 

(

12 

(

11 

(

+

13 

EGND 

19 

N/O 

21 

N/C 

20 

IN4 

IN5 

OUT1 

22

 

N

/C

 

24

 

N

/O

 

23

 

C

 

O

U

T2

 

Power Supply (SLE-ULPS-R)  

Optional; if not used, connect 10K 

resistor between terminals 9 and 

10 (IN4) 

StarLink 

BATTERY 

(+) 

 RED 

(–) 

BLACK 

8

 

9

 

10

 

N/C

 

CO

M

 N/O

 

J2 

Note:  Battery 

leads are not 

power limited 

10kΩ

 

10kΩ

 

10kΩ

 

TELCO RJ SOCKET (PRIMARY) 

EOLR 

(

J2

 jumper off) 

(This connection only used with 

Power Supply SLE-ULPS-R) 

The feature "

Tip/Ring 

Wiring Fault Report

"  is 

required for supervision. 

Requires all 8 wires in 

the RJ-45 cable 

JP1

 

Shunt 

JP1

 on 

bottom 2 pins 

when using the 

SLE-ULPS-R 

Shunt on top 2 

pins when NOT 

using the 

SLE-

ULPS-R

 

(These connections 

only used without 

Power Supply) 

EOLR 

JP

Remove shunt 

on 

JP2

 to enable 

TELCO 2 trouble 

*

Not required if 

JP2

 shunt is removed and FACP monitors TELCO 2. 

To FACP Zone 

Dedicated to Radio 

Trouble

*

 

When using 

JP2 

option (monitoring Telco 2) with power supply 

wire:  

1.  Move Power Supply 

IN1 

from Radio 

OUT1 

terminal 21 to 

power supply terminal 4 (-). 

2.  Do not wire power supply trouble relay to FACP zone. 
3.  Wire power supply terminals 9 and 10 in series with the 10K 

EOLR to Radio 

IN4 

(+).    

4.  Program 

IN4 

to report power supply trouble. 

Optional:

  When Power Supply 

SLE-ULPS-R is not used, connect 
FACP AUX/Remote Fire Power or 

Listed power supply (+12V or 

+24V) to StarLink terminals 1 and 

2 (observing polarity) 

(

+

)  (

+12V or +24V 

AUX/Remote Fire 

PWR 

       

 

 

Either the 

TRF12/T123 

(16.5V / 20VA) 

transformer 

or the 

chassis-mounted 

16.5VAC / 20VA 

transformer 

J7

 

J7

: Remove shunt to disable 

10K EOLR across pins 1 and 8 of 
primary TELCO input.  Do not 
remove if "

Tip/Ring Wiring Fault 

Report

"  is enabled. 

Содержание SLE-LTEAI-CFB

Страница 1: ...icators are fully su pervised wireless digital two way subscriber units All models are compatible with most 12 24VDC alarm control panels always adhere to the documentation provided by the control panel manufacturer These communicators are for use as the primary means of communication with the central station and do not have backup mode capability No POTS Telco Line connection permitted Dual Path ...

Страница 2: ...igh input for wiring to the control panel bell output When this input detects a pulsing temporal 3 high it sends a Fire alarm a pulsing temporal 4 CO Alarm a CO alarm is sent When used these conductors must be run in conduit max 20 feet for Commercial Fire and 3 feet for Residential Fire For this input to re port to a central station the StarLink communicator must be configured with the central st...

Страница 3: ...T2 Common Dry contact Form C relay Relay rated 30V AC DC 500mA TB24 N C OUT2 Normally closed Dry contact Form C relay LED DESCRIPTIONS The PC board contains several LED s as follows GREEN RF SIGNAL STRENGTH LED Labeled D3 this LED is located at the lower right corner of the PC board Every 30 seconds the StarLink communicator receiver section turns on and listens to the cell tower Depending on the ...

Страница 4: ...ces for 24 hours unless an engine driven genera tor is provided on the premises then only 4 hours of UPS backup are required JUMPER DESCRIPTIONS Jumper block labeled X5 from top to bottom as detailed in the table below Note Contact ID is always available in response to a Contact ID handshake The SLE Series Dual Path communicators are compatible with 4 2 Pulse Dialing formats with 10pps 20pps and 4...

Страница 5: ...unt and register specific StarLink com municator modules at www NapcoComNet com Accounts and modules registered via the Internet are enabled for activation within 24 hours STEP 2 SELECT A MOUNTING LOCATION The mounting location should be indoors within the protect ed area and selected based on RF performance It is HIGHLY recommended that the installer carefully adhere to the following recommendati...

Страница 6: ...vate the trouble with an open by wiring the EOLR in series with the Common and N C of the OUT1 relay Activate the trouble with a short by wiring the EOLR in parallel with the Common and N O of the OUT1 relay The communicator must also report this trouble to the central station With NAPCO GEMC control panels wire SIGNALS ORIGINATED AT THE NOC NOC Originated Alarms Contact ID Event Data Sent Initiat...

Страница 7: ...and N O in series with a 2 2k EOLR For communicator models without the SLE ULPS R Pow er Supply powered by the control panel Aux Power termi nals wire the communicator directly to the 12V of the control panel Program the communicator to report all troubles on OUT1 Common and N C You can also wire across the dedicated zone on a GEMC EZM8 Thus when a communicator trouble is detected the communicator...

Страница 8: ...es with which the compatibility has been determined by UL Listing Report 5 Only enclosures painted red in color shall be used 6 Underwriters Laboratories Inc s listing requirements and limitations shall be complied with to the transmitted message e The maximum duration between the initiation of an alarm signal at the protected premises transmission of the signal and subsequent display and recordin...

Страница 9: ...e transformer compartment from the yellow secondary wires of the transformer Remove shunt J2 to isolate relay OUT1 common from ground i e jumper on wet circuit common off dry contact When wet configuration is used the power should be derived from the alarm control panel J7 Remove shunt to disable 10K EOLR across pins 1 and 8 of primary TELCO input Do not remove if Tip Ring Wiring Fault Report is e...

Страница 10: ...vision Requires all 8 wires in the RJ 45 cable JP1 Shunt JP1 on bottom 2 pins when using the SLE ULPS R Shunt on top 2 pins when NOT using the SLE ULPS R These connections only used without Power Supply EOLR JP2 Remove shunt on JP2 to enable TELCO 2 trouble Not required if JP2 shunt is removed and FACP monitors TELCO 2 To FACP Zone Dedicated to Radio Trouble When using JP2 option monitoring Telco ...

Страница 11: ... when not using the SLE ULPS R RJ31X RING TIP GREEN RED GREEN RED WIRE DIRECTLY TO CONTROL PANEL USE FOR SHORTER DISTANCES OPTIONAL WIRE TO RJ31X USE FOR LONGER DISTANCES RJ31X RING TIP GREEN RED WIRE DIRECTLY TO CONTROL PANEL USE FOR SHORTER DISTANCES OPTIONAL WIRE TO RJ31X USE FOR LONGER DISTANCES GREEN The feature Tip Ring Wiring Fault Report is required for supervision RED JP2 Remove shunt on ...

Страница 12: ...removed and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifying Telco line cut this is the DACT interconnect wiring to the radio PC Board All connections are power limited except AC Mains and battery terminals Or use a 12V 24V UL Listed monitored power supply 10kΩ 10kΩ 10kΩ EOLR Requires all 8 wires in the RJ 45 cable JP1 Shunt JP1 on top ...

Страница 13: ...or supervision and central station reporting through the StarLink SLE LTEVI FIRE radio By removing the JP2 shunt and enabling the feature Tip Ring Wiring Fault Report when any radio trouble is detected the StarLink radio will remove voltage from the secondary telephone output triggering the FACP to locally annunciate the Telco trouble and report the trouble to the central station Note Some FACPs r...

Страница 14: ...r that opening the enclosure door will cause a tamper alarm Wiring a normally closed sensor loop for tamper supervision wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC206LF Slotted Pan Head 6 32 x 3 4 Machine Screw 6 SW105 Tamper Switch 2 Tamper Switch Mounting Instructions Back Tamper Door Tamper VIEW OF TAMPER SWITCHES 1 ENCLOSURE BASE 2 BACK TAMPER SWITCH TO PRE...

Страница 15: ... TRF12 T123 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM LENGTH Maintain a minimum of 1 4 inch separation of circuits transformer secondary wiring from 120V branch circuit EXAMPLE OF CONDUIT LOCATION Optional Alternate Methods for Commercial Fire Branch Ci...

Страница 16: ...may not be compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all cases provide adequate warning or protection A properly installed and maintained alarm may only reduce risk of burglary robbery fire or otherwise but it is not insurance or a guarantee that these even...

Отзывы: