NAPCO GEMC-WL-SMK Скачать руководство пользователя страница 2

NOTE:

  Smoke detectors are not to be used with 

detector guards unless the combination has been 
evaluated and found suitable for that purpose. 

Pick smoke-detector location.  

Referring to the 

NFPA standard on page 3, select a suitable loca-

tion to mount the GEMC-WL-SMK.  

Note:

  

Mount-

ing the GEMC-WL-SMK on foil-backed wallpaper is NOT 

recommended because the radio range will be reduced. 

Install mounting plate.  

Use the two screws 

and anchors provided to attach the mounting 

plate to the wall or ceiling.  

NOTE:  

Do not install 

on removable surfaces such as ceiling tiles.

 

Map the GEMC-WL-SMK Transmitter.  

Referring 

to the instructions for the panel and keypad in use, 
enter the following: 

 

the zone to which the transmitter will be mapped; 

the 6-digit RF identification number/1-digit check-
sum number printed on the transmitter (include all 
numbers and/or letters and leading zeros, if any); 
and 

the transmitter point number ("1").

 

 

NOTE:

  In fire alarm installations, the control panel 

must be programmed to activate the fire alarm bells or 
horns upon detection of a fire.

 

Low Battery Chirp Silence 

Allows temporary disabling of the Low Battery Chirp ("sleep") 
for 12 hours.  Press TEST button during low battery condition 
to enter Mode. 
 

Smoke Alarm 

Sounder and red LED both turn on continuously. 
 

Silencing the Unit 
To silence the unit

 during a smoke alarm, press and hold 

the TEST button for 10 seconds to temporarily silence the unit 
for 5 minutes. 
 

Maintenance Warning 

The smoke detector will warn that it must be cleaned when 
the unit flashes the red LED every 5 seconds and the unit 
does not pass the weekly test by the user (see #8 at left).  To 
clean the smoke detector, vacuum the outside of the unit at 
least once a year (preferably every six months) using a soft 
brush attachment.  

Do not attempt to clean the unit in any 

other way.  

If this maintenance procedure fails to clean the 

unit sufficiently, call for service and/or replace the unit. 

Test system weekly with unit mounted.  

If the 

system is monitored, notify central station of im-
pending test.  Press and hold TEST button (using a 

non-conductive pointed object such as a toothpick) for 5 
seconds after the local alarm sounds.  The sounder will 
turn on while the button is pressed; if the unit is operating 
within its proper sensitivity limits and is not in a low battery 
condition, the green LED turns off and the red LED turns 
on continuously.  Verify that the GEMC-WL-SMK triggers 
the correct zone on the control panel and that the correct 
report is sent to the central station. 

HOLD BUTTON FOR AT LEAST 5 SEC-
ONDS AFTER LOCAL ALARM SOUNDS 
TO SEND AN ALARM TRANSMISSION 

Attach the GEMC-WL-SMK to mounting 
plate.  

Match up alignment tabs on detector 

and plate.  Turn detector clockwise until it locks 

into place.

 

TWIST  

DETECTOR 

CLOCKWISE 

TO LOCK TO 

MOUNTING 

PLATE 

 

 

 

 

 

 

DINING 

ROOM 

KITCHEN 

SMOKE 

DETECTOR 

BEDROOM 

BEDROOM 

LIVING 

ROOM 

BEDROOM 

 

 

 

 

 

 

SCREW  

ANCHORS FOR 

WALLBOARD 

 

MATCH UP 

ALIGNMENT 

TABS 

PRESS AND HOLD TEST BUTTON BY 

INSERTING NON-CONDUCTIVE 

POINTED OBJECT 