background image

 

www.nano-sense.com 

All Rights Reserved 

Tel : 33 (0)1 41 41 00 02 

page 3 

 

 

1.  Security 

 

WARNING

 

Danger of death, risk of electric shock and fire! 
The installation should only be undertaken by a qualified electrician! 
 
To apply for correct  bus  and power cables  and to  activate the device, comply  with  the state of the art 
and standards. 
 
Any intervention or modification to the device will invalidate any warranty claim. 
 
• Do not use this probe in environments with regular exposure to silicon vapors (HMDS) because this 
gradually alters the sensitivity of the VOC sensor.  
• Do not use the sensors for measuring gas content relating to safety! 
• Use the probe only with secured low voltages! 
 

2.  Positioning 

The  position  of  the  probe  is  crucial  vis-à-vis  efficiency  and  energy  savings  for 
ventilation, heating and cooling. 
 
•  The  probe  is  designed  to  ensure  air  quality;  it  must  be  placed  in  the  area  of 
occupancy  of  the  premise  served  by  outlet  vents,  on  a  wall  at  eyes  level 
(breathing human level, between 1.5 and 1.8m). 
 
• Avoid drafts (near openings, blowing air, doors, outlet vents) and dead zones 
(niche, shelves and curtains). 
 
• Avoid orthogonal walls (corners of room in particular) 
 
•  Avoid  heat  sources  and  the  proximity  of  occupants  (radius  of  1  m  from 
workstation). 
 
• Avoid direct exposure to sunlight. Consider all seasons sun positions  
 
• Position the probe vertically on a wall or partition. 
This device is not intended for installation in duct or ceilings. 
 
 
 
 
 
 
 

Any work not in accordance with this documentation or 

changes to the device will invalidate all warranty claims.

 

Содержание EP5000-Z

Страница 1: ... Billancourt France Tél 33 0 1 41 41 00 02 www nano sense com www nano sense com All Rights Reserved Tel 33 0 1 41 41 00 02 page 1 EP5000 Z air quality probe Installation manual Ver Date Modification Update V1 16 12 2019 Initial Version ...

Страница 2: ...ved Tel 33 0 1 41 41 00 02 page 2 Summary 1 Security 3 2 Positioning 3 3 Flush mounting 4 4 Wiring 4 5 Installation 4 6 Power on 4 7 Indication of LEDs in normal operation 5 8 Connections 6 8 1 Power supply 6 8 2 Remote control 6 9 NFC 6 ...

Страница 3: ...ltages 2 Positioning The position of the probe is crucial vis à vis efficiency and energy savings for ventilation heating and cooling The probe is designed to ensure air quality it must be placed in the area of occupancy of the premise served by outlet vents on a wall at eyes level breathing human level between 1 5 and 1 8m Avoid drafts near openings blowing air doors outlet vents and dead zones n...

Страница 4: ...membrane from which the duct passes through If the case crosses through the sealing plane plasterboard seal between the casing and panel with a special sealant without silicone and VOC 5 Installation It is recommended to install the probe at the end of the work after painting and using silicone based products Connect the 24V power cable to the back of the probe Just push the stripped ends flexible...

Страница 5: ...f IAQ physiological impacts on health cognitivity and quality of sleep which depend on the combined effects cocktail effect of CO2 VOCs particles noise and light The building health is also synthesized and takes into account risk of condensation deposit of particles on cold parts This synthesis is materialized by a continuous gradual rising and then descending gradation of the breathing type Senso...

Страница 6: ...ctions 8 1 Power supply The power supply must be continuous DC and between 12 and 32V 24V nominal 8 2 Remote control The probe can receive instructions from the smartphone application It is thus possible to deviate from certain instructions and to recover certain information status physiological impact concentrations current mode etc See user manual for more details 9 NFC Used for commissioning Se...

Отзывы: