Mutec HVT 300-SIL-DX Скачать руководство пользователя страница 12

7/2021 

                                                                                                                                                                                                                                                                                                                                                               

 

 

     

 

  12 

 

 

 

6  Jumper (Option)  

Jumper JP1 und JP2: 
Depending on the position of the jumper JP1 for the contact of the relay REL-1, this is 
made available as a break or make contact at the terminals T-1 and T-2. Depending on 
the position of the jumper JP2 for the contact of the relay REL-2, this is provided as a 
break or make contact on the terminals T-6 and T-15.

 

 

Der Zugang zu den Jumpern erfolgt über entsprechend gekennzeichnete Ausbrüche auf 
der rechten Seite des Hutschienengehäuses.

  

 

 
 

7  Loop resistance mA Output 

 

 

Analog output (AA) data for constant current: max. 22 mA at a load ≤ 500 Ω 

 

The maximum load for the analog output is the sum of the forward and return lines and the 
input resistance (shunt) of the following module:

 

 

   

      R

Load, max

 =  2x R

Line

 + R

Shunt   

≤  500 Ω

 

 

 

The following applies to the line resistance:

 

   

      R

Line

  

=   l x ϱ x A

-1

  

[Ω]

   

         

  

ϱ  =  0,0178           [Ω mm

2

 m

-1

]

    

       

 

 

 

 

 

 

 

 

        

A  =  0,25 x d

2

 x 

π

  [mm

2

]

 

Maximum line length (distance):

 

   

      

l   =  0,5 (500 Ω 

- R

Shunt

) x ϱ

-1

 x A    [m] 

 

 

Wire length depending on the wire cross section and the shunt resistor:

 

 

 

     R

Shunt

 

 

            

[Ω]

 

L

diameter

 

 

[mm]

 

  

L

cross-section

 

[mm

2

]

 

 L

Length 

 

[m]

                                  

 

L

Length

 

[km]

 

 

        100

 

0,6

 

0,283

 

3179

 

3,18

 

 

 

0,7

 

0,385

 

4325

 

4,33

 

 

 

0,8

 

0,502

 

5640

 

5,64

 

 

 

0,9

 

0,636

 

7146

 

7,15

 

 

 

1,0

 

0,785

 

8820

 

8,82

 

 

 

     R

Shunt

 

 

            

[Ω]

 

L

diameter

 

 

[mm]

 

    

L

cross-section

 

[mm

2

]

 

 L

Length

 

[m]

                                  

 

L

Length 

 

[km]

 

 

        

200

 

0,6

 

0,283

 

2385

 

2,39

 

 

 

0,7

 

0,385

 

3244

 

3,24

 

 

 

0,8

 

0,502

 

4230

 

4,23

 

 

 

0,9

 

0,636

 

5360

 

5,36

 

 

 

1,0

 

0,785

 

6615

 

6,62

 

 

 

     R

Shunt

 

 

            

[Ω]

 

L

Durchmesser

 

 

[mm]

 

  

L

Querschnitt

 

[mm

2

]

 

 L

Länge 

 

[m]

                                  

 

L

Länge

 

[km]

 

 

        300

 

0,6

 

0,283

 

1590

 

1,59

 

 

 

0,7

 

0,385

 

2163

 

2,16

 

 

 

0,8

 

0,502

 

2820

 

2,82

 

 

 

0,9

 

0,636

 

3573

 

3,57

 

 

 

1,0

 

0,785

 

4410

 

4,41

 

 

Содержание HVT 300-SIL-DX

Страница 1: ... of an error The absolute value of the measured DC voltage is output as a 0 4 20 mA signal For signaling the safety function 2 relays and the mA output are available which can be interconnected with each other or with the alarm outputs 1 and 2 WARNING high voltage risk of death The device is electrical equipment with voltage inputs for up to 1000 VDC It is designed for use in secure operating envi...

Страница 2: ...nsmission and duplication of this document as well as utilization and disclosure of its content are prohibited unless expressly permitted Any breach or infringement shall result in liability for damages The software described in this document is licensed and may only be used and copied in accordance with the terms of the licence All rights reserved Disclaimer We have checked the content of the pri...

Страница 3: ...10 7 4 6 Status LEDs 8 4 7 USB Interface front socket 8 4 8 RS485 Interface T BUS contacts T B1 T B2 8 4 9 Supply Terminals T 3 T 4 or T B4 T B5 8 4 10 General Data 8 4 11 Standards 9 4 12 Self Monitoring 9 4 13 Installation 9 4 13 Electrostatic Discharge 9 4 14 Housing Dimensions 10 4 15 Block diagram 10 4 16 Nameplate 11 5 Variants of Input Connections 11 5 1 Absolute Value Measurement 11 5 2 Re...

Страница 4: ...nstructions are highlighted using a triangular warning sign and shown as follows depending on the degree of risk HAZARD means that death or severe physical injury will occur if the appropriate precautionary measures are not taken WARNING means that death or severe physical injury may occur if the appropriate precautionary measures are not taken CAUTION with a triangular warning sign means that min...

Страница 5: ... operation of this device requires proper transport proper storage installation and assembly as well as careful operation and maintenance The device may only be used for the purposes specified in this operating manual DISCLAIMER All modifications to the device fall within the responsibility of the user unless expressly specified otherwise in the operating manual VALIDITY The data sheet is only val...

Страница 6: ...age Do not remove any protective cover blind cap between the terminal blocks or cables on the terminals during operation Suitable effective protective circuits must be provided for inductive loads on the relay circuits The protective circuit with suppressor diodes or varistors must always be in parallel with the load BROKEN DEVICE The device may be damaged after an error Correct and safe operation...

Страница 7: ...teresis freely configurable between 0 99 9 Operating mode open or closed current principle Alarm function Signal monitoring and indication of maintenance requirement Switching power max 62 5 VA max 30 W Switching voltage max 125 V AC or 110 V DC Switching current max 1 A Min contact voltage 10 mVDC Min contact current 10 µA Contact material AG Pd 10 µAu Relay type according to IEC 947 5 1 EN60947 ...

Страница 8: ...sport 20 C 70 C Perm Humidity 10 95 r H without condensation Max operating altitude 2000m above mean sea level Temperature coefficient Maximum 0 01 K Typical 0 005 K Galvanic isolation 3 port isolation Input output supply Input Output 4 3 kV AC test voltage Input Supply 4 3 kV AC test voltage Overvoltage category CAT II 1000 V AC DC pollution level 1 according to IEC 61010 1 Electrical connection ...

Страница 9: ...h 8A maximum contact load Gold plating ensures high contact quality Designed for mounting to NS 35 7 5 or NS 35 15 DIN rails Important note The device may only be attached to or removed from the TBUS Connection when power is switched off Attach the housing to a 35 mm DIN rail according to EN 60715 For installation mount the snap lock to the DIN rail and lock it For dismounting use a screw driver t...

Страница 10: ...7 2021 10 4 14 Housing Dimensions 4 15 Block diagram Fig 2 Fig 3 ...

Страница 11: ...e detected by the transmitter with 0 VDC since the connection to the Measurement input E1 is interrupted However the maximum voltage value in the signal source could still be 1000 VDC and mean a massive danger or danger to life 5 2 Redundant Absolute Value Measurement A line break monitoring is available for all 4 input lines if the measurement signal has a value 0 V The transmitter then detects t...

Страница 12: ...ard and return lines and the input resistance shunt of the following module RLoad max 2x RLine RShunt 500 Ω The following applies to the line resistance RLine l x ϱ x A 1 Ω ϱ 0 0178 Ω mm2 m 1 A 0 25 x d2 x π mm2 Maximum line length distance l 0 5 500 Ω RShunt x ϱ 1 x A m Wire length depending on the wire cross section and the shunt resistor RShunt Ω Ldiameter mm Lcross section mm2 LLength m LLengt...

Страница 13: ...lways closed The safety related mA output can also be integrated for reporting the safety function as shown in Figure 9 This enables the highest availability of the safety function The permissible deviation from the setpoint between 0 2 and 5 0 can be parameterized for the analog output as well as for the input signal Any exceeding of these limit values is recognized as an error and signaled exter...

Страница 14: ...limit The operating mode with a low request rate is used as a basis The proportion of the MSK 200 SIL DX at the PFDAVG value of the entire safety chain should not exceed 30 Signal source 35 MSK 200 SIL DX 30 Signal processing PLS 35 Conditions The failure rates of the components used are constant over the period of use The spread of errors by the device in the system is not considered The repair t...

Отзывы: