2.4.
R
EFRIGERANT PIPING CONNECTION
The piping can be run in the 3 directions indicated by numbers in
the picture. When the piping is run in direction 1 or 3, cut a notch
along the groove on the side of the indoor unit with a cutter.
Run the piping in the direction of the wall hole and bind the
copper pipes, the drain pipe and the power cables together with
the tape with the drain pipe at the bottom, so that water can flow
freely.
•
Do not remove the cap from the pipe until connecting it,
to avoid dampness or dirty from entering.
•
If the pipe is bent or pulled too often, it will become stiff.
Do not bend the pipe more than three times at on point.
•
When extending the rolled pipe, straighten the pipe by
unwinding it gently as shown in the picture.
2.5.
C
ONNECTIONS TO THE INDOOR UNIT
1.
Remove the indoor unit pipe cap (check that there is no
debris inside).
2.
Insert the fare nut and create a flange at the extreme end
of the connection pipe.
3.
Tighten the connections by using two wrenches working
in opposite directions.
2.6.
I
NDOOR UNIT CONDENSED WATER DRAINAGE
The indoor unit condensed water drainage is fundamental for the
success of the installation.
1.
Place the drain hose below the piping, taking care not to
create siphos.
2.
The drain hose must slant downwards to aid drainage.
3.
Do not bend the drain hose or leave it protruding or
twiested and do not put the end of it in water. If an
extension is connected to the drain hose, ensure that it is
lagged when it passes into the indoor unit.
4.
If the piping is installed to the right, the pipes, power
cable and drain hose must be lagged and secured onto
the rear of the unit with a pipe connection.