13
cycling refrigerated air dryer
R
1
2.4 installation
Note: These instructions help to improve the service durability of the equipment. Please read them carefully
and follow them.
Location of the compressed air dryer
1. Locate the air dryer on a surface in a horizontal position.
2. The air dryer can corrode quickly if it is located on a surface that is contaminated by acid or alkali.
3. The location of installation should be clear and have sufficient space. (Blocked air circulation reduces the
rate of dehumidification and the service life of the dryer).
Allow 5 feet of clear space around the dryer to facilitate maintenance operations and repairs.
4. The ambient temperature where the air dryer is installed should be greater than 32°F to avoid the dryer
freezing. The location should not have direct exposure to sun rays.
Ambient temperature for dryers using R-134a (34-122°F); using R-407c (34-110°F).
It is necessary to arrange for suitable ventilation in order to prevent any malfunctioning.
If ambient temperature can fall to 32°F or below, contact your supplier to obtain specific
installation or air dryer recommendations.
5. There should be no flammable products at the place of installation.
Содержание NXC 0020
Страница 1: ...NXC series cycling refrigerated air dryer user guide...
Страница 47: ...47 cycling refrigerated air dryer R1 3 3 electrical wirings NXC 0020 115V 1 60 NXC 0030 to NXC 0045 115V 1 60Hz...
Страница 48: ...48 cycling refrigerated air dryer R1 NXC 0065 to NXC 0110 115V 1 60 NXC 0130 to NXC 0165 115V 1 60Hz...
Страница 49: ...49 cycling refrigerated air dryer R1 NXC 0200 to NXC 0400 230V 1 60 NXC 0200 to NXC 0400 460V 3 60Hz...
Страница 50: ...50 cycling refrigerated air dryer R1 NXC 0500 to NXC 0850 460V 3 60Hz NXC 1050 to NXC 2000 460V 3 60Hz...
Страница 61: ...notes...
Страница 62: ...notes...