(Revised 2011-09-02)
5
HAZARDOUS LOCATION INSTALLATION REQUIREMENTS
1.
This equipment is suitable for use in Class I, Div 2, Groups A, B, C, and D, or unclassified or non-
hazardous locations only.
2.
WARNING:
Explosion Hazard - Substitution of components may impair suitability for Class I,
Division 2.
3.
WARNING:
Explosion hazard, do not disconnect while the circuit is live or unless the area is known to be
non-hazardous.
4.
WARNING:
Explosion Hazard - Do not remove or replace the device unless power has been switched off
or the area is known to be non-hazardous.
5.
Use 60/75ºC rated Copper wire, (0.22Nm) 2 inch-lbs Tightening torque for field installed connectors.
6.
WARNING:
Install only in accordance with Local & National Codes of Authorities Having Jurisdiction.
7.
Class I, Div 2 installations require that all devices connected to this product must be UL listed for the area in
which it is installed.
8.
WARNING:
Damage may occur to the RJ-45 port of the powered device (PD), if the 100-POE4 is not
powered down before disconnecting the Cat5E cable.