background image

MeCANTM 

00-02-0665

revision D, 19th August 2015 

Mechanical Engine to CAN J1939 interface 

MU� 

section 78 

Installation Instructions 

by 

El{OVATION CONTROLS 

Please read the following information before installing. A 

visual inspection of this product for damage during 

shipping is recommended before installation.  It is your responsibility to ensure that qualified mechanical and electrical 

technicians install this product.  If in doubt, please contact your local Murphy representative. 

General Information 

MeCAN

™ 

is a compact, encapsulated interface module that 

translates resistive sender, fault switch and speed signals into 

SAE J1939 CAN bus data. MeCAN allows quick and simple 

integration of mechanical, non-ECU engines into modern CAN 

bus systems. Applications include the retrofit of older engine 

fleets with modern digital instruments, controls and telemetry 

and the development of standard control panels 

for both ECU 

and non-ECU engines. 

MeCAN has three sensor inputs and one output. Two inputs 

are for oil pressure and coolant temperature sensing, either by 

fault switches or resistive senders. The third input measures 

engine speed, using a magnetic pickup or charge alternator 

signal. Input signals are translated into SAE J1939 CAN bus 

messages with appropriate PGN address, data scaling and 

transmission rate. The shut-down output operates and latches if 

the pressure, temperature or speed inputs deviate outside 

preset fault limits. 
A fourth input is connected to a speed calibration potentiometer 

during set-up mode only. DIP switches allow selection of 

normal/set-up mode and two speed input ranges. An LED 

gives indication of operating mode and CAN bus activity. 

MeCAN is compact and light enough for inclusion in many 

wiring harnesses but can also be surface mounted via four 

fixing holes. The case is fully sealed in epoxy resin for high 

impact and environmental resistance. 

Two standard versions allow use with either fault switches or 

Murphy ES series resistive senders: 

part number 

model/description 

E2501300 

MEC301-1 MeCAN 1/0 module, for use with 

Murphy ES pressure & temperature senders 

E2501200 

MEC301-2 MeCAN 1/0 module, for use with 

pressure & temperature switches (closing to 

negative DC on fault) 

Custom solutions are also available for non-standard, volume 

OEM requirements. 

CE 

Specifications 

Power supply 

Operating voltage, steady state: 7 to 35 voe 

Current consumption: 25mA (typ.) 

Inputs 

Maximum operating range: -2 to +35 voe 

Oil pressure, coolant temperature: 

MEC301-1, E2501300  : for resistive senders,  Murphy ES series 

MEC301-2, E2501200  : for switches, closed to negative DC on fault 

Speed (magnetic pickup): 

opto-isolated, 3 - 30 Vrms, adjustable 10 - 180 pulses per rev 

Speed calibration: O - 5 kOhm potentiometer (setup only) 

Outputs 

Shutdown: negative DC (open collector transistor), 250mA max. 

CAN  bus: 

SAE J1939 protocol, 120 Ohm terminating resistor fitted. 

Physical 

Case material: high impact ABS, epoxy filled 

Dimensions: see diagram below 

Weight: approx 60g 

0.13 lb 

Operating temperature: -20 to +85 °C /-4 to +185 °F 

Environmental sealing: 

IP65 (with DIP switch protective film intact), exposed lead ends 

Electromagnetic compatibility: 2004/108/EC 

Connection and Dimensions 

Dimensions in mm (in.) for reference only. Use actual product for template. 

Standard lead length= approx. 100 mm (4.0 in.) 

Отзывы: