DF Series installation manual  

25

 

www.nagasinnovation.com 

FIREYE AND HONEYWELL TROUBLESHOOTING CHECK LIST

 

SYMPTOMS 

ACTIONS 

 OPEN AIR PRESSURE SWITCH 

CODE 21 FIREYE 
CODE 32 HONEYWELL 
NOTE: While the heater is in 
operation, the safety contacts 
located between terminals 6 and 8 of 
the FIREYE relay and terminals 6 and 
7 of the HONEYWELL relay must be 
closed. 

There are three safety devices in series between terminals 6 and 7 of the HONEYWELL flame 
safeguard relay and between terminals 6 and 8 of the FIREYE flame safeguard relay. 

A) Low air pressure switch 
(set at 0.2 inch of water) 

The low air pressure switch 
will open when there is 
insufficient airflow and cause 
an alarm. 
Its contacts are normally 
open (N.O.) when the blower 
starts and it closes if the 
differential pressure at the 
burner exceeds 0.25 inch of 
water (see the Start-up 
Instructions section for more 
information on the 
adjustment of the burner 
profile plate). 

AT START UP 

1. The static pressure drop in 
the air ducts exceeds the 
specifications. 
2. Check the size of the 
pulleys and adjust or change 
them if necessary. 
3. Adjust the opening of the 
profile plate if necessary. 
4. Check the blower rotation. 

WHEN HEATER IS IN USE 

1. Check condition of filters. 
2. Check condition of belts. 
3. Look for duct work 
modifications. 
4. Check fresh air damper 
operation. 
5. Replace the defective 
switch. 
6. Refer to the manufacturer. 

B) High air pressure switch 
(set at 1.2 inches of water) 

The high air pressure switch 
will open when there is 
excessive airflow and cause 
an alarm. 
Its contacts are normally 
closed (N.C.) and open if the 
differential pressure at the 
burner exceeds 1.2 inches of 
water (see the Start-up 
Instructions section for more 
information on the 
adjustment of the burner 
profile plate). 

AT START UP OR WHEN THE HEATER IS IN USE 

1. The duct work static pressure drop does not meet the 
specifications. 
2. Check size of pulleys and adjust or change them if 
necessary. 
3. Adjust profile plate opening if necessary. 
4. Replace the defective switch. 
5. Refer to the manufacturer. 

C) Safety high temperature 
limit switch (set at 160°F) 

Its contacts are normally 
closed (N.C.) and opens 
when the temperature of the 
air after the burner exceeds 
160°F. 

AT START UP OR WHEN THE HEATER IS IN USE 

1. Check air temperature after the burner (the safety high 
temperature limit switch opens at 160°F). 
2. Check modulation of the Maxitrol valve and controls as well 
as the amplifier and temperature signal. 
3. Check gas pressure at the burner when set at high fire. 
4. Replace defective switch. 
5. Refer to the manufacturer. 

GROUND FAULT 

CODE 54 FIREYE 

1. Check for proper grounding of the heater. Check for proper grounding of the flame 
safeguard relay. 
2. Check for faulty ground in the wiring between the heater and the electrical distribution 
panel. 
3. Refer to the manufacturer. 

✓

FAULTY PROGRAMMER 

CODE 55 FIREYE 

1. Replace the programmer. 
2. Refer to the manufacturer. 

✓

FAULTY AMPLIFIER 

CODE 56 FIREYE

 

1. Replace the amplifier. 
2. Refer to the manufacturer. 

 VOLTAGE DROP 

CODE 5 HONEYWELL 

1. While heater is in operation, check voltage at relay. 
2. Check electrical connections and relay installation. 
3. Refer to the manufacturer. 

 GROUND FAULT 

CODE 109 HONEYWELL 

1. Check for proper grounding of the flame safeguard relay. 
2. The main current and neutral wires are inverted. 
3. Refer to the manufacturer. 

 

Содержание DF SERIES

Страница 1: ...DIRECT GAS FIRED AIR HEATER DF SERIES INSTALLATION AND OPERATION MANUAL CUSTOM GAS SOLUTIONS LEGENDARY PERFORMANCE...

Страница 2: ...y read the installation start up and maintenance instructions before installing or servicing this unit GAS ODOR If a gas odor is detected 1 Open all windows 2 Do not touch any switches 3 Extinguish al...

Страница 3: ...N 6 2 GAS CONTROL PANEL INSTALLATION 7 3 GAS PIPING CONNECTIONS 8 4 ELECTRICAL CONTROL SENSORS CONNECTIONS 9 5 AIR PRESSURE SWITCH CONNECTION 10 6 IGNITION AND FLAME DETECTIONS CONNECTIONS 10 7 START...

Страница 4: ...FPA 70 in the USA and all local applicable codes for this category of equipment All electrical installations must comply with the electric diagrams of the heater For more information refer to the star...

Страница 5: ...plate installation 2 Control panel installation 3 Gas piping connections main burner pilot and vents 4 Electrical control sensors connections 5 Differential pressure switches connections 6 Ignition w...

Страница 6: ...g to allow the insertion of the profile plate at the chosen location CLEARANCES TO BE RESPECTED Table of clearances Model F G H in mm in mm in mm DF 25 50 75 100 1 25 6 152 30 762 DF 150 12 305 DF 200...

Страница 7: ...th of the control panel length TYPICAL PIPING SCHEMATIC OF AN INSTALLATION WITH THE PANEL MOUNTED DIRECTLY ON UNIT TYPICAL PIPING SCHEMATIC OF AN INSTALLATION WITH THE PANEL REMOTELY MOUNTED FROM UNIT...

Страница 8: ...BH and less Use external gas regulator to reduce to psig From 751 to 1000 MBH 1 From 1001 to 2500 MBH 1 1 1 From 2501 to 5000 MBH 2 1 2 5001 MBH and more 3 2 3 Pilot vent and bleed valve pipe size NPT...

Страница 9: ...of operation of the electrical diagram must never be modified without consulting the manufacturer Electrical controls location Installed by others Items Description All wires must comply with codes a...

Страница 10: ...ropriate hardware to pass the tubes through unit wall 6 IGNITION AND FLAME DETECTIONS CONNECTIONS SNAPPING BUSHING IF DOUBLE WALL RUBBER GROMMET BLACK PLASTIC TUBE PROFILE PLATE PROFILE PLATE SUPPORT...

Страница 11: ...H GTO 15 Red with blue stripe 13mm 4 Pilot gas tubing With ultra violet flame detector Components Description Wire gauge Color Hole diameter to drill in wall5 1 Pilot ignition wire GTO 15 Black 13mm 2...

Страница 12: ...mation should only be used by a qualified technician for gas equipment installation with qualification cards with knowledge in electricity and ventilation WARNING Smoking is not recommended during the...

Страница 13: ...Pa DF 150 200 300 375 450 550 700 Min 13 w c 3235 Pa Min 11 w c 2734 Pa Max 14 w c 3484 Pa Max 14 w c 3484 Pa For lower gas pressure consult manufacturer b Ensure that the air is completely purged fr...

Страница 14: ...r profile plate is too high or too low the unit will not function properly This could produce an excess of carbon monoxide CO or trigger a FLAME FAILURE alarm b To measure the differential pressure at...

Страница 15: ...to the value indicated in the graph below 40 35 30 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 0 4 0 5 0 6 0 7 0 8 40 36 32 28 24 20 16 12 8 4 0 4 8 12 16 20 24 28 32 36 4...

Страница 16: ...ing of the profile plate by moving the adjustment plates closer to the burner g If the differential pressure reading is higher than the desired value enlarge the opening of the profile plate by moving...

Страница 17: ...mperature 20 F 29 C Desired final temperature 70 F 21 C Temperature rise T 90 F 50 C b When the outside temperature does not allow for the simulation of the specified temperature rise across the burne...

Страница 18: ...utside air temperature permits full fire M511 M611 or ES371 MR212 FINAL AIR TEMPERATURE ADJUSTMENT a Set the MAXITROL temperature selector TD 114 to the desired final temperature This selector is loca...

Страница 19: ...e following checks must be performed a Verify the alarm code on the flame supervision relay and consult the troubleshooting section of this manual b Set the main power switch to OFF c Ensure that all...

Страница 20: ...e selected set point of the temperature selector 10 OPERATING SEQUENCE FOR DOUBLE VOLUME DIRECT FIRED HEATER For guidance only Starting up the burner a Create a heating demand b If outside temperature...

Страница 21: ...it switches are closed and terminal 6 is energized c The PTFI light is ON only during the pilot ignition cycle d The FLAME light is ON only when the flame safeguard relay detects a flame signal and is...

Страница 22: ...n and operation manual of the flame relay manufacturer for any code not listed in this table CONSULT THE FIREYE TROUBLESHOOTING TABLE TO ESTABLISH THE DIAGNOSTIC Trouble code Trouble description alarm...

Страница 23: ...ng demand b The PILOT light is ON when there is a heating demand and the pilot control valve coil as well as the ignition transformer is energized c The FLAME light is ON when the flame safeguard rela...

Страница 24: ...el it should be set to BURNER 3 Check the outside temperature thermostat it prevents the burner from running if the outside temperature is over 70 F 4 Check the burner purge time delay relay 5 Refer t...

Страница 25: ...N C and open if the differential pressure at the burner exceeds 1 2 inches of water see the Start up Instructions section for more information on the adjustment of the burner profile plate AT START UP...

Страница 26: ...provided LOW FIRE PULSATING OR ERRATIC FLAME OR IMPROPER CAPACITY 8 Incorrect low fire adjustment 9 Excessive negative pressure at burner 8 Make sure that low fire is properly adjusted There should b...

Страница 27: ...orrespond to the desired average discharge air temperature 24 Disconnect the room thermostat from terminal 2 of the TD114 21 Correct wiring 22 Adjust the TD114 23 Move the TS114 to a location where th...

Страница 28: ...ct thermostat ______ F Pre purge delay ______sec Start up delay on low fire ______sec Inlet temperature thermostat ______sec Profile plate openings _______ X _______ _______ X _______ Main fixed Auxil...

Отзывы: