I want DHCP
is preselected to set up the network using
dynamic IP addressing. The Modbus Gateway is set up at
the factory to receive an IP assignment from a DHCP
Server. If a DHCP Server is not available on your network, it
will default to
169.254.102.39
.
If a DHCP server is not available and the default address
does not work on your PC, change your PC network
settings to IP Address: 169.254.102.1, Subnet Mask:
255.255.0.0, Default Gateway: 169.254.102.100. If you are
not able to use these settings in your installation, refer to
the user’s manual for directions to change the Modbus
Gateway’s TCP/IP settings.
S
S
e
e
t
t
u
u
p
p
M
M
o
o
d
d
b
b
u
u
s
s
T
T
C
C
P
P
Modbus TCP Settings:
Connect to Port
identifies TCP port used in TCP client
mode. Valid range is 1 to 65535.
Response timeout
is the maximum response time. Valid
range is from 1 to 65535.
TCP Server Settings:
Listen on port
identifies TCP port in TCP server mode.
Valid range is from 1 to 65535.
Limit the number of connections
…Controls the number of
simultaneous TCP clients that can be connected.
“…allow everyone
,” “…
allow specific IP address
” &
“
allow a range of IP addresses
” are
Connection Filter
Mode
options, controlling which TCP clients can connect.
S
S
e
e
t
t
u
u
p
p
P
P
o
o
r
r
t
t
1
1
S
S
e
e
r
r
i
i
a
a
l
l
Change the
Description
of the serial port if needed.
Set the
Mode
to RS-232, RS 422 (4 wire), RS 485 (2 wire)
or RS 485 (4 wire).
Set the
Baud Rate
to control the speed of the port. Valid
speeds range between 75 and 230,400 bits per second.
Set
Data Bits
to control the number of bits in each
character. Only 8 bits is valid when the protocol of the
device connected to the port is RTU.
Stop Bits
controls the number of bits for end of character.
Parity
controls the error checking mode, with options of No
Parity, Odd, Even, Mark and Space.
S
S
e
e
t
t
u
u
p
p
P
P
o
o
r
r
t
t
1
1
M
M
o
o
d
d
b
b
u
u
s
s
Select the
Attached
as
Master
or
Slave
.
Select the
Modbus
protocol to be used, either
RTU
or
ASCII
.
As needed, check option boxes for “
Enable Modbus
broadcast
, “
Enable OBh Exception
” and “
Enable
serial message buffering.
”
Select from 0 to 5
Modbus Serial Retries
.
Enter
Milliseconds Modbus Message Timeout
, from 1
to 65535.
Enter
Milliseconds TX Delay
, from 1 to 65535.
Set up “Port 2 Modbus” the same, only if it has a Port 2.
S
S
e
e
t
t
u
u
p
p
P
P
o
o
r
r
t
t
1
1
I
I
D
D
R
R
e
e
m
m
a
a
p
p
Only use this screen if
Modbus Slave ID
s are to be
remapped.
On each line select a range of serial ports to remap. In the
1
st
box enter the first serial port of the range to remap
From
. Valid port IDs range from 1 to 255.
2
nd
box - enter the last serial port of the range to remap.
3
rd
box - enter starting ID of the range to remap
To
.
The 4
th
box auto fills based on ranges entered in the first
three columns.
Set up “Port 2 Remap” the same, only if it has a Port 2.
S
S
e
e
t
t
u
u
p
p
M
M
o
o
d
d
b
b
u
u
s
s
I
I
D
D
R
R
o
o
u
u
t
t
i
i
n
n
g
g
Only use this screen if
Modbus Slave ID
s are to be re-
routed.
On each line select the range of
ID
s to re-route. In the 1
st
box enter the starting ID. Valid IDs range from 1 to 255.
2
nd
box – enter the last
ID
of the range to re-route.
3
rd
box - enter the
IP Address
or
Port
that has slave
devices attached.
The 4
th
box shows the IP address of the slave device, if
an IP address is chosen in the third box.
S
S
e
e
t
t
u
u
p
p
M
M
o
o
d
d
b
b
u
u
s
s
P
P
r
r
i
i
o
o
r
r
i
i
t
t
y
y
Only use this screen if
Modbus Priority
is to be set.
Enter up to five different priorities, based on
Originating IP
Address
,
Modbus ID
,
Modbus Function Code
, or a
combination of these.
IP Address
sets a static IP address for the Modbus
gateway.
Modbus ID
has a valid range from 1 to 255.
Function Code
has a valid range from 1 to 99.
S
S
a
a
v
v
e
e
a
a
n
n
d
d
L
L
o
o
g
g
o
o
u
u
t
t
If you have completed the configuration, click Save to save
the configuration to the serial server.
To Logout, click the Logout button.
T
T
o
o
T
T
e
e
s
s
t
t
a
a
n
n
d
d
V
V
e
e
r
r
i
i
f
f
y
y
O
O
p
p
e
e
r
r
a
a
t
t
i
i
o
o
n
n
The primary check for correct operation is the device
LEDs. See Section 3 this document for more information.
For advanced information, see the
Modbus Configuration
Manager
menu, at the top of Modbus Gateway Manager
screen.
Select
Diagnostic
for a check of communications status
with attached ESERV-M12T device, and then select the
device for which the communications check is desired.
A report of reply times and ping statistics is generated and
can be saved.
Select
Monitor
to review activity logs of attached ESERV-
M12T devices, then select the device for which logged
information is needed
Logged information includes
Time
,
Source & Destination
,
Type
of event, Subscriber ID
,
Data
collected, and
Information
the Modbus Gateway Manager program has
gathered since current login of the affected device.