HRQ-ERGO-SENS-CO2-W

 

 

 
 

 

Function Introduction 

Main function of HRQ-ERGO-SENS-CO2-W sensor is room CO2 concentration 
detection. HRU-CONT-TPAD is needed for operation.  

 

Technical specification 

Sensor technology: NDIR infrared CO2 detection 

Measurement range 400-2000ppm CO2 

Maximum drift: ±2% 

Resolution: 10ppm 

Temperature influence: 

0.5% FS per  ° C

 

Response time (T90): 

120S 

Accuracy: 75ppm 

Repeatability: 

2% 

Sample mode: diffussion 

Power supply: DC5V±5% 

Operating current : average 70mA, peak value 120mA 

PWM linear output 

UART: data bits 8; stop bit 1; check bit: No 

Standard baud rate: 9600bps 

Operating temperature: -10 to 50° C

 

Operating humidity: 0-95% 

 

 