NAiS LT4H-L Скачать руководство пользователя страница 2

onlinecomponents.com

2

LT4H-L

Specifications

Type

Ralay output type

Transistor output type

Item

AC type, AC/DC type

DC type

AC type, AC/DC type

DC type

Rating

Rated operating voltage

Rated frequency

Rated power consumption

Rated control capacity

Time range

Time counting direction

Operation mode

Start/Reset input

100 to 240 V AC, 24 V AC/DC

50/60 Hz common

Max. 10 V A

5 A, 250 V AC (resistive load)

9.999 s, 99.99 s, 999.9 s, 9999 s, 99 min 59 s, 999.9 min, 99 h 59 min, 999.9 h (selected by DIP switch)

Addition (UP)/Subtraction (DOWN)

(2 directions selectable by DIP switch)

A (Power ON delay 1), A2 (Power ON delay 2), B (Signal ON delay), C (Signal OFF delay), D (Pulse one-shot),

E (Pulse ON delay), F (Signal Flicker), G (Totalizing ON delay) (selectable by DIP switch)

Min. input signal width: 1 ms, 20 ms (2 directions by selected by DIP switch)

12 to 24 V DC

Max. 3 W

100 to 240 V AC, 24 V AC/DC

50/60 Hz common

Max. 10 V A

100 mA, 30 V DC

12 to 24 V DC

Max. 3 W

Input signal

Indication

Power failure memory
method

Contact or open collector input   Input impedance: Max. 1 k

; Residual voltage: Max. 2 V

Open impedance: 100k

or less, Max. energized voltage: 40V DC

7-segment LCD

EEP-ROM (Min. 10

5

overwriting)

Time 
accuracy
(max.)

Contact

Life

Electrical

Mechanical

Operating time fluctuation

Voltage error

Temperature error

Setting error

Contact arrangement

Contact resistance 
(Initial value)

Contact material

Mechanical (contact)

Electrical (contact)

Allowable operating 
voltage range

Breakdown voltage
(Initial value)

Insulation resistance
(Initial value)

Operating voltage reset
time

Temperature rise

Functional

Destructive

Vibration
resistance

Functional

Destructive

Shock 
resistance

± (0.005 % + 50 ms) in case of power on start

± (0.005 % + 20 ms) in case of input signal start

Rated operating voltage: 85 to 110%
Ambient temperature: –10 to +55°C 

+14 to +131°F

Min. input signal width: 1ms

Timed-out 1 Form C

100 m

(at 1 A 6 V DC)

Ag alloy/Au flash

2.0 

×

10

7

ope. (Except for switch operation parts)

1.0 

×

10

5

ope. (At rated control voltage)

Timed-out 1 Form A (Open collector)

1.0 

×

10

7

ope. (At rated control voltage)

85 to 110 % of rated operating voltage

2,000 Vrms for 1 min: Between live and dead metal parts
2,000 Vrms for 1 min: Between input and output

2,000 Vrms for 1 min: Between input and output
1,000 Vrms for 1 min: Between contacts

Between live and dead metal parts

Min. 100 M

: Between input and output               (At 500V DC)

Between contacts

Max. 0.5 s

10 to 55 Hz: 1 cycle/min single amplitude of 0.35 mm 

.014 inch

(10 min on 3 axes)

10 to 55 Hz: 1 cycle/min single amplitude of 0.75 mm 

.030 inch

(1 h on 3 axes)

Max. 65° C 

(under the flow of nominal operating current at nominal voltage)

Min. 98 m 

321.522 ft.

/s

2

(4 times on 3 axes)

Min. 294 m 

964.567 ft.

/s

2

(5 times on 3 axes)

Operating
conditions

Ambient temperature

Ambient humidity

Air pressure

Ripple rate

Connection

Protective construction

–10° C to 55° C 

+14° F to +131° F

Max. 85 % RH

860 to 1,060 h Pa

8-pin type

IEC standards IP66 (front panel with rubber gasket)

20 % or less

20 % or less

LT4HL  02.1.9 6:25 PM  Page 2

Содержание LT4H-L

Страница 1: ...lay DIP switches Set time display Time units display Up keys Down keys Controlled output indicator Reset indicator Lock indicator Reset switch Lock switch TIMER LT4H Countdown time display Product typ...

Страница 2: ...ontact Electrical contact Allowable operating voltage range Breakdown voltage Initial value Insulation resistance Initial value Operating voltage reset time Temperature rise Functional Destructive Vib...

Страница 3: ...between the unit and installation panel is lost LT4H TIMER RESET LOCK UP h m s OP RST LOCK DOWN M48 M1 890 M44 5 M1 752 55 6 2 189 14 5 571 5 5 217 7 5 295 Embedded installation front panel installat...

Страница 4: ...of the set time in the subtraction direction downwards P RESET switch Resets the elapsed time and the output LOCK switch Locks the operation of all keys on the unit 9 8 7 2 3 4 5 6 11 10 DOWN UP LOCK...

Страница 5: ...power outage countermeasure func tion The output remains ON even after the power is cut and restarted After timer completion stops at the display of the set value addition or stops at 0 sub traction I...

Страница 6: ...1 2 and 3 on the side of the timer as shown Clears elapsed time value at power ON Time delay starts at start ON Ignores start input during time delay In order to have the time delay start at power ON...

Страница 7: ...ted transformer Single coil trance AC power supply AC power supply Fig A Input contact point or transistor Input terminal Power supply 1 2 7 1 2 7 Input terminal Fig B Input contact point or transisto...

Страница 8: ...an 40V DC because it may destroy the internal circuitry 5 Transistor output 1 Since the transistor output is insulated from the internal circuitry by a photocoupler it can be used as an NPN output or...

Страница 9: ...1 496 Rear terminal socket Part No AT78041 31 4 dia 1 236 dia 32 5 dia 1 280 dia 34 6 1 362 26 1 024 8 6 339 8 315 30 dia 1 181 dia 14 dia 551 dia 1 2 3 4 5 6 7 8 31 4 dia 1 236 dia 34 6 1 362 30 dia...

Страница 10: ...terproofing characteristic is lost 4 Installation Loosen the screws on the mounting frame spread the edge of frame and remove it 5 Correctly connect the pins while seeing the pin connection diagram 6...

Страница 11: ...o n l i n e c o m p o n e n t s c o m 11 LT4HL 02 1 9 6 25 PM Page 11...

Страница 12: ...shita Electric Works China Co Ltd Shanghai Branch Office Guangzhou Matsushita Electric Works China Co Ltd Guangzhou Branch Office Dalian Matsushita Electric Works China Co Ltd Dalian Branch Office She...

Отзывы: