MVE LN2 Tx Скачать руководство пользователя страница 7

PN 15098830 Rev A — 7

Warranty

The warranty on the LN2 TX is described in the warranty state-

ment included with the device.

Maintenance 

No maintenance is required on the LN2 TX.  There are no mov-

ing parts to wear out.

Troubleshooting

If the flow rate is low, make sure that the gas supply valve is fully 

opened and that supply pressure is between 22 and 55 psi.
If the gas supply meets the above requirements, the orifices in the 

suction head at the inlet of the LN2 TX may be partially blocked.  

•  To clean the orifices, disassemble the suction head by 

removing the three screws and separating the two halves of 

the unit.

•  Remove the o-rings and insert inside the unit.
•  Clean the orifices in the outlet end of the insert as required.
•  Reassemble the unit in the reverse order of disassembly, 

making sure that the orifices on the insert face the outlet 

end of the suction head.

Technical Assistance

USA 

1-800-482-2473
[email protected]

EUROPE

 +44 (0) 1344 403 100
[email protected]

AUSTRALIA/PAC RIM

 +61 297 494333
[email protected]

The discharge end of the LN2 TX is shown in Figure 8

 

Figure 8, Discharge end of LN2 TX

Place the discharge end of the LN2 TX as shown in Figure 9.  The 

LN2 TX is equipped with a phase separator to minimize splash.  

The discharge end can be placed in the bottom of the receiving 

container, but flow will be reduced and splash will increase.  The 

transfer will be more efficient if the phase separator is suspended 

above the liquid level in the receiving container.

Figure 9, Discharge end of LN2 TX placed inside the receiving 

container

Once both ends of the LN2 TX are placed in their respective con-

tainers as described above, open the gas use valve on the liquid 

cylinder supply.
Liquid transfer will begin as soon as the transfer device is cooled 

to liquid temperature.  Transfer will continue until the originating 

container is empty, or the suction end is removed from the liquid.
When the transfer is complete; close the gas use valve on the 

liquid cylinder supply.
The rate of transfer is dependent on the flow rate of the gas sup-

ply.  The higher the pressure, the higher the flow rate up to a 

point.  Supply pressure in excess of 50psi will reduce the transfer 

rate due to liquid flashing to gas.

Содержание LN2 Tx

Страница 1: ...fer System OPERATORS MANUAL BioMedical Chart Inc BioMedical Group 2200 Airport Industrial Drive Suite 500 Ball Ground Georgia 30107 This Operators Manual covers use and maintenance of the MVE LN2 TX I...

Страница 2: ...g 7 Technical Assistance 7 Table of Figures Figure 1 LN2 TX 3 Figure 2 Typical cryogenic Dewar 3 Figure 3 Nitrogen Gas connection 6 Figure 4 Nitrogen Gas supply hose connected to the LN2 TX 6 Figure 5...

Страница 3: ...m area in the transfer system thus minimizing flash loss Once the liquid is entrained in the gas stream it is re pressurized to further minimize flash loss N2 Gas Connection LN2 Outlet Flex Transfer H...

Страница 4: ...operated in open and well ventilated areas Persons transferring LN2 should make every effort to protect the eyes and skin from accidental contact with liquid or cold gas issuing from the Dewar Protec...

Страница 5: ...ere are additional safety considerations to keep in mind in the handling of O2 These additional considerations are associated with the oxidizer properties of liquid oxygen DO NOT SMOKE NEAR THE TRANSF...

Страница 6: ...gas use capability is the preferred supply method a high pressure nitrogen gas supply cylinder can be used to supply gas to the LN2 TX A suitable pressure regula tor and hose adapter fittings will be...

Страница 7: ...techservice australia chart ind com The discharge end of the LN2 TX is shown in Figure 8 Figure 8 Discharge end of LN2 TX Place the discharge end of the LN2 TX as shown in Figure 9 The LN2 TX is equip...

Страница 8: ...8 Ln2 Tx Instructions...

Страница 9: ...PN 15098830 Rev A 9...

Отзывы: