background image

 
 
 

 

 
 

 
 

 
 

 
 

 
 
 

 
 

 
 
 
 
DESCRIPTION 

This variable-purpose power supply is suitable for many differ-
ent applications for security, access control and CCTV system 
accessories that need supplementary power.  The NP-P10A 
power supply/charger converts low voltage AC input into 12VDC 
or 24VDC @ 10 Amps of continuous supply current (see fea-
tures).   

 

FEATURES 

Maximum charge current 700mA. 

Automatic switch over to stand-by battery.   

Thermal overload and short circuit protection. 

Battery is fuse protected. 

AC input and DC output LED indicators. 

Includes battery leads. 

Dip switch selectable 12VDC-24VDC output. 

10 Amps continuous supply current at 12VDC-24VDC*. 

Filtered and electronically regulated output. 

Built-in charger for sealed lead acid or gel type batteries. 
Board dimensions: 179.32mm (L) x 108.71mm (W) x 60mm (H) 

Specified at 25° C ambient. 

 

INSTALLATION INSTRUCTIONS 

    The NP-P10A should be installed in accordance with The National 

Electrical Code and all applicable Local Regulations. 

1. Mount the NP-P10A in desired location/enclosure. 
2. 

Connect proper transformer to terminals marked [AC].  (See 
Voltage Output/Transformer Selection Table).  Use 18 AWG or 
larger for all power connections (Battery, DC output). 

    Keep  power  limited  wiring  separate from non-power limited 

wiring (115VAC / 60Hz Input, Battery Wires).  Minimum .25" 
spacing must be provided. 

3. Set the NP-P10A to the desired DC output voltage by setting the 

switches to the appropriate positions (see 

Voltage Output/

Transformer Selection Table

). 

4. Connect devices to be powered to terminals marked [+ DC -]. 

    Note: 

It is important to measure output voltage before connecting 

devices to help avoid potential damage. 

5. 

When the uses of stand-by batteries are desired, they must be 
lead acid or gel type.  Connect battery to terminals marked [+ 
BAT -] on the unit (battery leads included).  Use two (2) 12VDC 
batteries connected in series for 24VDC operation. 

    Note: 

When batteries are not used a loss of AC will result in the 

loss of output voltage. 

R

333 Bayview Avenue 

Amityville, New York 11701 

For Sales and Repairs, (800) 645-9445 

For Technical Service, (800) 645-9440 

NP-P10A 

10 AMP POWER SUPPLY / CHARGER 

WI1328C  12/05 

© NAPCO 2005 

Red  

(DC) 

Green 

(AC) 

Power Supply Status 

ON 

ON 

Normal operating condition. 

ON 

OFF  Loss of AC, Stand-by battery supplying power. 

OFF 

ON 

No DC output.  Short circuit or thermal overload condition. 

OFF 

OFF  No DC output.  Loss of AC.  Discharged or no battery. 

LED DIAGNOSTICS

 

Terminal 

Legend 

Function/Description 

AC 

Low voltage AC input (see Voltage Output/Transformer Selection Table). 

For 12VDC output use 28VAC with 175 VA power rating or higher. 
For 24VDC output use 28VAC with 300VA power rating or higher. 

Caution: Do not apply voltages above 28VAC (28VAC is maximum input rating). 

+ BAT -- 

Stand-by battery connections. 

+ DC -- 

DC output voltage for devices to be powered. 

TERMINAL IDENTIFICATION 

Item 

Description 

Dimension  Volume 

Memo 

Instruction Sheet 

A4 

 

Wire 

18AWG 22cm 

RED 

Wire 

18AWG 22cm 

BLACK 

Double Stick Foam Tape 

60*20*7mm 

 

APPENDIX LIST

 

VOLTAGE OUTPUT/TRANSFORMER SELECTION TABLE 

Voltage 

Dip Switch  

Position 

Transformer /  

Output Rating 

12VDC @ 10 
Amps continuous 
supply current 

1.  ON 

2.  OFF 

P-TRF28175 

24VDC @ 6 Amps 
continuous supply 
current 

1.  ON 
2.  ON 

P-TRF28175 

24VDC @ 10 
Amps continuous 
supply current 

1.  ON 
2.  ON 

P-TRF28300 

AC 

   

Отзывы: