Installation 

 

Choosing a Suitable Location 

The detector should be sited so that the occupants of the room fall inside the detection pattern shown opposite). 

 

Avoid positioning the unit where direct sunlight may enter the sensor element. 

 

Do not site the sensor within 1m of any lighting, forced air heating or ventilation. 

 

Do not fix the sensor to an unstable or vibrating surface. 

 

Avoid metallic objects directly in front of the sensor head. 

Note 1. When controlling two circuits, the circuits must be on the same phase. 

2. L/In Ch1 is used to supply the detector with power. 

 

 Wiring Diagram 

 

 

 

 Absence detection 

 

 

To use absence detection a retractive (momentary) switch must be connected between the 2 terminals on the 
diagrams. Note that this will be switching mains voltage. 

 

The unit ships with presence detection as default. To change to absence detection, press and release the 
external switch 5 times within the first minute of power up. The LED will turn on solid for 30 seconds to indicate 
absence mode has been selected. 

 

To change back to presence detection, repeat the above procedure—the LED will flash for 30 seconds to indicate 
presence mode has been selected. 

Note: 

the above adjustments can also be made using the UHS5 or UNLCDHS handsets. See Programming sections. 

 

  

Power-up test procedure 

 

 

When power is applied to the unit, the load will turn on immediately. 

Set the timeout to 10 seconds, vacate the room or remain very still and wait for the load to switch off . 

Check that the load switches on when movement is detected. 

The unit is now ready for programming. 

 
 
 
 
 
 
 
 
 

 

CH1 and CH2 plugs are coded. 
Ensure that the plugs are 
inserted correctly and do not 
apply excessive force 

Содержание MWS6-PRM-2CH

Страница 1: ...with separate lux control on each circuit All functionality isfully programmable using an IRhandset MWS6 PRM 2CH Ceiling Microwavepresence absence detector 2 channel MWS6 PRM 2CH NC Ceiling Microwave...

Страница 2: ...r the adjustable time period has elapsed In either case sensitivity to movement of the Microwave sensor can be adjusted using the Sensitivity parameter HINT To assist in setting the Sensitivity turn o...

Страница 3: ...will be switching mains voltage The unit ships with presence detection as default To change to absence detection press and release the external switch 5 times within the first minute of power up The...

Страница 4: ...o read back the settings stored in a device To read back individual parameters Navigate to the parameter and press the R Read button whilst pointing at the device The handset will click when the param...

Страница 5: ...minaires will always be switched on at level 9 Lux off level Switch level off 9 2 5 7 4 6 9 Lux level setting to switch the luminaires off during occupancy if the ambient light level goes above the se...

Страница 6: ...whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Power Up State On On or Off Select No for a 30 se...

Страница 7: ...olling the channels separately This option can only be used in conjunction with a VITM4 2CH Vitesse Modular marshalling box 2 position switch together Short press on Short press off A single position...

Страница 8: ...vels with Respect to HumanExposureto Radio FrequencyElectromagnetic Fields3kHz300GHz IPrating IP40 Compliance EMC 2004 108 EC LVD 2006 95 EC MWS6 PRM 2CH DBB Part numbers Partnumber Description Detect...

Отзывы: