background image

SPL/45-94117B page 4 of 4

h t t p : / / w w w . f w m u r p h y . c o m

Find us on the internet:

Range

250 =

15 to 250°F

350 =

130 to 350°F 

450 =

260 to 450°F

Armor / Capillary / Bulb

P =

PVC / Copper / Copper

S =

Stainless steel / Stainless steel / Stainless Steel

Capillary Length

Specify in feet

Specify in metres

05 =

5 feet

1.5M =

1-1/2 metres

10 =

10 feet

2M =

2 metres

Etc.

Etc.

5 ft. increments available to 30 ft., thereafter 10 ft.
increments only. Some ranges are not available
over 50 ft.

Base Model

SPLC
SPLCE
SPLFC
SPLBP*
SPLBPE*

45TE
45TEE
45TEF
45TEBP*
45TEBPE*

Options

NOTE: 

Verify option availability. Not all options can be

provided for every model.

BC

=  Capillary tubing exits from back of case

ES

=  Environmentally sealed for isolation from 

the elements

EX

= Explosion-proof; SWICHGAGE

®

enclosed 

within explosion proof case; Class I, Division 1,
Groups C & D

EL

=  (EXLC) Explosion-proof less case; internal gage 

mechanism only–without case

LC

= Less case; SWICHGAGE

®

mechanism and 

hardware connections–without case

OS

=  Liquid filled case for resistance against corrosion,

environment, vibration and electrical arc

TA

=  (TCA) Tickler contact; includes 1 auxiliary con-

tact (tickler) and 2 limit contacts (all-face-
adjustable-SPL series)

Specify model number. 

NOTE:

No designator is required for 

Standard

configurations. 

Also, list options in alphabetical order (A to Z). Place a dash (–) between each option. See example below.

SPLBP – 4 – 350 G 10 – EX

How to Order

Latching Control Relay Voltage (applies to “BP” models only)

Blank =

120 VAC

2 =

12 VDC

4 =

24 VDC

*

This version not covered by CE mark.

Warranty

A limited warranty on materials and workmanship is
given with this FW Murphy product. A copy of the
warranty may be viewed or printed by going to
www.fwmurphy.com/support/warranty.htm

Tamperproof Contact Accessory

Knob
Lock

Limit
Switch
Knobs

Order 05000610

CONTROL SYSTEMS & SERVICES DIVISION

P.O. Box 1819; Rosenberg, Texas 77471; USA
+1 281 633 4500  fax +1 281 633 4588 

e-mail

[email protected]

MURPHY DE MEXICO, S.A. DE C.V.

Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje 
San Luis Potosí, S.L.P.; México 78384 
+52 444 8206264  fax +52 444 8206336
Villahermosa 52 993 3162117

e-mail

[email protected]

www.murphymex.com.mx

FRANK W. MURPHY, LTD.

Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K.
+44 1722 410055  fax +44 1722 410088  

e-mail

[email protected]

www.fwmurphy.co.uk

In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.

FW Murphy

P.O. Box 470248
Tulsa, Oklahoma 74147 USA 
+1 918 317 4100  

fax

+1 918 317 4266  

e-mail

[email protected]

www.

fwmurphy

.com

Printed in U.S.A.

Содержание Temperature SWICHGAGE SPL

Страница 1: ...Wire Connections Surface mount models 1 2 NPT conduit and terminal block Panel mount models Wire leads 18 AWG 1 0 mm2 x 9 in 229 mm long OS models 1 2 NPT conduit and wire leads 18 AWG 1 0 mm2 x 9 in 229 mm long Item Weight 8 lb 3 6 kg approximately Explosion proof models 22 lb 10 kg approx Item Dimensions 16 x 11 x 5 1 2 in 406 x 279 x 140 mm Explosion proof models 12 x 12 x 9 in 305 x 305 x 229 ...

Страница 2: ...o 121 C 8 F 4 C 2 F 1 C 2 F 1 C 5 in 127 mm 130 to 350 F 60 to 180 C 8 F 4 C 2 F 1 C 3 F 1 5 C 2 1 2 in 64 mm 260 to 450 F 127 to 232 C 8 F 4 C 2 F 1 C 3 F 1 5 C 2 1 2 in 64 mm Minimum Sensing Bulb Insertion into Process Using a Thermowell Start Up Lockout Start Up Lockout Toggle Switch SPLC Series Low Limit Contact TEMPERATURE MURPHY SWICHGAGE TULSA U S A 270 250 220 200 170 350 340 320 300 290 C...

Страница 3: ...E model The 45TE series SWICHGAGE incorporates 2 SPDT snap switches instead of the pointer type contacts of the SPL Unlike the SPL that completes an elec trical circuit as soon as the pointer touches the contact the 45TE trip point indi cators will stop the pointer movement slightly before the switches operate As temperature continues to increase reaching high set point or to decrease reaching low...

Страница 4: ... NOTE No designator is required for Standard configurations Also list options in alphabetical order A to Z Place a dash between each option See example below SPLBP 4 350 G 10 EX How to Order Latching Control Relay Voltage applies to BP models only Blank 120 VAC 2 12 VDC 4 24 VDC This version not covered by CE mark Warranty A limited warranty on materials and workmanship is given with this FW Murph...

Отзывы: