Installation and Operation Instructions for 
SELECTRONIC

®

Speed Switches 

SS300 Series 

SS-97028N

Revised 05-04

Section 20

00-02-0286

Please read the following information before installing

.  

A visual inspection of this product for damage during shipping is rec-

ommended before mounting. It is your responsibility to have a qualified person install this unit and make sure it conforms to NEC
and local codes.

GENERAL INFORMATION

WARNING

BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT

Disconnect all electrical power to the machine.

Make sure the machine cannot operate during installation.

Follow all safety warnings of the machine manufacturer.

Read and follow all installation instructions.

SPEED SWITCH

1

PICKUP

INPUT

-BATT

+BATT

GND. FOR

T/D

POS. TO

LATCH

ENERGIZE

SPEED

ADJ.

DE-ENERGIZE

2

3

4

5

6

7

8

SS300-AD

Description

The SS300 Series are single set point speed switches with SPDT relay dry contact
output. The trip point is set by a potentiometer. An LED indicates when the signal
source is present. A second LED turns on when the trip point is reached. 

See Table 1

for available models and requirements. An optional time delay is on board to delay
operation of the relay for 2-6 seconds after the set point has been reached.

The SS300 Series speed switch is intended for installation within a weatherproof
enclosure to protect it from rain, dust, etc.

Overspeed Shutdown

The SS300 Series shuts down the engine if RPM exceeds the pre-set limit.

Speed Sensitive Pull-in/Drop-out

Engage or disengage PTO’s, 4-wheel drives, other switch points, etc. according
to speed of engine being monitored.

Engine and Transmission Alarm/Shutdowns

Oil pressure in some engines and transmissions varies widely between running
and idle speeds. The SS300 Series can select between two pressure switch set
points according to speed of the engine or transmission and thus give maximum
protection to the equipment while at operating RPM and eliminate nuisance
alarms when at idle.

Adjustable Differential Model

The (“AD”) can be adjusted to change the speed range over which the pull-in and
drop-out differential of the relay will operate. A typical application is to insure
that engine speed is above a minimum RPM before applying a load but allows a
drop in speed of several hundred RPM without disconnecting the load.

Table 1: Models Available and Input Signal

Specifications

Power Requirements: 

12 VDC (9-16 VDC).
24 VDC (18-30 VDC).

Frequency Signal: 

Voltage (all models):

• Minimum Input Voltage Signal: 

4.5 Vrms.

• Maximum Input Voltage Signal: 

50 Vrms.

Reset Differential Magnetic Pickup Signal Models:

• 

“Standard Models: 

2 Hz Differential.

• 

“AD” Models (Adjustable Differential): 6

50-8900 Hz Adjustable

Reset Differential Alternator Models:

• 

“LF” Models (Low Frequency): 

2 Hz Differential

• 

“AD-LF” Models (Adjustable Differential Low Frequency): 

50-1900 Hz Adjustable.

Output:

Relay contact, SPDT, resistive load, 6 A, 30 VDC.

Time Delay:

When terminal 7 is grounded, the relay operation is delayed for 

2-6 seconds after rpm set point is reached. 

Adjustment:

20–turn potentiometer(s).

Temperature Range:

-4° to 185°F (-20° to 85°C).

Relative Humidity:

0 to 95% Non-condensing.

Case:

Black, ABS plastic.

Model Number

Distributor

Ignition

Magnetic 

Pickup

Alternator

SS300 (std. model)

SS300-LF (low frequency)

SS300-AD (adjustable differential)

SS300-AD-LF (low frq. & Adjst. diff.)

Voltage 

12       24

Maximum Current

12V

24V

Pull In

46 mA

46 mA

Pickup only

10.5 mA

16 mA

Frequency Range in Hz

Model Number

25-2000

SS300-LF
SS300-AD-LF

625-9000

SS300-AD 
SS300

Содержание Selectronic SS300 Series

Страница 1: ...rm Shutdowns Oil pressure in some engines and transmissions varies widely between running and idle speeds The SS300 Series can select between two pressure switch set points according to speed of the engine or transmission and thus give maximum protection to the equipment while at operating RPM and eliminate nuisance alarms when at idle Adjustable Differential Model The AD can be adjusted to change...

Страница 2: ...ach Terminal Ignition Switch SS300 4 INPUT 3 2 1 5 BATT 6 BATT 7 8 SPEED GND FOR T D POS TO LATCH Battery Ignition Switch Coil SS300 4 INPUT 3 2 1 5 BATT 6 BATT 7 8 SPEED GND FOR T D POS TO LATCH Figure 1 Magnetic Pickup Input Figure 2 Alternator Tach Input Figure 3 Distributor Ignition Input Figure 5 Energize to Stop Solenoid CAUTION If replacing an SS100 Series model with an SS300 Series model n...

Страница 3: ...00 AD with Clutch Engager The SS300 AD can be applied with a Murphy CO 3 engager Figure 10 The circuit is designed to engage a clutch after engine speed has increased to a preset RPM Example 1200 RPM and disengage clutch when engine speed has decreased to idle Example 600 RPM The adjustable differential SS300 AD relay is set to pull in at 1200 RPM and drop out at 600 RPM Figure 6 Figure 7 Figure 8...

Страница 4: ... potentiometers SPEED ADJ DE ENERGIZE Figure 13 Figure 14 CONTROL SYSTEMS SERVICES DIVISION P O Box 1819 Rosenberg Texas 77471 USA 1 281 633 4500 fax 1 281 633 4588 e mail sales fwmurphy com MURPHY DE MEXICO S A DE C V Blvd Antonio Rocha Cordero 300 Fracción del Aguaje San Luis Potosí S L P México 78384 52 444 8206264 fax 52 444 8206336 Villahermosa Office 52 993 3162117 e mail ventas murphymex co...

Отзывы: