background image

Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.

For  optimum  performance,  2  to  3  equivalent  diameters  of  straight 

duct should be installed prior to the inlet of the unit.   Rectangular 

discharge opening is designed for a flanged duct connection. A clear 

area around the opening has been left for screw penetration. Fasten 

and seal all connections by method prescribed in the job specification.

Minimum Access

Make appropriate accommodations for access panel removal. If unit 
is to be installed in 

hard ceiling/wall application

, refer to Nailor 

fan powered terminal unit submittals for specific dimensions before 

installing to assure there is access to the unit and components after 

installation is complete. Nailor 35S fan powered VAV terminal units 
have  access  panels  on  the  top,  bottom  and  side.  Nailor  35N  units 
have only bottom panels. Model 37S and 37N have top and bottom 

panels. Removable top and bottom access panels are secured as 
standard with screws. However, if the ¼ turn fastener access panel 
option is supplied, the bottom panel screws are replaced with two 
quick-connect latches.

Units  with  a  removable  top  access  panel  are  secured  with  two 

additional screws in the middle for shipping and handling. These 
additional screws can be removed after the unit is hung for quicker 
service if needed.

For low voltage control enclosure access, a minimum of 18" (457) is 
recommended.    Specific  control  enclosure  location  is  indicated  on 

product submittals. Low

 

voltage control enclosures have removable 

covers that are attached with sheet metal screws. High voltage 
controls enclosures have access panels that are equipped with 
hinges. For clearances for full opening of hinged access doors, refer 

to project specifications, submittal sheets and NEC. 

Important:

 

These recommendations do not preclude 

NEC or local codes that may be in effect, which are the 

responsibility of the installing contractor.

Field Wiring

All field wiring must comply with NEC and local codes. Disconnect 

switches are optional. Wiring diagrams can be found on labels 

affixed  to  the  exterior/interior  of  the  control  box  enclosure.  Unless 
specifically  requested  by  customer,  all  units  are  wired  for  a  single 

point connection to the fan and electric heater (if present). All electric 

heaters will be staged per specification.  Motors rated for 277 or 120 
VAC on units with 480 or 208 VAC ratings respectively are always 

connected between the neutral and L1 terminals. The installing 
electrician should rotate the incoming electric service by phase to 
help balance the building electric load.
Fuse size designates the size of the internal fuse if it is supplied. 

Maximum  Overcurrent  Protection  (MOP)  designates  the  largest 

breaker or fuse in the electrical service panel that can be used to 
protect the unit. See Table 1 for calculation details.

Electrical Suggestions and Requirements

1. Provide a safety disconnect per NEC 424-19, 20, 21.

2. Disconnect the power supply before wiring or servicing unit. If+  a 

disconnect switch is present, it should be in the OFF position while 

making power connections or repairs.

3. All units with electric heat should have copper wires sized for minimum 

circuit ampacity (MCA). See Table 1 for calculation details.

4. Follow  wiring  diagrams  and  instructions  mounted  on  the  unit. 

480V/3  phase  heaters,  for  example,  require  a  neutral  wire  in 
addition to the full sized ground wire. NEC 424-15 and 250 also 

require that all units be grounded.

Water Pipe Connections

Exercise extreme caution during "sweating" or brazing process of coil 

piping to avoid applying excessive heat to components associated 
with valve package. This could cause irreversible damage, requiring 
immediate replacement of parts. Make sure valves are in full open 

position during brazing process. Heat can be dissipated more 
effectively by wrapping a wet towel around the valve body during the 
brazing process. 

Control Start-up and Operation

Your local Nailor Representative can provide detailed information 
about start-up and operating procedures for Nailor’s digital, analog, 

and pneumatic controls. For specific information on controls provided 

by other manufacturers contact the control manufacturer’s local or 

national office. This applies whether the controls were factory or field 

installed.

NOTE

Note:

 

Digital controllers may use specific communication 

addresses based on Building Management Systems, 

Architecture and original engineering drawings. 

Installing the terminal in a location other than that noted 

on the label may result in excessive start-up labor.

Primary Air Damper and Fan Adjustment

Before starting the fan motor:

a. If filters are required, make sure they are installed as intended.

b. Make sure duct system is clear of all debris and foreign objects. 

c. Ensure unit enclosure, blower housing and blower wheel are free 

of any debris and foreign objects. 

Starting the fan motor:

1. Start  motor  and  let  it  run-in  at  least  15  minutes.  During  run-in, 

check ductwork connections for leaks and repair if necessary.

2. All  Nailor  fan  powered  VAV  terminal  units  incorporating  PSC 

motors use a solid state SCR speed controller to adjust motor 
speed and consequently air volume. Speed controllers have built-in 
maximum and minimum stops as detailed on the fan performance 

pages in the Nailor VAV Terminal Unit catalog. Turning the manual 

fan speed control counterclockwise will increase the fan speed; 
clockwise will decrease speed. The fan speed control is located 
on the side of the motor controls enclosure.

3. For series units, set the unit to full cooling. Adjust and set primary 

maximum  cfm  by  measuring  the  airflow  with  a  manometer 

attached between the gauge ports in the pneumatic tube leading 
to the high and low sides of the inlet air pick-up. A chart is attached 

to the side of the unit showing airflow vs. pressure for different inlet 

sizes. Adjust and set remote balancing dampers, if present. Do not 

worry about airflow at this time; just proportion the outlets with the 

dampers. Be sure to leave the dampers in the most possible open 
position. This will generate the minimum noise level. Adjust the fan 
speed control until the required CFM is obtained (by measuring 
the air quantity at the room outlets or by zeroing the induction air if 
primary and fan match).  Fan should be adjusted with primary air 
at maximum set point to ensure that no supply air is discharged at 

the induction port. Recheck the fan and primary airflows when the 

damper is reset to the minimum set point.

4. For parallel units, turn the fan off, and set the primary air in the 

same manner as described for series units. Proportion the diffusers 
as above. Reset the primary airflow to the design fan turn-on point. 
Measure  the  airflow  again  to  verify  proper  airflow.  Turn  the  fan 

on. Allow the primary air damper to come under control after the 

fan is started, and then adjust the fan until the prescribed airflow 

is achieved by measuring the air quantity at the room outlets. Be 
sure to allow the primary air damper to stabilize after each fan 

adjustment and prior to measuring the airflow. Turn the fan off and 
verify the minimum airflow point on the damper.

5. For units equipped with ECM motors, set the primary air dampers 

as described in (3). Set the fan as described on the ECM MOTORS 
IOM, page 1. Proportion the dampers after the fan is set. Remember 

to adjust the dampers so that they are in the most open condition 
after proportioning. This will generate the minimum noise.

Page 2 of 10

7-6-23   IOM-FPTU

Содержание 35S

Страница 1: ...ing barriers where applicable and always have a fire extinguisher accessible Caution Any improper product handling installation servicing or operation resulting in personal injury and property damage...

Страница 2: ...ciated with valve package This could cause irreversible damage requiring immediate replacement of parts Make sure valves are in full open position during brazing process Heat can be dissipated more ef...

Страница 3: ...ther reverse the procedure Be sure to align the blower set screw with the flat section of motor shaft NOTE Note Over tightening motor mounting screws may crush isolation bushing causing excessive fan...

Страница 4: ...ound 182 5 Round 325 6 Round 455 7 Round 657 8 Round 899 9 Round 1158 10 Round 1497 12 Round 2048 14 Round 2742 16 Round 3683 14 x 8 Rect 2035 14x10Rect 2417 18 Oval 4323 CFM K x P ALLOWABLE PNEUMATIC...

Страница 5: ...CR SCR Elect Heat controller 600V 1ph 45A H1 2064 EC SSR SSR Elect Heat controller 600V 1ph 45A H1 2082 ECM Motor Wiring harness EC HARNESS1 Wiring Harness Card to ECM 16 Pin H1 1104 EC HARNESS2 Wirin...

Страница 6: ...199 VH1 1810 Filter 1 MERV8 16x16 H1 1810 6 VH1 1529 Filter 1 17x18 H1 1529 VH1 1529A Filter 1 MERV8 17x18 H1 1529A 7 2 VH1 0196 Filter 1 14x16 H1 0196 VH1 0196A Filter 1 MERV8 14x16 H1 0196A Model 37...

Страница 7: ...2270A 35N_Size5_ALL_E 6 MTR35NECMS6 ECM Motor 35N Size 6 120 277V H1 2270A 35N_Size6_ALL_E Model Series 35SXC Unit Size RAPP Code Description Part Number Program 1 MTR35XECMS1A V4 H1 3146 35S ST_XC _1...

Страница 8: ...TR35NPSCS3B PSC 35N Size 3 1 4 HP 208V Cap H1 2591S H1 0878 3 MTR35NPSCS3C PSC 35N Size 3 1 4 HP 277V Cap H1 2592S H1 0878 5 MTR35NPSCS5A PSC 35N Size 5 1 2 HP 120V Cap H1 2596S H1 0877 5 MTR35NPSCS5B...

Страница 9: ...35NHWC13 HW Coil 35N 1 Row Size 3 H1 1254 5 V35NHWC15 HW Coil 35N 1 Row Size 5 H1 1257A 6 V35NHWC16 HW Coil 35N 1 Row Size 6 H1 1260 2 V35NHWC22 HW Coil 35N 2 Row Size 2 H1 1252 3 V35NHWC23 HW Coil 35...

Страница 10: ...ibution Solutions Houston Texas Tel 281 590 1172 Fax 281 590 3086 Las Vegas Nevada Tel 702 648 5400 Fax 702 638 0400 Toronto Canada Tel 416 744 3300 Fax 416 744 3360 Calgary Canada Tel 403 279 8619 Fa...

Отзывы: