Zoning systems seem complex, however the MyZone 2 

system has been designed to dramatically simplify 

the cabling process. The key to its simplicity is in the 

way the different processes have been separated.

a.

 Zone motors connect to the 6P6C

RJ12 damper output sockets.

b.

 MyZone 2 Touch Screen connects

to the touchpad socket.

4.1 Wiring

Shielded cable to all touchpads and sensors is 

recommended to minimise the effects of external 

interference. Cabling regulations apply.  

Cables are to be kept to the maximum 

practical distance from any power cables 

≥240volts (minimum distance 300mm).

Maximum cable length is not to exceed 20m.

28AWG or higher 6P6C RJ12 cable must be used.

The following cables are recommended:

CAB12 (1609219) – six core flat cable for 

damper motors

CAB20IAS (1609221) – five core + shield flat cable 

for all touchpads

Refer to section 5 for crimping instructions.

03 Technical Specifications

04 Installation

Number of Zones

ZoneBoss 3Nm

Belimo 5Nm

2

14.2 VA

12.8 VA

3

19.4 VA

15.8 VA

4

24.5 VA

18.8 VA

5

29.7 VA

21.8 VA

6

34.8 VA

24.8 VA

7

40.0 VA

27.8 VA

8

45.2 VA

30.8 VA

3.1

 

Electrical Requirements

Power input to system – 24 Volts AC +/- 10%

Line Frequency – 50 Hz

3.2 System Power Consumption

The power consumption data in this table 

represents maximum values with all motors 

driving and 2 x LCD touchpads with backlighting 
on. Typical loads will be less than this.

3.3 Environmental requirements

Operating Temperature – 0°C to 60°C 

Altitude – 0m to 2000m 

Operating Relative Humidity – 10% to 80%

Avoid exposure to:

Static electricity

Intense electromagnetic radiation

Dusty conditions

Highly corrosive environments

Excess vibration

3.4 Inputs/Outputs

3.4.1 24 VAC Power Input

3.4.2 24 VAC Zone Motor Outputs

8 x 6P6C RJ12 Socket

3.4.3 Touchpad I/O

2 x 6P6C RJ12 Socket

3.4.4 Spill Zone I/O

8 x Dipswitches – Spill Zone Settings

3.5 Zone Motor Ratings

The MyZone 2 system is specifically designed 

for operation with 24 volt motors. All dampers 

in a MyZone 2 system must have the same 

actuator type. Please refer to the relevant 

Actuator Data Sheet for more details. MyZone 2 

works with three position actuators only.

4  |  MyZone 2 Installation 

Manual

Содержание Myzone2

Страница 1: ...Climate Control System 2 Installation Manual ...

Страница 2: ...01 02 03 04 05 06 Introduction System Overview Technical Specifications Installation Crimping Instructions Commissioning 3 3 4 4 6 7 Contents 2 MyZone 2 Installation Manual ...

Страница 3: ... Although the installation commissioning and operation of the system are simple the actual control process is ingenious The operation can be separated into 3 areas 1 Individual Zone Airflow Management 2 Total Airflow Management 3 Safety Modes 2 1 1 Individual Zone Airflow Management One of the strengths of the MyZone 2 system is the way it handles each zone as an independent entity The zone damper...

Страница 4: ... 3 19 4 VA 15 8 VA 4 24 5 VA 18 8 VA 5 29 7 VA 21 8 VA 6 34 8 VA 24 8 VA 7 40 0 VA 27 8 VA 8 45 2 VA 30 8 VA 3 1 Electrical Requirements Power input to system 24 Volts AC 10 Line Frequency 50 Hz 3 2 System Power Consumption The power consumption data in this table represents maximum values with all motors driving and 2 x LCD touchpads with backlighting on Typical loads will be less than this 3 3 E...

Страница 5: ...ntrol One touchpad on each floor or in each zone is often the case The touchpad has been designed to be mounted using the provided c clip and wall mount box 4 2 3 Motorised Damper The motorised dampers should be fitted in line with the flexible duct Care should be taken to make certain that all dampers motors are of the same type MyZone 2 utilises time proportional modulation and conducts a honing...

Страница 6: ...tion each time Squeeze the handles firmly to set the contacts and secure the cable 05 Crimping Instructions Never insert uncrimped plugs into the sockets Doing so may cause damage to the socket contacts Crimped plugs should insert easily into sockets until the locking tab clicks into place Plugs that have been incorrectly crimped may be difficult to insert and may cause damage to the socket contac...

Страница 7: ...otors supplied and that the system safety mechanisms are operating as intended Using the MZWFTP8 V2 System Configuration settings are accessed by pressing the Zones icon from the Home screen from the Zone Overview Screen press the Settings icon in the top right corner System configuration settings are password protected to prevent accidental tampering The password is 4321 Please see MyZone 2 User ...

Страница 8: ...Climate Control System 2 ...

Отзывы: